SPEC 41001

TELCOFLEX® L2 Telecom Power Wire and Cable

Limited smoke, Non-halogenated Insulation, 105°C Dry, 60°C Wet

...

Construction:

  1. Conductor:Class K (14-10 AWG), Class I modified bunched (8 and 6 AWG) or rope bunched (4 AWG and larger) tinned copper
  2. Separator:Opaque Mylar tape
  3. Insulation:Limited smoke, non-halogenated, 105°C Dry, 60°C Wet TelcoHyde® 5221. Conforms to UL 44, UL 758, CSA C22.2 No. 210-11, and Telcordia Specification GR-347- CORE. Insulation has a Limiting Oxygen Index of 35%

Applications and Features:

This specification covers the construction requirements for a limited smoke, non-halogenated power cable insulated with TelcoHyde® 5221. UL listed Type RHH, FT4-ST1 in accordance with the National Electrical Code. Product is for use in Central Office, CATV Head End, Data Center and Cell tower applications. Cable is suitable for UL “CT USE” (Cable Tray rated) in sizes 1/0 AWG and larger.

Specifications:

  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • ASTM B172 Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors
  • UL 44 Type RHH, FT4-ST1, VW-1, 600 Volts DC or AC
  • UL 2731 Telecommunications Central Office Power Cable
  • CSA AWM IB 105°C 600V. FT4-ST1
  • IEC including 60674 and 60332
  • RoHS Compliant Lead-Free, Silicone-Free, Halogen Free
  • ATIS 0600017.2020 List 2
  • Telcordia GR-347-CORE
  • Sample Print Legend:

    SIZES 14 AWG THROUGH 10 AWG:
    {SQFTG} SOUTHWIRE AIW{TM} CORD BRAND TELCOFLEX ® II ATIS 0600017.2020 L2 NON-HAL (UL) E30117 XXX AWG CLASS K (XXXmm2) 600 VOLTS RHH ST1 FT4 OR AWM 3578 60°C WET --- LL90458 (CSA) AWM I B 105°C 600 VOLTS FT4-ST1 {YYYY} {HH:MM} {JULIAN} --- MEETS IEC INCLUDING 60674 & 60332---MEETS GR-347

    SIZES 8 AWG THROUGH 1 AWG:
    {SQFTG} SOUTHWIRE AIW{TM} CORD BRAND TELCOFLEX ® II ATIS 0600017.2020 L2 NON-HAL (UL) E30117 XXX AWG CLASS I (XXXmm2) 600 VOLTS RHH ST1 FT4 OR AWM 3578 60°C WET --- LL90458 (CSA) AWM I B 105°C 600 VOLTS FT4-ST1 {YYYY} {HH:MM} {JULIAN} --- MEETS IEC INCLUDING 60674 & 60332---MEETS GR-347

    SIZES 1/0 AWG THROUGH 750 KCMIL:
    {SQFTG} SOUTHWIRE AIW{TM} CORD BRAND TELCOFLEX ® II ATIS 0600017.2020 L2 NON-HAL {UL} E30117 XXX AWG CLASS I (XXX{mm2}) 600 VOLTS RHH ST1 FT4 SR FOR CT USE OR AWM 3578 60°C WET --- LL90458 {CSA} AWM I B 105°C 600 VOLTS FT4-ST1 {YYYY} {HH:MM} {JULIAN} --- MEETS IEC INCLUDING 60674 & 60332---MEETS GR-347

    Packaging:

