SPEC 46313
AL Compact 15kV NLEPR Insulation 133% IL Black SIM-PVC Jacket. 2x5 mils Tape Shield - MV 105 - Tray Rated - Sunlight Resistant - For Direct Burial
Type MV-105 Single Conductor Aluminum, 220 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% Insulation Level, 2x5 Mils Tape Shield, SIMpull® Polyvinyl Chloride (PVC) Jacket, Dual Rated UL/CSA

Construction:
- Conductor:Class B compact stranded TRIPLE E Aluminum Alloy (AA-8176) per ASTM B801 and B836
- Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
- Insulation:220 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% Insulation Level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Copper Tape Shield:Helically wrapped 2x5 mil copper tape with 25% overlap
- Overall Jacket:Polyvinyl Chloride (PVC)
Applications and Features:
Southwire’s 15KV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial when installed with a grounding conductor in close proximity that conforms to NEC section 311.36 and 250.4(A)(5), and where su- perior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated at -35°C for cold bend when UL listed. Rated at -25°C for cold bend and cold impact and marked with "LTDD" when CSA listed or dual UL/CSA listed. ST1 (low smoke) Rated for sizes 1/0 and larger. PVC jacket is made with SIM technology and has a coefficient of friction COF of 0.2. Cable can be installed in conduit without the aid of lubrication. Rated for 1000 lbs./FT maximum sidewall pressure. 2x5 mils tape shield for higher short circuit withstand.
Specifications:
Sample Print Legend:
SOUTHWIRE [SYMBOL - LIGHTING BOLT] #P# (UL/CSA) 1/C [#AWG or #kcmil] AL 220 MILS NL-EPR 15KV 133% INS LEVEL 25% TS MV-105 FOR CT USE SUN. RES. TC-ER(CSA 1/0 LARGER) FOR DIRECT BURIAL FT4 -ST1 YEAR (NESC) [SEQUENTIAL FEET MARKS]
Table 1 – Weights and Measurements
| Stock Number | Cond. Size | Strand Count | Diameter Over Conductor | Diameter Over Insulation | Diameter Over Insulation Shield | Jacket Thickness | Approx. OD | Copper Weight | Aluminum Weight | Approx. Weight | Max Pull Tension | Min Bending Radius | Conduit Size |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. of Strands | inch | inch | inch | mil | inch | lb/1000ft | lb/1000ft | lb/1000ft | lb | inch | inch | |
| TBA | 2 | 7 | 0.268 | 0.746 | 0.806 | 80 | 0.986 | 66 | 63 | 514 | 398 | 11.8 | 2.5 |
| TBA | 1 | 19 | 0.299 | 0.777 | 0.837 | 80 | 1.017 | 69 | 79 | 552 | 502 | 12.2 | 2.5 |
| TBA | 1/0 | 19 | 0.336 | 0.814 | 0.874 | 80 | 1.054 | 72 | 99 | 598 | 633 | 12.6 | 2.5 |
| TBA | 2/0 | 19 | 0.376 | 0.854 | 0.914 | 80 | 1.094 | 75 | 126 | 653 | 798 | 13.1 | 2.5 |
| TBA | 3/0 | 19 | 0.423 | 0.901 | 0.961 | 80 | 1.141 | 79 | 159 | 719 | 1006 | 13.7 | 3 |
| TBA | 4/0 | 19 | 0.475 | 0.953 | 1.013 | 80 | 1.193 | 83 | 200 | 796 | 1269 | 14.3 | 3 |
| 589002 | 250 | 22 | 0.52 | 1.006 | 1.066 | 80 | 1.266 | 185 | 236 | 940 | 1500 | 15.2 | 3 |
| TBA | 350 | 35 | 0.616 | 1.102 | 1.162 | 80 | 1.342 | 96 | 332 | 1037 | 2100 | 16.1 | 3.5 |
| 640814 | 500 | 34 | 0.736 | 1.246 | 1.306 | 80 | 1.506 | 222 | 471 | 1355 | 3000 | 18.1 | 4 |
| TBA | 600 | 58 | 0.813 | 1.309 | 1.369 | 80 | 1.549 | 113 | 570 | 1429 | 3600 | 18.6 | 4 |
| 589001 | 750 | 58 | 0.908 | 1.426 | 1.486 | 80 | 1.746 | 250 | 707 | 1825 | 4500 | 21 | 4.5 |
| 585564 | 1000 | 61 | 1.117 | 1.568 | 1.628 | 110 | 1.888 | 257 | 942 | 2159 | 6000 | 22.7 | 5 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Cond. Size | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Shield Short Circuit Current 6 Cycles | Allowable Ampacity In Duct 90/105°C | Allowable Ampacity In Air 90/105°C |
|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 2 | 0.266 | 0.365 | 0.046 | 0.052 | 0.725+j0.468 | 0.366+j0.057 | 2528 | 115/125 | 125/145 |
| 1 | 0.211 | 0.289 | 0.044 | 0.05 | 0.649+j0.452 | 0.290+j0.054 | 2624 | 135/145 | 145/165 |
| 1/0 | 0.167 | 0.229 | 0.041 | 0.048 | 0.590+j0.436 | 0.230+j0.052 | 2739 | 150/165 | 170/185 |
| 2/0 | 0.133 | 0.182 | 0.038 | 0.046 | 0.543+j0.419 | 0.183+j0.050 | 2863 | 170/185 | 190/215 |
| 3/0 | 0.105 | 0.144 | 0.035 | 0.045 | 0.505+j0.401 | 0.145+j0.048 | 3009 | 195/210 | 220/245 |
| 4/0 | 0.084 | 0.115 | 0.032 | 0.043 | 0.474+j0.382 | 0.116+j0.047 | 3170 | 220/240 | 255/285 |
| 250 | 0.07 | 0.096 | 0.03 | 0.042 | 0.453+j0.364 | 0.097+j0.046 | 3334 | 245/265 | 280/315 |
| 350 | 0.051 | 0.07 | 0.027 | 0.04 | 0.423+j0.334 | 0.071+j0.043 | 3631 | 295/315 | 345/385 |
| 500 | 0.036 | 0.05 | 0.024 | 0.038 | 0.393+j0.295 | 0.051+j0.042 | 4077 | 355/385 | 425/475 |
| 600 | 0.03 | 0.042 | 0.021 | 0.037 | 0.381+j0.279 | 0.043+j0.040 | 4273 | 389/421 | 471/525 |
| 750 | 0.023 | 0.033 | 0.02 | 0.037 | 0.362+j0.255 | 0.034+j0.040 | 4635 | 440/475 | 540/600 |
| 1000 | 0.017 | 0.025 | 0.015 | 0.034 | 0.343+j0.228 | 0.026+j0.039 | 5075 | 510/545 | 635/705 |
* NEC ampacities are based on:
* For Duct: Table 310.60(C)(12) Detail 1.
* For Free Air: Table 310.60(C)(4).
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft, Spacing: one diameter spacing center-to-center.
* Capacitive Reactance is between Phase-to-Shield.
* For Duct: Table 310.60(C)(12) Detail 1.
* For Free Air: Table 310.60(C)(4).
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft, Spacing: one diameter spacing center-to-center.
* Capacitive Reactance is between Phase-to-Shield.