SPEC 60257

MC-AP™ HCF Type MC All Purpose Health Care Facility THHN/THWN Circuit Size Copper Conductor 277/480V Colors Green Aluminum Armor

Copper THHN/THWN Insulated Conductors. Green Copper Ground. Full-Sized Aluminum Equipment Grounding/Bonding Conductor. UL Listed. 600 Volt. Rated VW1. Lightweight Aluminum Interlocked Armor is Part of Equipment Bonding/Grounding Path.

...

Construction:

  1. Conductor:Solid or 19 strands class C compressed copper per ASTM B3 and ASTM B8
  2. Insulation:All phases are insulated with Polyvinyl Chloride with Nylon Sheath Type THHN/THWN
  3. Binder:Mylar tape
  4. Ground:A Green insulated Polyvinyl Chloride with Nylon Sheath Type THHN/THWN ground. Redundant grounding provided by a bare 8000 series aluminum grounding/bonding conductor and armor.
  5. Armor:Green Aluminum Interlocked Armor

Applications and Features:

Southwire MC-AP HCF Type MC All Purpose Heath Care Facility Cable is suitable for use as follows:
- Branch-circuit wiring for patient care areas of hospitals, medical centers, and other health care facilities (when installed in accordance with NEC® Articles 517 and 330, and mechanically protected per Article 300.4). Such areas include nursing homes, dental offices, clinics, and outpatient facilities. Use in hazardous anesthetizing areas is prohibited.
- Applications requiring redundant, dedicated or isolated grounding paths.
- Fished or embedded in plaster.
- Concealed or exposed installations.
- Environmental air-handling spaces per NEC 300.22 (C).
- Places of Assembly per NEC 518.4 and theaters per NEC 520.5.
- Installation in cable tray and approved raceways.
- Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) & 645.5(E)
- Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations.
- Use with UL Listed MCI-A fittings.
- Binder tape with print legend wrapped around assembly.
- Type THHN/THWN rated 90ºC Dry.
- Armor is in contact with aluminum grounding/bonding conductor and serves as a redundant equipment grounding path component

Southwire Armorlite® Type MC Cable - meets or exceeds the following requirements:
- UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
- Federal Specification A-A59544 (formerly J-C-30B)
- NFPA 70 (National Electrical Code), Article 330
- Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 1569 Metal-Clad Cables
  • UL 1479 Standard for Safety Fire Tests of Penetration Firestops
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • RoHS-2 (European Directive 2011/65/EU)
  • Buy American: Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j); specify “Made in the USA Only!” when ordering to ensure your project receives American made products.
  • Sample Print Legend:

    SOUTHWIRE E96627 {UL} TYPE MC XX AWG THHN OR THWN CDRS FOR USE IN CABLE TRAYS 600 VOLTS
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeConductor NumberColorDiameter Over ConductorConductor StrandingInsulation ThicknessGround SizeDiameter Over ArmorCopper WeightOverall Weight
    AWG/KcmilinchmilsNo. x AWGinchlbs/1000ftlbs/1000ft
    12 AWG | Solid
    596280122PE,WE,GN0.08Solid201x100.50659117
    677421122PE,GY,GN0.08Solid201x100.50659117
    590167124BN,OE,GY/BN,GY/OE,GN0.08Solid201x120.57399172
    567400126BN,OE,YW,GY/BN,GY/OE,GY/YW,GN0.08Solid201x120.61139223
    555739◊122BN,GY0.080Solid201x100.51259118
    555544◊122YW,GY0.080Solid201x100.50659117
    555543◊122OE,GY0.080Solid201x100.50659117
    555741◊123BN,OE,GY0.080Solid201x100.53879144
    555743◊124BN,OE,YW,GY0.080Solid201x100.57399172
    12 AWG | 19 Strands
    561383122YW,GY,GN0.08819201x100.52860122
    564027124BN,GY,OE,YW,GN0.08819201x100.6100179
    10 AWG | Solid
    555745◊102BN,GY0.101Solid251x80.58092169
    565839102OE,GY,GN0.101Solid251x80.5892169
    565841102YW,GY,GN0.101Solid251x80.5892169
    555747◊103BN,OE,GY0.101Solid251x80.619123210
    596349104BN,OE,GY/BN,GY/OE,GN0.101Solid251x100.663154251
    555750◊104BN,OE,YW,GY0.101Solid251x80.663154251
    573237106BN,OE,YW,GY/BN,GY/OE,GY/YW,GN0.101Solid251x100.709216329
    10 AWG | 19 Strands
    593402104BN,OE,GY,YW,GN0.11319251x80.705161269
    599142106BN,OE,YW,GY/BN,GY/OE,GY/YW,GN0.11319251x100.761226351
    12 AWG | 19 Strands
    560977◊122OE,GY0.09019201x100.52860122
    558724◊122BN,GY0.09019201x100.52860122
    559791◊123BN,OE,GY0.09019201x100.56280151
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Note: Conductor number = number of phase conductors plus neutral. Does not include green ground.
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeConductor NumberMin. Bend RadiusDC Resistance at 25°CAC Resistance at 75°CInductive Reactance @ 60HzAllowable Ampacity Raceway 75°CAllowable Ampacity Raceway 90°C
    AWG/KcmilInchesΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    12 AWG | Solid
    1223.51.6622.0020.0542530
    1223.51.6622.0020.0542530
    12441.6622.0020.0542024
    1264.31.6622.0020.0541721
    1223.61.6622.0020.0542530
    1223.51.6622.0020.0542530
    1223.51.6622.0020.0542530
    1233.81.6622.0020.0542530
    1244.01.6622.0020.0542024
    12 AWG | 19 Strands
    1223.71.6622.0020.0542530
    1244.21.6622.0020.0542024
    10 AWG | Solid
    1024.11.0401.2530.0503540
    1024.11.041.2530.053540
    1024.11.041.2530.053540
    1034.31.0401.2530.0503540
    1044.61.041.2530.052832
    1044.61.0401.2530.0502832
    10651.041.2530.052428
    10 AWG | 19 Strands
    1044.91.041.2530.052832
    1065.31.041.2530.052428
    12 AWG | 19 Strands
    1223.71.6622.0020.0542530
    1223.71.6622.0020.0542530
    1233.91.6622.0020.0542530
    * Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    * Ampacities have been adjusted for more than Three Current-Carrying Conductors.

    Revision: 1.000.003

    Updated On: Dec. 31, 2024, 11:08 p.m. UTC

    MCAP Savings Calculator
    QR Code