SPEC 80007

C7® Advanced Conductor - ACCS/TW/C7-TS

Shaped Wire, Aluminum Conductor, Composite Supported

...

Construction:

  1. Core: Stranded continuous carbon fiber thermoset composite core with a protective capping layer
  2. Stranding:Annealed aluminum (1350-O) trapezoidal shaped strands with 63% conductivity

Applications and Features:

Southwire’s C7-TS conductor is a high-temperature, low-sag (HTLS) advanced conductor designed for overhead transmission and distribution systems where increased capacity and reliability are critical. Its multi-strand carbon fiber composite core delivers near-zero thermal sag, exceptional tensile strength, and structural redundancy to eliminate single-point failures. C7-TS uses fully annealed 1350-O aluminum strands, with trapezoidal strands (TW) for reduced diameter and improved ampacity. Its crew-friendly design allows installation using conventional hardware and familiar techniques. Applications include long-span transmission corridors, thermal uprating of congested lines, and environments requiring superior corrosion resistance. Rated for a continuous operating temperature of 180°C and an emergency operating temperature of 200°C.

Download additional information here: C7® Portfolio

Specifications:

  • ASTM B609 Standard Specification for Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes
  • ASTM B987 Standard Specification for Carbon Fiber Thermoset Polymer Matrix Composite Core (CFC) for use in Overhead Electrical Conductors
  • Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661
  • Resources:

    C7 Installation Guide↓
    C7 Brochure – Imperial Units↓
    C7 Brochure – Metric Units↓
    Overhead Conductor Comparison↓
    C7 River Crossing Profile↓
    ACCS Spec Sheet↓

