SPEC 84013
3-Layer 15kV AAAC CAMV™ Covered Conductor (Tree Wire or Spacer Cable)
An Alternative and Robust Design to Bare AAAC Conductors to Harden the Electrical Grid.
3-Layer, 15kV, Covered Conductor, Concentrically Stranded AAAC, Track-Resistant Crosslinked Polyethylene.

Construction:
- Conductor:Concentrically stranded aluminum-alloy 6201-T81 wires AAAC
- Strand Shield:Semi-conducting cross linked polymer
- Inner Layer:Low-Density Crosslinked Polyethylene (LDXLPE)
- Outer Layer:High-Density Track-Resistant Crosslinked Polyethylene (HDTRXLPE)
Applications and Features:
Specifications:
Table 1 – Weights and Measurements
| Stock Number | Cond. Size | Cond. Strands | Diameter Over Conductor | Conductor Shield Thickness | Inner Layer Thickness | Outer Layer Thickness | Approx. OD | Approx. Weight | Rated Strength |
|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | # | inch | mil | mil | mil | inch | lb/1000ft | lb | |
| TBA | 48.69 | 7 | 0.250 | 15 | 75 | 75 | 0.580 | 137 | 1584 |
| TBA | 77.47 | 7 | 0.316 | 15 | 75 | 75 | 0.646 | 179 | 2520 |
| 142448 | 123.3 | 7 | 0.398 | 15 | 75 | 75 | 0.728 | 236 | 4014 |
| TBA | 155.4 | 7 | 0.447 | 15 | 75 | 75 | 0.777 | 283 | 4851 |
| TBA | 195.7 | 7 | 0.502 | 15 | 75 | 75 | 0.832 | 334 | 6111 |
| 622448 | 246.9 | 7 | 0.563 | 15 | 75 | 75 | 0.863 | 385 | 7704 |
| TBA | 312.8 | 19 | 0.642 | 15 | 75 | 75 | 0.972 | 473 | 9900 |
| TBA | 394.5 | 19 | 0.720 | 15 | 75 | 75 | 1.050 | 568 | 11970 |
All dimensions are nominal and subject to normal manufacturing tolerances
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Revision: 1.000.005
Updated On: Oct. 9, 2025, 3:02 p.m. UTC

