SPEC 80110

ACSS

Aluminum Conductor, Steel Supported

...

Construction:

  1. Core:Stranded standard-strength steel core with zinc-5% aluminum-mischmetal alloy coating for corrosion protection
  2. Stranding:Annealed aluminum (1350-O) round wires with 63% conductivity

Applications and Features:

ACSS (Aluminum Conductor, Steel Supported) is a concentrically stranded, high-temperature, low-sag overhead conductor consisting of one or more layers of fully annealed aluminum wires surrounding a mischmetal alloy coated steel core. The annealed aluminum provides electrical conductivity, while the steel core carries the conductor’s mechanical load.

Southwire batch anneals the completed conductor after stranding, allowing the aluminum to be fully annealed while supporting tighter stranding and verification of finished conductor properties after heat exposure.

ACSS is used for overhead transmission and distribution applications requiring increased ampacity and reduced thermal sag compared with conventional ACSR. It is suitable for new-line construction and reconductoring projects where additional capacity is needed while maintaining existing structure, tension, or clearance requirements.

Continuous operating temperature - 250°C

Specifications:

  • ASTM B500 Standard Specification for Metallic Coated or Aluminum-Clad Stranded Steel Core for Use in Overhead Electrical Conductors
  • ASTM B609 Standard Specification for Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes
  • ASTM B802 Standard Specification for Zin-5% Aluminum-Mischmetal Alloy-Coated Steel Core Wire for Use in Overhead Electrical Conductors
  • ASTM B856 Standard Specification for Concentric-Lay-Stranded Aluminum Conductors, Coated Steel Supported (ACSS)
  • Weights, Measurements, Electrical and Engineering Data
    Stock NumberCode WordConductor SizeStrandingCross-Sectional AreaLayers of AlDiameterWeightRated Breaking StrengthDC Resistance @ 20°C
    Individual StrandsSteel CoreComplete Conductor
    AlTotalAlStAlTotalStd
    kcmilAl/Stin²in²ininininlb/1000 ftlb/1000 ftlbΩ/mile
    TBASpoonbill/ACSS266.822/70.20950.230120.11010.06120.18360.624251.2320.96,0300.3298
    TBAScaup/ACSS266.824/70.20940.236620.10540.07030.21090.633251.1343.27,4100.3286
    TBAPartridge/ACSS266.826/70.20950.243620.10130.07880.23640.642251.2366.68,8800.3271
    TBAJunco/ACSS266.830/70.20950.258420.09430.09430.28290.660251.9417.511,7000.3250
    TBAEider/ACSS266.845/70.20950.224030.07700.05130.15390.616251.2300.34,7500.3310
    TBAOstrich/ACSS300.026/70.23550.273820.10740.08350.25050.680282.4412.19,9700.2910
    TBATrogon/ACSS336.420/70.26420.282420.12970.05760.17280.692316.8378.45,9900.2625
    TBAWoodcock/ACSS336.422/70.26440.290320.12370.06870.20610.701317.1404.87,6100.2613
    TBAWidgeon/ACSS336.424/70.26420.298420.11840.07890.23670.710316.8432.69,3400.2605
    TBALinnet/ACSS336.426/70.26400.307020.11370.08840.26520.720316.6462.211,2000.2596
    TBAOriole/ACSS336.430/70.26420.325920.10590.10590.31770.741317.6526.514,8000.2577
    TBAPtarmigan/ACSS397.520/70.31230.333920.14100.06270.18810.752374.5447.67,0900.2221
    TBAStork/ACSS397.522/70.31210.342820.13440.07470.22410.762374.3478.28,9900.2214
    TBABrant/ACSS397.524/70.31220.352720.12870.08580.25740.772374.4511.511,0000.2204
    TBAIbis/ACSS397.526/70.31200.362820.12360.09610.28830.783374.2546.213,0000.2196
    TBALark/ACSS397.530/70.31210.384920.11510.11510.34530.806375.2621.717,5000.2181
    TBATailorbird/ACSS477.020/70.37450.400420.15440.06860.20580.823449.1536.88,4900.1852
    TBAToucan/ACSS477.022/70.37440.411220.14720.08180.24540.834449.0573.610,8000.1845
    TBAFlicker/ACSS477.024/70.37470.423320.14100.09400.28200.846449.4613.913,0000.1837