    Table 1 – Dimensions and Weight

    Stock NumberCode WordCond
    Size
    TypeCross-
    Sectional
    Area
    Layers
    of AL
    StrandingDiameterWeightRBS
    ALTotalALC7 StrandsC7 CoreOverallALC7 CoreTotal
    kcmilnumin2in2numnumnum x inininlb/1000ftlb/1000ftlb/1000ftlb
    TBAFUNDY/TW203.2430.15960.228187 x 0.11150.33460.585194.248.2242.422100
    TBASHENANDOAH/TW266.8210.20950.2533187 x 0.08920.26770.60825530.9285.815000
    TBAOLYMPIC/TW325170.25530.2992207 x 0.08920.26770.671309.230.9340.115400
    TBAWRANGELL/TW336.4170.26420.3082207 x 0.08920.26770.681320.130.935115500
    TBABADLANDS/TW336.4220.26420.32182207 x 0.10240.30710.685320.140.6360.719700
    TBAANDES/TW397.5140.31220.3562187 x 0.08920.26770.71378.130.9408.915900
    TBAJOSHUA TREE/TW397.5160.31220.36272187 x 0.09580.28740.718373.535.6409.117900
    TBASEQUOIA/TW397.5220.31220.38062187 x 0.11150.33460.738378.148.2426.323400
    TBAROGERS/TW477130.37460.42512187 x 0.09580.28740.778447.435.6483.318400
    TBAYOSEMITE/TW477150.37460.43222187 x 0.10240.30710.787453.740.6494.320600
    TBACAPITOL REEF/TW477230.37460.46012207 x 0.12470.3740.82450.460.2510.629100
    TBAPINNACLES/TW556.5100.43710.48092167 x 0.08920.26770.823522.130.955316900
    TBAWHITE SANDS/TW556.5130.43710.49472187 x 0.10240.30710.832522.440.656321100
    TBAINDIANA DUNES/TW556.5160.43710.50552207 x 0.11150.33460.847522.948.2571.124400
    TBANEW RIVER GORGE/TW556.5230.43710.53952207 x 0.13650.40940.888525.472.2597.634700
    TBATORTUGAS/TW636100.49950.552207 x 0.09580.28740.88596.735.6632.319400
    TBAYELLOWSTONE/TW636120.49950.55712167 x 0.10240.30710.887605.440.664621600
    TBAGLACIER/TW636150.49950.57622207 x 0.11810.35430.905605.254.1659.227400
    TBACARLSBAD/TW636220.49950.612207 x 0.14170.42520.937605.277.868336900
    TBACONGAREE/TW641.7110.5040.56162167 x 0.10240.30710.89610.840.6651.421600
    TBAVINSON/TW714100.56080.61842167 x 0.10240.30710.933669.940.6710.522100
    TBAKILIMANJARO/TW79570.62440.66822207 x 0.08920.26770.962745.130.977618400
    TBAALPS/TW79590.62440.6822207 x 0.10240.30710.974756.540.6797.122600
    TBAWIND CAVE/TW795120.62440.70112207 x 0.11810.35430.99756.554.1810.528400
    TBADENALI/TW795160.62440.72682207 x 0.13650.40941.0174772.2819.236200
    TBAROCKY/TW795220.62440.76072247 x 0.15750.47241.044756.396.1852.445600
    TBAGATEWAY ARCH/TW90070.70690.75733327 x 0.09580.28741.031847.735.6883.321000
    TBARAINIER/TW900130.70690.79972207 x 0.12990.38981.056844.865.4910.234000
    TBAMAUNA KEA/TW900210.70690.85482207 x 0.16400.49211.1856.4104.3960.749700
    TBACRATER LAKE/TW95470.74930.79973347 x 0.09580.28741.058898.635.6934.121300
    TBAGRAND CANYON/TW954100.74930.8263347 x 0.11810.35431.072899.454.1953.529300
    TBAFUJI/TW954120.74930.84212207 x 0.12990.38981.077907.865.4973.234300
    TBAJASPER/TW954160.74930.8682227 x 0.14700.44091.104896.483.7980.141400
    TBAARCHES/TW954200.74930.89722207 x 0.16400.49211.126907.8104.3101250100
