SPEC 60410

Red Alert® Type MC-FPL Fire Alarm and Control

Copper THHN/THWN or TFN or TFFN Insulated Copper Singles. Type TFN Insulated Copper Singles. Green Insulated Copper Grounding Conductor. UL Listed as Type MC and Type FPL. 600 Volt Type MC and 300 Volt Type FPL. Red Lightweight Aluminum Interlocked Armor.

...

Construction:

  1. Conductor:Solid or stranded copper per ASTM B3 and ASTM B8 or B174
  2. Insulation:All phases are insulated with Polyvinyl Chloride with Nylon Sheath Type THHN/THWN for 10, 14, 12, 16 and 18 AWG
  3. Ground:Green insulated ground. Polyvinyl Chloride with Nylon Sheath Type TFN or TFFN
  4. Binder:Mylar tape
  5. Armor:Red Aluminum Interlocked Armor

Applications and Features:

Southwire Red Alert® Type MC-FPL Cable is suitable for use as follows:
- Wiring in Plenums, Ducts or Other Spaces Used for Environmental Air-Handling Purposes per NEC 300.22(C) & 760.135(C).
- Power-Limited and Non-Power Limited fire alarm circuits, including smoke detectors, bells, horns, fire alarm control panel equipment, and initiation and signaling devices.
- Class 1, Class 2, and Class 3 remote control, signaling, and power-limited circuits.
- Power, lighting, control, and signal circuits.
- Fished or embedded in plaster.
- Concealed or exposed installations.
- Places of Assembly per NEC 518.4 and theaters per NEC 520.5.
- Installation in cable tray and approved raceways.
- Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) & 645.5(E)
- Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations.
- Binder tape with print legend wrapped around assembly.
- Rated at 600V, 90ºC dry as Type MC or 300V, 90ºC dry as Type FPL.
- Anti-short bushings are not required for use with MC cable per NEC and UL.

Southwire Red Alert® Type MC-FPL Cable - meets or exceeds the following requirements:
- UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
- Federal Specification A-A59544 (formerly J-C-30B)
- NFPA 70 (National Electrical Code), Article 330
- Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems

Specifications:

  • UL 1424 Cables for Power-Limited Fire-Alarm Circuits
  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B174 Standard Specification for Bunch-Stranded Copper
  • UL 66 Fixture Wire
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 1569 Metal-Clad Cables
  • UL 1479 Standard for Safety Fire Tests of Penetration Firestops
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • Buy American: Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j); specify “Made in the USA Only!” when ordering to ensure your project receives American made products.
  • Sample Print Legend:

    SOUTHWIRE E96627 XX AWG MC 600V {UL} TYPE (THHN OR TFFN) INSULATED CONDUCTORS OR TYPE FPL {UL} 90°C DRY-FOR USE IN CABLE TRAYS
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeConductor NumberColorDiameter Over ConductorConductor StrandingInsulation ThicknessDiameter Over ArmorCopper WeightOverall Weight
    AWG/Kcmilinchmilsinchlbs/1000ftlbs/1000ft
    18 AWG | Solid
    677747182BK/WE/BK/WE/GN0.04Solid200.3931559
    554686182BK/RD/GN0.04Solid200.3961560
    554686182BK/WE/GN0.04Solid200.3961560
    554686182BK/WE/GN0.04Solid200.3961560
    554687184/GN0.04Solid200.442579
    554687184BK/BE/YW/GN0.04Solid200.442579
    553124186BK/BN/OE/RD/BE/YW/GY/WE/GN0.04Solid200.4593595
    553125188BK/RD/BE/WE/BN/YW/GN0.04Solid200.51545115
    553125188BK/BN/OE/RD/BE/YW/GY/WE/GN0.04Solid200.51545115
    677747182BK,RD,GN0.040Solid200.39159
    554686182BK,WE,GN0.040Solid200.39159
    554687184BK,RD,BE,WE,GN0.040Solid200.43478
    553124186BK,BN,RD,BE,YW,WE,GN0.040Solid200.45995
    553125188BK,BN,OE,RD,BE,YW,GY,WE,GN0.040Solid200.507115
    16 AWG | Solid
    554688162BK/RD/GN0.05Solid200.4192472
    586569162BK/WE/RD/BE0.05Solid200.5042484
    586569162YW,PE,GN0.05Solid200.62123100
    589152162BE,WE,GN0.05Solid200.3992370
    589152162BK/WE/GN /RD/BE0.05Solid200.4192472
    138226162RD/BE/GN0.05Solid200.4192472
    138291162BK/RD/GN0.05Solid200.4192472
    554688162BE/WE/GN0.05Solid200.4192472
    554689164BN/OE/YW/BE/GN0.05Solid200.4693999
    554689164BK/RD/GN0.05Solid200.4693999
    553128166BK/RD/GN0.05Solid200.49655123
    553128166BK/RD/BE/WE/BN/YW/GN0.05Solid200.49655123
    554688162BK,WE,GN0.050Solid200.41472
    554689164BK,RD,BE,WE,GN0.050Solid200.46398
    553128166BK,RD,BE,WE,BN,YW,GN0.050Solid200.490122
    14 AWG | Solid
    554690142BK,WE,GN0.064Solid200.45192
    138228142RD/BE/GN0.064Solid200.4513892
    138293142BN/OE/GN0.064Solid200.4513892
    138295142GY/YW/GN0.064Solid200.4513892
    554537142BK/RD/GN0.064Solid200.4513892
    554537142BE/WE/GN0.064Solid200.4513892
    554538142BE/WE/GN0.064Solid200.4513892
    554538142BK/RD/BE/WE/GN0.064Solid200.4513892
    554690142BK/WE0.064Solid200.4513892
    554690142BK/WE0.064Solid200.4513892
    554690142BK/WE0.064Solid200.4513892
    554537142BK,RD,GN0.064Solid200.45192
    554538142BE,WE,GN0.064Solid200.4323790
    554539144BK,RD,BE,WE,GN0.064Solid200.509131
    554539144BK/RD/BE/WE/GN0.064Solid200.50463129
    554539144BK/WE/GN0.064Solid200.50463129
    6657971440.064Solid200.50463129
    14 AWG | 19 Strands
    555264142BK,WE,GN0.0719200.4493894
    641189142BK,WE,GN0.0719200.46838149
    555264142BK/WE/RD/BE0.07319200.4683897
    555264142BK/WE/RD/BE0.07319200.4683897
    641181142BN/OE/GN /RD/BE0.07319200.4683897
    559605143BK/WE/GN /BK/WE0.07319200.49751117
    12 AWG | Solid
    554540122BK/WE/GN0.08Solid200.48460120
    554540122BK/RD/BE/WE/GN0.08Solid200.48460120
    554541124BK/WE/GN0.08Solid200.55100175
    554541124BK/RD/BE/WE/GN0.08Solid200.55100175
    554540122BK,WE,GN0.080Solid200.487121
    554541124BK,RD,BE,WE,GN0.080Solid200.554179
    12 AWG | 19 Strands
    555814122BK,RD,GN0.08819200.50460124
    555814122BK/WE/RD/BE0.0919200.50560125
    16 AWG | Solid
    641527168BK,WE,RD,BE,BN,YW,OE,GY0.050Solid200.536137
    16 AWG | 26 Strands
    573267162BK,WE,GN0.05826200.43676
    14 AWG | 19 Strands
    559605143BK,BE,YW,GN0.07319200.497117
    12 AWG | 19 Strands
    557329122BE,WE,GN0.09019200.509126
    10 AWG | 19 Strands
    583397104BN,OE,YW,GY,GN0.11719250.679275
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Note: Conductor number = number of phase conductors. Does not include ground
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeConductor NumberMin. Bend RadiusDC Resistance at 25°CAC Resistance at 75°CInductive Reactance @ 60HzAllowable Ampacity Raceway 75°CAllowable Ampacity Raceway 90°C
    AWG/KcmilInchesΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    18 AWG | Solid
    1822.86.678.040.04-14
    1822.86.678.040.04-14
    1822.86.678.040.04-14
    1822.86.678.040.04-14
    1843.16.678.040.04-11
    1843.16.678.040.04-11
    1863.26.678.040.04-11
    1883.66.678.040.04-9
    1883.66.678.040.04-9
    1822.76.6708.270-18
    1822.76.6708.270-18
    1843.06.6708.270-14
    1863.26.6708.270-14
    1883.56.6708.270-12
    16 AWG | Solid
    1622.94.185.040.03-18
    1623.54.185.040.03-18
    1624.34.1815.0370.033018
    1622.84.1815.0370.033018
    1622.94.185.040.03-18
    1622.94.185.040.03-18
    1622.94.185.040.03-18
    1622.94.185.040.03-18
    1643.34.185.040.03-14
    1643.34.185.040.03-14
    1663.54.185.040.03-14
    1663.54.185.040.03-14
    1622.84.1805.190-18
    1643.24.1805.190-14
    1663.44.1805.190-14
    14 AWG | Solid
    1423.22.5803.1702025
    1423.22.633.170.062025
    1423.22.633.170.062025
    1423.22.633.170.062025
    1423.22.633.170.062025
    1423.22.633.170.062025
    1423.22.633.170.062025
    1423.22.633.170.062025
    1423.22.633.170.062025
    1423.22.633.170.062025
    1423.22.633.170.062025
    1423.22.5803.1702025
    14232.6313.170.0582025
    1443.62.5803.1701620
    1443.52.633.170.061620
    1443.52.633.170.061620
    1443.52.633.170.061620
    14 AWG | 19 Strands
    1423.12.6313.170.0582025
    14242.6313.170.0582025
    1423.32.633.170.062025
    1423.32.633.170.062025
    1423.32.633.170.062025
    1433.52.633.170.062025
    12 AWG | Solid
    1223.41.6620.052530
    1223.41.6620.052530
    1243.91.6620.052024
    1243.91.6620.052024
    1223.41.6602.0002530
    1243.91.6602.0002024
    12 AWG | 19 Strands
    1223.51.6622.0020.0542530
    1223.51.6620.052530
    16 AWG | Solid
    1683.74.1805.190-18
    16 AWG | 26 Strands
    1623.04.1805.190-18
    14 AWG | 19 Strands
    1433.52.6303.1702025
    12 AWG | 19 Strands
    1223.61.6602.0002530
    10 AWG | 19 Strands
    1044.81.0201.2502832
    * Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    * Ampacities have been adjusted for more than Three Current-Carrying Conductors.