SPEC 81127

15kV CU 100% EPR (EAM) One-Third Neutral LLDPE Patented POWERGLIDE® MV CABLE (PATENT: www.patentsw.com)

Single Conductor, 175 Mils Ethylene Propylene Rubber (EPR) / Ethylene Alkene Copolymer (EAM), 100% Insulation Level, One-third Concentric Neutral, Linear Low Density Polyethylene (LLDPE) Jacket. Silicone Free

...

Construction:

  1. Conductor:Class B compressed stranded soft drawn bare copper per ASTM B3 and ASTM B8; (Conductor moisture block optional and tinned copper per ASTM B33 optional)
  2. Conductor Shield:Conventional Semi-conducting cross-linked copolymer. A conductor tape is used for cable size larger than or equal to 1500 Kcmil
  3. Insulation:175 Mils Ethylene Propylene Rubber (EPR) / Ethylene Alkene Copolymer (EAM) 100% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Concentric Neutral:Helically applied soft drawn bare copper one-third concentric neutral
  6. Overall Jacket:Linear Low Density Polyethylene (LLDPE) Jacket with PowerGlide® Technology. Black with red extruded stripes

Applications and Features:

Southwire's 15kV cables are suited for use in wet and dry areas, conduits, ducts, direct burial, sunlight, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation. 140°C for emergency overload, and 250°C for short circuit conditions. Jacket types available that can be installed in conduit without the aid of lubrication. Rated for 1000 lbs./FT maximum sidewall pressure.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5 - 46kV
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Rural Utility Standard RUS 1728F-U1 or 1728.204 (Electric standards and specifications for materials and construction)
  • UL 1072 Listed as MV 90 When Specified
  • Optional CSA 68.5: -40ºC and MV 90ºC optional marking available upon request
  • Sample Print Legend:

    SOUTHWIRE HI-DRI(R) [CONDUCTOR SIZE] [AWG or KCMIL] CU 15000 VOLTS EPR INSULATION 175 MILS -- (NESC) -- SOUTHWIRE {MMM} {YYYY} NON-CONDUCTING JACKET
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralNeutral DC Resistance 25°CJacket ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull Tension
    AWG/KcmilinchinchmilinchNo. x AWGΩ/1000ftmilinchlb/1000ftinchlb
    TBA2 (SOLID)0.2580.6461750.7466x140.54500.9745826.8530
    TBA2 (7)0.2830.6711750.7716x140.54500.9995957530
    TBA1 (SOLID)0.2890.6771750.7777x140.463501.0056647669
    TBA1 (19)0.3220.711750.817x140.463501.0386817.3669
    TBA1/0 (SOLID)0.3250.7131750.8139x140.36501.0417777.3844
    TBA1/0 (19)0.3620.751750.859x140.36501.0787967.5844
    TBA2/0 (19)0.4050.7931750.89311x140.295501.1219297.81064
    TBA2/0 (19)0.4050.7931750.89311x140.295501.1219297.81064
    TBA3/0 (19)0.4560.8441750.94414x140.231501.17211028.21342
    TBA4/0 (19)0.5120.9175118x140.18501.22813188.61692
    TBA4/0 (19)0.5120.9175118x140.18501.22813188.61692
    TBA250 (37)0.5580.9541751.05421x140.154501.282150892000
    TBA350 (37)0.6611.0571751.17729x140.112501.40519989.82800
    TBA500 (37)0.7891.1851751.30526x120.079501.5672677114000
    628688500 (37)0.7891.1791751.28916x100.08501.593278211.24000
    TBA750 (61)0.9681.3741751.49425x100.051751.848392512.96000
    TBA1000 (61)1.1171.5231751.67321x80.038752.081511314.68000
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Pulling tension based on pulling eye directly connected to conductor
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzCharging CurrentDielectric LossZero Sequence ImpedancePositive Sequence ImpedanceShort Circuit Current @ 30 CycleAllowable Ampacity in Duct 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftA/1000ftW/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    2 (SOLID)0.1620.2210.0410.0520.211.80.564+j0.2720.222+j0.0562095160195
    2 (7)0.1620.2210.0380.0510.2320.563+j0.2730.222+j0.0572095160195
    1 (SOLID)0.1280.1750.0380.050.2320.497+j0.2250.176+j0.0532444180220
    1 (19)0.1280.1750.0350.0490.242.10.497+j0.2260.176+j0.0542444180220
    1/0 (SOLID)0.1020.1390.0350.0480.252.10.421+j0.1620.141+j0.0513142200250
    1/0 (19)0.1020.1390.0330.0470.262.30.421+j0.1630.141+j0.0523142200250
    2/0 (19)0.0820.1120.030.0450.292.50.359+j0.1240.114+j0.0503840230285
    2/0 (19)0.0820.1120.030.0450.292.50.359+j0.1240.114+j0.0503840230285
    3/0 (19)0.0640.0870.0280.0430.312.70.293+j0.0890.09+j0.04904887260320
    4/0 (19)0.0510.070.0260.0420.342.90.237+j0.0640.073+j0.0476284300360
    4/0 (19)0.0510.070.0260.0420.342.90.237+j0.0640.073+j0.0476284300360
    250 (37)0.0430.0590.0240.0410.363.10.204+j0.0530.063+j0.0467331325
    350 (37)0.0310.0430.0210.0390.413.60.151+j0.0370.048+j0.04410123390460
    500 (37)0.0210.030.0180.0370.474.10.107+j0.0270.037+j0.04114406455525
    500 (37)0.0210.030.0180.0380.484.20.108+j0.0280.037+j0.04114092455525
    750 (61)0.0140.0210.0150.0370.564.90.072+j0.0210.031+j0.03722019545580
    1000 (61)0.0110.0180.0140.0360.645.50.056+j0.0180.029+j0.03429419
    *Ampacities for Direct Buried are based on ICEA P-117-734-2016 Single-Conductor Solid Dielectric 15-35kV. Single Circuit Flat Direct Buried Figure 3
    *Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
    *Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft, Spacing: one diameter spacing center-to-center.
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralNeutral DC Resistance 25°CJacket ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull Tension
    AWG/KcmilmmmmmmmmNo. x AWGΩ/kmmmmmkg/kmmmnewton
    TBA2 (SOLID)6.5516.414.4418.956x141.771.2724.74866172.722359
    TBA2 (7)7.1917.044.4419.586x141.771.2725.37885177.802359
    TBA1 (SOLID)7.3417.204.4419.747x141.521.2725.53988177.802977
    TBA1 (19)8.1818.034.4420.577x141.521.2726.371013185.422977
    TBA1/0 (SOLID)8.2518.114.4420.659x141.181.2726.441156185.423756
    TBA1/0 (19)9.1919.054.4421.599x141.181.2727.381185190.503756
    TBA2/0 (19)10.2920.144.4422.6811x140.971.2728.471383198.124735
    TBA2/0 (19)10.2920.144.4422.6811x140.971.2728.471383198.124735
    TBA3/0 (19)11.5821.444.4423.9814x140.761.2729.771640208.285972
    TBA4/0 (19)13.0022.864.4425.4018x140.591.2731.191961218.447529
    TBA4/0 (19)13.0022.864.4425.4018x140.591.2731.191961218.447529
    TBA250 (37)14.1724.234.4426.7721x140.511.2732.562244228.608900
    TBA350 (37)16.7926.854.4429.9029x140.371.2735.692973248.9212460
    TBA500 (37)20.0430.104.4433.1526x120.261.2739.803984279.4017800
    628688500 (37)20.0429.954.4432.7416x100.261.2740.464140284.4817800
    TBA750 (61)24.5934.904.4437.9525x100.171.9146.945841327.6626700
    TBA1000 (61)28.3738.684.4442.4921x80.121.9152.867609370.8435600
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Pulling tension based on pulling eye directly connected to conductor
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzCharging CurrentDielectric LossZero Sequence Impedance*Positive Sequence Impedance*Short Circuit Current @ 30 CycleAllowable Ampacity in Duct 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilΩ/kmΩ/kmMΩ*kmΩ/kmA/kmW/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    2 (SOLID)0.53150.730.01250.17060.6895.90550.564+j0.2720.222+j0.0562095160195
    2 (7)0.53150.730.01160.16730.7556.56170.563+j0.2730.222+j0.0572095160195
    1 (SOLID)0.41990.570.01160.16400.7556.56170.497+j0.2250.176+j0.0532444180220
    1 (19)0.41990.570.01070.16080.7876.88980.497+j0.2260.176+j0.0542444180220
    1/0 (SOLID)0.33460.460.01070.15750.8206.88980.421+j0.1620.141+j0.0513142200250
    1/0 (19)0.33460.460.01010.15420.8537.54590.421+j0.1630.141+j0.0523142200250
    2/0 (19)0.26900.370.00910.14760.9518.20210.359+j0.1240.114+j0.0503840230285
    2/0 (19)0.26900.370.00910.14760.9518.20210.359+j0.1240.114+j0.0503840230285
    3/0 (19)0.21000.290.00850.14111.0178.85830.293+j0.0890.09+j0.04904887260320
    4/0 (19)0.16730.230.00790.13781.1159.51440.237+j0.0640.073+j0.0476284300360
    4/0 (19)0.16730.230.00790.13781.1159.51440.237+j0.0640.073+j0.0476284300360
    250 (37)0.14110.190.00730.13451.18110.17060.204+j0.0530.063+j0.0467331325
    350 (37)0.10170.140.00640.12801.34511.81100.151+j0.0370.048+j0.04410123390460
    500 (37)0.06890.100.00550.12141.54213.45140.107+j0.0270.037+j0.04114406455525
    500 (37)0.06890.100.00550.12471.57513.77950.108+j0.0280.037+j0.04114092455525
    750 (61)0.04590.070.00460.12141.83716.07610.072+j0.0210.031+j0.03722019545580
    1000 (61)0.03610.060.00430.11812.10018.04460.056+j0.0180.029+j0.03429419
    *Ampacities for Direct Buried are based on ICEA P-117-734-2016 Single-Conductor Solid Dielectric 15-35kV. Single Circuit Flat Direct Buried Figure 3
    *Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
    *Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft, Spacing: one diameter spacing center-to-center.

    Revision: 1.000.000

    Updated On: Aug. 10, 2025, 11:33 p.m. UTC

    Concentric Neutral Calculator
    QR Code