    TBAEVERGLADES/TW973.1140.76430.87472207 x 0.14170.42521.108925.977.81003.839000
    TBABIG BEND/TW1033.550.81170.85553347 x 0.08920.26771.093972.530.91003.419800
    TBALASSEN/TW1033.570.81170.86933347 x 0.10240.30711.103973.440.6101424000
    TBATAHOE/TW1033.5110.81170.89723347 x 0.12470.3741.118980.960.21041.232500
    TBASAMOA/TW1033.5130.81170.91412227 x 0.13650.40941.13970.172.21042.337800
    TBAOCALA/TW1033.5160.81170.93912207 x 0.15220.45671.15971.189.81060.944500
    TBACOOK/TW111350.87410.91793307 x 0.08920.26771.1251047.330.91078.220200
    TBABLANC/TW111370.87410.93183347 x 0.10240.30711.1391048.340.61088.924500
    TBANIAGARA/TW1113100.87410.95963347 x 0.12470.3741.1551049.360.21109.632900
    TBAGANNETT/TW1113130.87410.98463387 x 0.14170.42521.1811050.977.81128.739800
    TBAWASHINGTON/TW1192.550.93660.98043347 x 0.08920.26771.1661122.130.9115320700
    TBAELBERT/TW1192.570.93661.0053347 x 0.11150.33461.1841123.248.21171.428200
    TBAKINGS CANYON/TW1192.5100.93661.02943347 x 0.12990.38981.2031124.365.41189.735700
    TBAACADIA/TW1192.5130.93661.05543387 x 0.14700.44091.2231125.983.71209.742700
    TBAREDWOOD/TW1233.670.96891.03733367 x 0.11150.33461.2071161.948.21210.128500
    TBAMESA VERDE/TW1233.6100.96891.06173387 x 0.12990.38981.221116365.41228.535900
    TBABISCAYNE/TW1233.6130.96891.09633367 x 0.15220.45671.2451164.789.81254.545600
    TBASAGUARO/TW127250.9991.04953387 x 0.09580.28741.2111196.935.61232.523300
    TBASIERRA NEVADA/TW127270.9991.06743387 x 0.11150.33461.2241198.148.21246.328700
    TBAELDORADO/TW1272100.9991.10143387 x 0.13650.40941.2441199.372.21271.439100
    TBAVOYAGEURS/TW1272130.9991.12643397 x 0.15220.45671.259120189.81290.845800
    TBACASCADES/TW1351.571.06151.13823387 x 0.11810.35431.264127354.1132731800
    TBABANFF/TW1351.5101.06151.16393427 x 0.13650.40941.2781274.272.21346.439600
    TBAELBRUS/TW1351.5131.06151.19783427 x 0.15750.47241.2991276.196.11372.249000
    TBAKINGS PEAK/TW143171.12391.20063367 x 0.11810.35431.2921347.854.11401.932300
    TBAWHEELER/TW1431101.12391.23433367 x 0.14170.42521.3091349.277.8142741700
    TBAGRANITE/TW1431131.12391.27183367 x 0.16400.49211.3411351.1104.31455.452900
    TBABORAH/TW1510.571.18631.27183367 x 0.12470.3741.331422.760.2148335400
    TBABOUNDARY/TW1510.5101.18631.30513367 x 0.14700.44091.3471424.183.71507.844700
    TBAWHITNEY/TW1510.5121.18631.33433367 x 0.16400.49211.3741434.2104.31538.553400
    TBABRYCE CANYON/TW159071.24881.33423367 x 0.12470.3741.3571497.660.21557.835900
    TBAADIRONDACK/TW1590101.24881.37623387 x 0.15220.45671.3861499.189.81588.947800
    TBAZION/TW1590121.24881.39673427 x 0.16400.49211.4051509.4104.31613.753900
    TBATETON/TW178051.3981.47473387 x 0.11810.35431.4221674.954.1172934400
    TBAEVEREST/TW178081.3981.50843387 x 0.14170.42521.4411674.177.81751.943900
    TBAKATMAI/TW1780101.3981.53443367 x 0.15750.47241.461678.296.11774.351600
    TBAGREAT BASIN/TW194971.53071.63323367 x 0.13650.40941.51835.772.21907.943300