    TBAHawk/ACSS477.026/70.37440.435420.13540.10530.31590.858449.0655.515,6000.1830
    TBAHen/ACSS477.030/70.37470.462120.12610.12610.37830.883450.5746.421,0000.1817
    TBAHeron/ACSS500.030/70.39270.484320.12910.12910.38730.904472.1782.222,0000.1734
    TBATody/ACSS556.520/70.43700.467220.16680.07410.22230.890524.1626.39,9100.1587
    TBASapsucker/ACSS556.522/70.43680.479720.15900.08830.26490.901523.8669.012,6000.1582
    TBAParakeet/ACSS556.524/70.43720.493820.15230.10150.30450.914524.3715.915,2000.1574
    TBADove/ACSS556.526/70.43710.508320.14630.11380.34140.927524.2765.218,2000.1568
    TBAEagle/ACSS556.530/70.43710.539120.13620.13620.40860.953525.5870.824,5000.1558
    TBAPeacock/ACSS605.024/70.47530.537020.15880.10590.31770.953570.0778.916,5000.1448
    TBASquab/ACSS605.026/70.47490.552220.15250.11860.35580.966569.5831.219,7000.1443
    TBAWood Duck/ACSS605.030/70.47510.586020.14200.14200.42600.994571.2946.726,0000.1433
    TBATeal/ACSS605.030/190.47510.583420.14200.08520.42600.994571.2938.626,6000.1434
    TBADuck/ACSS605.054/70.47470.536230.10580.10580.31740.952569.3777.516,5000.1450
    TBATuracos/ACSS636.020/70.49940.533920.17830.07920.23760.951598.9715.711,3000.1389
    TBAGoldfinch/ACSS636.022/70.49940.548420.17000.09440.28320.963598.9764.814,1000.1384
    TBARook/ACSS636.024/70.49960.564320.16280.10850.32550.977599.1818.117,3000.1377
    TBAGrosbeak/ACSS636.026/70.49950.580820.15640.12160.36480.990599.0874.220,7000.1372
    TBAScoter/ACSS636.030/70.49950.616020.14560.14560.43681.019600.5994.927,4000.1363
    TBAEgret/ACSS636.030/190.49950.613520.14560.08740.43701.019600.5987.228,0000.1364
    TBAGoose/ACSS636.054/70.49930.564030.10850.10850.32550.977598.8817.817,3000.1378
    TBAFlamingo/ACSS666.624/70.52380.591720.16670.11110.33331.000628.2858.118,2000.1314
    TBAGannet/ACSS666.626/70.52340.608620.16010.12450.37351.014627.7916.121,7000.1309
    TBAGull/ACSS666.654/70.52350.591430.11110.11110.33331.000627.8857.718,2000.1315
    TBAStilt/ACSS715.524/70.56220.635020.17270.11510.34531.036674.2920.719,5000.1224
    TBAStarling/ACSS715.526/70.56200.653520.16590.12900.38701.051674.0983.823,3000.1219
    TBARedwing/ACSS715.530/190.56170.689720.15440.09260.46301.081675.3111030,8000.1213
    TBACrow/ACSS715.554/70.56190.634730.11510.11510.34531.036673.9920.419,5000.1225
    TBATurbit/ACSS795.020/70.62460.667820.19940.08860.26581.063749.1895.414,2000.1110
    TBAPuffin/ACSS795.022/70.62440.685720.19010.10560.31681.077748.8956.317,7000.1107
    TBACuckoo/ACSS795.024/70.62440.705320.18200.12130.36391.092748.8102321,7000.1102
    TBADrake/ACSS795.026/70.62470.726420.17490.13600.40801.108749.2109425,9000.1097
    TBASkimmer/ACSS795.030/70.62450.770220.16280.16280.48841.140750.8124434,2000.1090
    TBAMallard/ACSS795.030/190.62450.766920.16280.09770.48851.140750.8123434,3000.1091
    TBAMacaw/ACSS795.042/70.62460.656730.13760.07640.22921.055749.185811,8000.1113
    TBATern/ACSS795.045/70.62420.667430.13290.08860.26581.063748.689514,2000.1111
    TBACondor/ACSS795.054/70.62400.704930.12130.12130.36391.092748.3102221,7000.1103
    TBARuddy/ACSS900.045/70.70660.755530.14140.09430.28291.131847.4101315,8000.0981
    TBACanary/ACSS900.054/70.70690.798530.12910.12910.38731.162847.7115824,6000.0974
    TBACorncrake/ACSS954.020/70.74920.801020.21840.09710.29131.165898.5107416,7000.0926
    TBARedbird/ACSS954.024/70.74950.846620.19940.13290.39871.196898.8122826,0000.0918
    TBAMerganser/ACSS954.030/70.74910.923920.17830.17830.53491.248900.5149241,1000.0909
    TBACanvasback/ACSS954.030/190.74910.919920.17830.10700.53501.248900.5148041,1000.0909
