SPEC 44080

Southwire® RenewaFLEX™ Power Cables for Battery Energy Storage Systems

Single Conductor, Copper, 2000V, XLPE insulation Type RHH/RHW-2, Flexible Power Cable.

...

Construction:

  1. Conductor:Sizes 6 - 4/0 AWG: Class K, flexible stranded, bare copper per ASTM B3 and B172.
                        Sizes 250 - 1000 kcmil: Class I, flexible stranded, bare copper per ASTM B3 and B172.
  2. Insulation: Cross Linked Polyethylene (XLPE) Type RHH/RHW-2

Applications and Features:

Southwire’s 2000 Volt power cables are suited for use in the internal wiring of Battery Energy Storage Systems (BESS), in wet and dry locations, conduits, ducts, troughs, covered trays, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation, 130°C for emergency overload, and 250°C for short circuit conditions. Gasoline and Oil Resistant. For CT USE sizes 1/0 AWG and larger. Rated 1000 lb/ft maximum sidewall pressure.

Also available in different colors like: black, red, green, brown, yellow, etc.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B172 Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • RoHS-3 Complies with European Directive 2015/863
  • Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661
  • Sample Print Legend:

    For 8 - 2 AWG:
    {SQFTG} SOUTHWIRE E30117 {UL} XX AWG CU TYPE RHH OR RHW-2 XX MILS XLP PRI/II GRI/II 2000 VOLTS

    For 1/0 - 4/0 AWG:
    {SQFTG} SOUTHWIRE E30117 {UL} XX AWG CU TYPE RHH OR RHW-2 XX MILS XLP FOR CT USE PRI/II GRI/II 2000 VOLTS

    For 250 -1000 kcmil:
    {SQFTG} SOUTHWIRE E30117 {UL} XX kcmil CU TYPE RHH OR RHW-2 XX MILS XLP FOR CT USE PRI/II GRI/II 2000 VOLTS
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandDiameter Over ConductorInsul. ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilNo.inchmilinchlb/1000ftlb/1000ft
    TBA81680.153700.2935273
    66577762590.198700.32789125
    66577644130.235700.383130174
    66577526650.302700.448211262
    6654221/010640.354900.558335416
    1389232/013300.4900.61420510
    1389244/021090.55900.71665772
    1389252506270.6051050.825764909
    1389263508930.671050.8910841242
    13892750012210.8581051.07815141710
    13895060014800.9631201.21518602112
    13895175018501.0941201.34623682650
    TBA777.719240.9661201.20622462423
    TBA100025161.191201.4330453259
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    • TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmp
    81.21320.6660.8270.05255
    61.32090.4190.520.05175
    41.53330.2630.3260.04895
    21.85300.1670.2070.045130
    1/02.28440.1050.130.044170
    2/02.410640.0850.1050.043195
    4/02.816920.0530.0660.041260
    2503.320000.0450.0560.041290
    3503.628000.0320.0410.04350
    5005.440000.0220.0290.039430
    6006.148000.0180.0240.039475
    7506.760000.0150.0210.038535
    777.7662210.0150.0210.038543
    10007.280000.0110.0160.037615
    • Ampacities based upon 2023 NEC Table 310.16 for Raceway, Cable, or Earth and NEC Table 310.17 for single conductors in Air. • Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    1 linearly interpolated value
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandDiameter Over ConductorInsul. ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilNo.mmmmmmkg/kmkg/km
    TBA81683.891.787.4477109
    66577762595.031.788.31132186
    66577644135.971.789.73193259
    66577526657.671.7811.38314390
    6654221/010648.992.2914.17499619
    1389232/0133010.162.2915.49625759
    1389244/0210913.972.2918.039901149
    13892525062715.372.6720.9611371353
    13892635089317.022.6722.6116131848
    138927500122121.792.6727.3822532545
    138950600148024.463.0530.8627683143
    138951750185027.793.0534.1935243944
    TBA777.7192424.543.0530.6333423606
    TBA1000251630.233.0536.3245314850
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    • TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmΩ/kmAmp
    830.485872.18502.710.170655
    633.029301.37471.710.167375
    438.1014820.86291.070.157595
    245.7223590.54790.680.1476130
    1/055.8837560.34450.430.1444170
    2/060.9647350.27890.340.1411195
    4/071.1275290.17390.220.1345260
    25083.8289000.14760.180.1345290
    35091.44124600.10500.130.1312350
    500137.16178000.07220.100.1280430
    600154.94213600.05910.080.1280475
    750170.18267000.04920.070.1247535
    777.7152.40276830.04920.070.1247543
    1000182.88356000.03610.050.1214615
    • Ampacities based upon 2023 NEC Table 310.16 for Raceway, Cable, or Earth and NEC Table 310.17 for single conductors in Air. • Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    1 linearly interpolated value

    Revision: 1.000.070