    All dimensions are nominal and subject to normal manufacturing tolerances.
    The final design of a TW conductor is contingent upon several factors such as: layer diameter, wire width, and wire thickness. This may result in a slight variation in the number of wires, number of layers, and outside diameter from that shown in the table.


    Table 2 – Electrical

    Stock NumberCode WordConductor SizeDC ResistanceAC Resistance @ 60HzGMRReactance @ 1ft Spacing 60HzAmpacity†
    @ 20°C@ 25°C@ 180°C@ 200°CInductive
    Xa
    Capacitive
    X'a
    @ 180°C@ 200°C
    kcmilΩ/mileΩ/mileΩ/mileΩ/mileftΩ/mileMΩ-mileampamp
    TBAFUNDY/TW203.20.44450.45390.74020.77710.02050.47190.1102644677
    TBASHENANDOAH/TW266.80.33870.34610.56420.59240.02040.47240.109746784
    TBAOLYMPIC/TW3250.27690.28310.46140.48440.02310.45720.1061851894
    TBAWRANGELL/TW336.40.26750.27360.44580.4680.02340.45580.1057869914
    TBABADLANDS/TW336.40.26750.27350.44560.46790.02390.4530.1055871916
    TBAANDES/TW397.50.22630.23170.37720.3960.02380.45370.10449571006
    TBAJOSHUA TREE/TW397.50.22350.22880.37260.39120.02430.45130.10419661016
    TBASEQUOIA/TW397.50.22620.23150.37710.39580.02540.44570.10339691019
    TBAROGERS/TW4770.18610.19080.31040.32590.0260.44290.101710851141
    TBAYOSEMITE/TW4770.18860.19330.31450.33010.02650.44060.101410821138
    TBACAPITOL REEF/TW4770.18720.19170.3120.32760.02870.43080.100211001157
    TBAPINNACLES/TW556.50.15940.16390.26620.27950.02740.43660.111921255
    TBAWHITE SANDS/TW556.50.15950.16380.26630.27950.02780.43480.099711961259
    TBAINDIANA DUNES/TW556.50.15970.16390.26640.27970.02910.42930.099212021265
    TBANEW RIVER GORGE/TW556.50.16040.16450.26760.28090.03110.4210.097812171282
    TBATORTUGAS/TW6360.13950.14370.23310.24470.02950.42760.098113001369
    TBAYELLOWSTONE/TW6360.14150.14570.23640.24820.02970.42680.097812941363
    TBAGLACIER/TW6360.14150.14550.23620.2480.0310.42140.097213031372
    TBACARLSBAD/TW6360.14150.14520.23610.24780.03280.41470.096213181388
    TBACONGAREE/TW641.70.14030.14440.23440.2460.02980.42640.097713021371
    TBAVINSON/TW7140.12430.12830.20780.21810.03110.42130.096314031477
    TBAKILIMANJARO/TW7950.11150.11560.18680.19610.03160.41910.095414931574
    TBAALPS/TW7950.11320.11720.18950.19890.03250.41580.09514891568
    TBAWIND CAVE/TW7950.11320.1170.18940.19880.03350.41190.094614971577
    TBADENALI/TW7950.11180.11530.18690.19610.03480.40750.09415161598
    TBAROCKY/TW7950.11320.11650.18910.19840.03670.4010.09315231605
    TBAGATEWAY ARCH/TW9000.0990.10310.16610.17430.03370.41130.093416191706
    TBARAINIER/TW9000.09860.10230.16520.17340.03590.40360.092716351724
    TBAMAUNA KEA/TW9000.10.10320.16720.17550.03840.39550.091416471736
    TBACRATER LAKE/TW9540.09340.09750.15690.16460.03430.40910.092616791770
    TBAGRAND CANYON/TW9540.09350.09730.15680.16450.03560.40470.092216861778
    TBAFUJI/TW9540.09430.0980.15810.16590.03650.40150.092116821773
    TBAJASPER/TW9540.09310.09660.1560.16370.03760.39830.091317061799
    TBAARCHES/TW9540.09430.09760.15790.16570.03930.39280.090717071800
    TBAEVERGLADES/TW973.10.09250.0960.1550.16260.03790.39710.091217141808
    TBABIG BEND/TW1033.50.08610.09040.1450.15210.03510.40640.091617651861
    TBALASSEN/TW1033.50.08620.09030.1450.15210.03590.40370.091417701866
    TBATAHOE/TW1033.50.08690.09070.14590.1530.03720.39950.09117721869
    TBASAMOA/TW1033.50.08590.08950.14420.15130.03780.39730.090617881886
    TBAOCALA/TW1033.50.0860.08940.14420.15130.03950.39210.090117981897
    TBACOOK/TW11130.080.08440.13490.14150.03550.40510.090818461948
    TBABLANC/TW11130.080.08430.13490.14150.0370.40020.090418541955
    TBANIAGARA/TW11130.08010.0840.13480.14140.03830.3960.0918621965
    TBAGANNETT/TW11130.08020.08390.13480.14150.040.39070.089318751978
    TBAWASHINGTON/TW1192.50.07460.07920.12620.13230.03720.39940.089719312037
    TBAELBERT/TW1192.50.07470.07890.12610.13220.03860.39490.089319412048
    TBAKINGS CANYON/TW1192.50.07480.07870.1260.13210.03980.3910.088819512059
    TBAACADIA/TW1192.50.07490.07860.1260.13220.04140.38650.088319622070
    TBAREDWOOD/TW1233.60.07220.07650.1220.12790.03990.3910.088719852095
    TBAMESA VERDE/TW1233.60.07230.07630.12190.12790.04070.38860.088319932104
    TBABISCAYNE/TW1233.60.07240.0760.12190.12780.04240.38340.087820062117
    TBASAGUARO/TW12720.070.07450.11850.12420.0390.39380.088620172129
    TBASIERRA NEVADA/TW12720.070.07440.11840.12420.040.39060.088320242136
    TBAELDORADO/TW12720.07010.0740.11830.1240.04160.38590.087820362149
    TBAVOYAGEURS/TW12720.07020.07390.11830.12410.04290.3820.087420432157
    TBACASCADES/TW1351.50.06590.07030.11160.1170.04140.38630.087321062224
    TBABANFF/TW1351.50.0660.070.11160.1170.04290.3820.08721142232
    TBAELBRUS/TW1351.50.06610.06980.11150.11690.04430.37810.086521262244
    TBAKINGS PEAK/TW14310.06230.06680.10570.11080.04260.38280.086721802302
    TBAWHEELER/TW14310.06230.06640.10550.11060.0440.3790.086321912313
    TBAGRANITE/TW14310.06240.06620.10550.11060.04570.37440.085622082332
    TBABORAH/TW1510.50.0590.06350.10030.10510.0440.3790.085822582386
    TBABOUNDARY/TW1510.50.0590.06320.10010.1050.04530.37540.085422692397
    TBAWHITNEY/TW1510.50.05940.06340.10070.10550.04670.37180.084822782406
    TBABRYCE CANYON/TW15900.0560.06070.09550.10010.04370.37990.085223292461
    TBAADIRONDACK/TW15900.05610.06030.09530.09990.04630.37270.084623482480
    TBAZION/TW15900.05650.06050.09580.10040.04770.36920.084223522485
    TBATETON/TW17800.050.05520.08590.08990.0460.37370.083824932636
    TBAEVEREST/TW17800.050.05470.08560.08960.04750.36970.083425092652
    TBAKATMAI/TW17800.05010.05460.08560.08970.0490.36590.08325192663
    TBAGREAT BASIN/TW19490.04570.05090.07880.08250.04950.36480.082226482801

    Resistance and ampacity based on an aluminum conductivity of 63% IACS at 20°C.
    † Ampacity based on 25°C ambient temperature, 2 ft/s perpendicular wind, 0.5 emissivity, 0.5 absorptivity, 60 Hz, clear atmosphere, sea level, 30° N. latitude, N-S line azimuth, noon on June 10th.

    Revision: 1.000.059