    TBAPhoenix/ACSS954.042/70.74910.787630.15070.08370.25111.155898.4102914,2000.0928
    TBARail/ACSS954.045/70.74920.801030.14560.09710.29131.165898.5107416,7000.0926
    TBATowhee/ACSS954.048/70.74950.815730.14100.10970.32911.175898.8112319,7000.0923
    TBACardinal/ACSS954.054/70.74910.846230.13290.13290.39871.196898.4122726,0000.0919
    TBASnowbird/ACSS1033.542/70.81210.853930.15690.08720.26161.203973.9111515,4000.0856
    TBAOrtolan/ACSS1033.545/70.81120.867330.15150.10100.30301.212972.8116318,1000.0855
    TBAWhooper/ACSS1033.548/70.81130.882930.14670.11410.34231.223973.0121521,3000.0853
    TBACurlew/ACSS1033.554/70.81120.916430.13830.13830.41491.245972.8132928,2000.0848
    TBAAvocet/ACSS1113.042/70.87430.919230.16280.09040.27121.2481049120116,3000.0795
    TBABluejay/ACSS1113.045/70.87450.935030.15730.10490.31471.2591049125419,5000.0793
    TBABullfinch/ACSS1113.048/70.87440.951630.15230.11850.35551.2691049131023,0000.0791
    TBAFinch/ACSS1113.054/190.87460.985530.14360.08620.43101.2931054143030,4000.0791
    TBAOxbird/ACSS1192.542/70.93660.984830.16850.09360.28081.2921123128617,5000.0742
    TBABunting/ACSS1192.545/70.93671.001430.16280.10850.32551.3021123134220,9000.0740
    TBACormorant/ACSS1192.548/70.93641.019030.15760.12260.36781.3131123140324,6000.0739
    TBAGrackle/ACSS1192.554/190.93651.055230.14860.08920.44601.3381129153232,6000.0739
    TBAScissortail/ACSS1272.042/70.99871.050130.17400.09670.29011.3341198137218,7000.0696
    TBABittern/ACSS1272.045/70.99871.067830.16810.11210.33631.3451198143222,3000.0694
    TBADiver/ACSS1272.048/70.99921.087330.16280.12660.37981.3571198149626,2000.0692
    TBAPheasant/ACSS1272.054/190.99931.125930.15350.09210.46051.3821204163434,1000.0692
    TBARingdove/ACSS1351.542/71.06171.116330.17940.09970.29911.3761273145819,9000.0655
    TBADipper/ACSS1351.545/71.06141.134730.17330.11550.34651.3861273152123,7000.0653
    TBAMartin/ACSS1351.554/191.06141.195830.15820.09490.47451.4241279173536,2000.0652
    TBAPopinjay/ACSS1431.042/71.12411.182030.18460.10260.30781.4151348154421,0000.0618
    TBABobolink/ACSS1431.045/71.12361.201330.17830.11890.35671.4271347161025,1000.0617
    TBAWagtail/ACSS1431.048/71.12441.223630.17270.13430.40291.4391348168429,5000.0615
    TBAPlover/ACSS1431.054/191.12411.266530.16280.09770.48851.4651355183838,4000.0615
    TBANuthatch/ACSS1510.545/71.18621.268230.18320.12210.36631.4661423170126,5000.0585
    TBAParrot/ACSS1510.554/191.18561.335730.16720.10030.50151.5051429193840,4000.0583
    TBARatite/ACSS1590.042/71.24921.313430.19460.10810.32431.4921498171523,4000.0556
    TBALapwing/ACSS1590.045/71.24921.335530.18800.12530.37591.5041498179027,9000.0555
    TBAHornbill/ACSS1590.048/71.24871.358930.18200.14160.42481.5171498187132,2000.0554
    TBAFalcon/ACSS1590.054/191.24891.407230.17160.10300.51501.5451505204242,6000.0554
    TBAChukar/ACSS1780.084/191.39861.512640.14560.08740.43701.6021685207235,4000.0497
    TBAWoodpecker/ACSS1843.072/71.44761.510240.16000.10670.32011.6001745195724,6000.0483
    TBASeahawk/ACSS1869.068/71.46811.514740.16580.09210.27631.6031769192721,5000.0477
    TBAMockingbird/ACSS2034.572/71.59791.667040.16810.11210.33631.6811926216027,2000.0438
    TBARoadrunner/ACSS2057.076/191.61521.703240.16450.07680.38401.7001946224531,7000.0432
    TBABluebird/ACSS2156.084/191.69311.830940.16020.09610.48051.7622040250742,1000.0411
    TBAKiwi/ACSS2167.072/71.70221.775840.17350.11570.34711.7352051230029,0000.0411
    TBAThrasher/ACSS2312.076/191.81551.914440.17440.08140.40701.8022188252435,6000.0385
    TBAJoree/ACSS2515.076/191.97502.082640.18190.08490.42451.8802380274538,7000.0354

    Revision: 1.000.004

    Updated On: Nov. 9, 2026, 9:51 p.m. UTC