SPEC 83353
Covered Line Wire With Crosslinked Polyethylene (XLPE)
Aluminum Conductor Covered with Black Crosslinked Polyethylene

Construction:
- Conductor:Solid 1350-H19 aluminum per ASTM B230, compressed stranded 1350-H19 aluminum per ASTM B230 and B231, or concentrically stranded 6201-T81 aluminum-alloy per ASTM B398 and B399
- Covering:Black Crosslinked Polyethylene (XLPE)
Applications and Features:
Aluminum alloy 1350-H19 or 6201-T81 concentrically stranded. Covered with crosslinked polyethylene (XLP). Used primarily for, but not limited to, overhead secondary distribution lines. Installed on insulators, otherwise treated as a bare conductor. Crosslinked covered line wires have the below temperature ratings:
• Normal Service temperature of 90ºC
• Emergency Overload of 130ºC
• Short Circuit temperature of 250ºC
• Normal Service temperature of 90ºC
• Emergency Overload of 130ºC
• Short Circuit temperature of 250ºC
Specifications:
Sample Print Legend:
Solid Conductor:
SOUTHWIRE AWG X AL {MMM/DD/YYYY}
AAC Conductor:
SOUTHWIRE® XXX.X AWG or KCMIL AAC XX MILS XLP
AAAC Conductor:
SOUTHWIRE® XXX.X KCMIL AAAC XX MILS XLP
SOUTHWIRE AWG X AL {MMM/DD/YYYY}
AAC Conductor:
SOUTHWIRE® XXX.X AWG or KCMIL AAC XX MILS XLP
AAAC Conductor:
SOUTHWIRE® XXX.X KCMIL AAAC XX MILS XLP
Table 1 – Weights and Measurements
| Stock Number | Code Word | Phase Cond. Size | Phase Strand | Phase Insul. Thickness | Approx. OD | Approx. Weight |
|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | mil | inch | lb/1000ft | ||
| 104547 | LINDEN | 77.47 | 7 | 45 | 0.406 | 98 |
| 104554 | OILNUT | 123.3 | 7 | 60 | 0.518 | 158 |
| 104570 | SHELLBARK | 195.7 | 7 | 60 | 0.622 | 239 |
| 104331 | HUCKLEBERRY | 477 | 37 | 80 | 0.931 | 540 |
| 104349 | PAW PAW | 556.5 | 37 | 80 | 0.992 | 622 |
| 202127 | BREADFRUIT | 636 | 61 | 95 | 1.081 | 721 |
| 148460 | PERSIMMON | 795 | 61 | 95 | 1.187 | 885 |
| 202135 | GRAPEFRUIT | 1033.5 | 61 | 95 | 1.327 | 1128 |
| TBA | APPLE | 6 | SOLID | 45 | 0.252 | 41 |
| TBA | PLUM | 6 | 7 | 45 | 0.268 | 42 |
| 457350 | PEAR | 4 | SOLID | 30 | 0.264 | 47 |
| 663570 | APRICOT | 4 | 7 | 30 | 0.285 | 50 |
| TBA | HORNBEAM | 4 | 7 | 45 | 0.315 | 60 |
| TBA | CHERRY | 2 | SOLID | 45 | 0.348 | 85 |
| 104240 | PEACH | 2 | 7 | 45 | 0.373 | 83 |
| TBA | NECTARINE | 1 | 7 | 60 | 0.442 | 118 |
| 104257 | QUINCE | 1/0 | 7 | 60 | 0.477 | 134 |
| TBA | ORANGE | 2/0 | 7 | 60 | 0.525 | 171 |
| TBA | WATERASH | 2/0 | 7 | 60 | 0.525 | 171 |
| 104273 | FIG | 3/0 | 7 | 60 | 0.57 | 202 |
| 104281 | OLIVE | 4/0 | 7 | 60 | 0.626 | 248 |
| TBA | PLANETREE | 4/0 | 7 | 60 | 0.632 | 255 |
| 104299 | POMEGRANATE | 4/0 | 19 | 60 | 0.632 | 246 |
| 104315 | ANNONA | 336.4 | 19 | 60 | 0.766 | 375 |
| 148130 | CHINQUAPIN | 350 | 19 | 60 | 0.778 | 390 |
All dimensions are nominal and subject to normal manufacturing tolerances
• TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Code Word | Phase Cond. Size |
|---|---|
| AWG/Kcmil | |
| LINDEN | 77.47 |
| OILNUT | 123.3 |
| SHELLBARK | 195.7 |
| HUCKLEBERRY | 477 |
| PAW PAW | 556.5 |
| BREADFRUIT | 636 |
| PERSIMMON | 795 |
| GRAPEFRUIT | 1033.5 |
| APPLE | 6 |
| PLUM | 6 |
| PEAR | 4 |
| APRICOT | 4 |
| HORNBEAM | 4 |
| CHERRY | 2 |
| PEACH | 2 |
| NECTARINE | 1 |
| QUINCE | 1/0 |
| ORANGE | 2/0 |
| WATERASH | 2/0 |
| FIG | 3/0 |
| OLIVE | 4/0 |
| PLANETREE | 4/0 |
| POMEGRANATE | 4/0 |
| ANNONA | 336.4 |
| CHINQUAPIN | 350 |
Revision: 1.000.019
Updated On: Nov. 6, 2026, 1:34 p.m. UTC