    All put-ups one length only unless agreed to otherwise. Maximum lengths per size will be advised. The ends of the cable shall be capped or taped to prevent the entrance of moisture during shipment or storage.
    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. StrandsDiameter Over Cond.Insul. ThicknessApprox. ODApprox. WeightDC Resistance @ 25°CMin Bending RadiusAllowable Ampacity 75°CAllowable Ampacity 90°C
    AWG/Kcmilstrandsinchmilinchlb/1000ftΩ/1000ftinchAmpAmp
    64884714410.073450.177262.8141.42025
    59286214410.073450.177262.8141.42025
    58868214410.073450.177262.8141.42025
    58868014410.073450.177262.8141.42025
    58868514410.073450.177272.8141.42025
    58904214410.073450.177262.8141.42025
    58904014410.073450.177262.8141.42025
    64884612650.094450.195351.7741.62530
    59286112650.094450.195351.7741.62530
    58867912650.094450.195351.7741.62530
    58867812650.094450.195351.7741.62530
    59532312650.094450.195361.7741.62530
    58904112650.094450.195351.7741.62530
    58904312650.094450.195351.7741.62530
    64931712650.094450.195351.7741.62530
    59268310260.116450.213491.0811.73540
    59268410260.116450.213491.0811.73540
    64931610260.116450.213491.0811.73540
    64446310260.116450.217501.0811.73540
    59286010260.116450.217501.0811.73540
    58868610260.116450.217501.0811.73540
    58867710260.116450.217501.0811.73540
    58867610260.116450.217501.0811.73540
    5698788410.153600.285820.6792.35055
    5928598410.153600.285820.6792.35055
    5698768410.153600.289830.6792.35055
    5717848410.153600.289830.6792.35055
    5783338410.153600.289830.6792.35055
    5698778410.153600.289830.6792.35055
    5698758410.153600.289840.6792.35055
    5712666650.186600.3181160.4352.56575
    5777246650.186600.3181160.4352.56575
    5715836650.186600.3221170.4352.66575
    5698606650.186600.3221170.4352.66575
    5714476650.186600.3221170.4352.66575
    5712646650.186600.3221170.4352.66575
    5698586650.186600.3221180.4352.66575
    5698596650.186600.3221170.4352.66575
    56982341260.260600.3921970.2743.18595
    57152941260.260600.3921970.2743.18595
    56982041260.260600.3921970.2743.18595
    56981941260.260600.3961990.2743.28595
    56982141260.260600.3961990.2743.28595
    56981841260.260600.3961990.2743.28595
    57128641260.260600.3961990.2743.28595
    56981741260.260600.3962000.2743.28595
    56975521680.315600.4472510.1723.6115130
    56975121680.315600.4472520.1723.6115130
    56975221680.315600.4472510.1723.6115130
    56974521680.315600.4512530.1723.6115130
    56974821680.315600.4512530.1723.6115130
    56975021680.315600.4512530.1723.6115130
    56975421680.315600.4512530.1723.6115130
    56975321680.315600.4512550.1723.6115130
    5696631/02660.392800.5664160.1094.5150170
    5714181/02660.392800.5664160.1094.5150170
    5696611/02660.392800.5664160.1094.5150170
    5696601/02660.392800.5704270.1094.6150170
    5714491/02660.392800.5704270.1094.6150170
    5714931/02660.392800.5704270.1094.6150170
    5696621/02660.392800.5704270.1094.6150170
    5696591/02660.392800.5704300.1094.6150170
    5778492/03420.455800.6295240.0875.0175195
    5697712/03420.455800.6295240.0875.0175195
    5697732/03420.455800.6295240.0875.0175195
    5697722/03420.455800.6335410.0875.1175195
    5697742/03420.455800.6335410.0875.1175195
    5714952/03420.455800.6335410.0875.1175195
    5714942/03420.455800.6335410.0875.1175195
    5697702/03420.455800.6335440.0875.1175195
    5714964/05320.560800.7347580.0555.9230260
    5698384/05320.560800.7347590.0555.9230260
    5698404/05320.560800.7347580.0555.9230260
    5698394/05320.560800.7387790.0555.9230260
    5698414/05320.560800.7387790.0555.9230260
    5712844/05320.560800.7387790.0555.9230260
    5712834/05320.560800.7387790.0555.9230260
    5712854/05320.560800.7387820.0555.9230260
    5698053508550.760950.96612650.0337.7310350
    5698003508550.760950.96612630.0337.7310350
    5698023508550.760950.96612650.0337.7310350
    5698013508550.760950.97012680.0337.8310350
    5698033508550.760950.97012680.0337.8310350
    5697993508550.760950.97012680.0337.8310350
    5698043508550.760950.97012690.0337.8310350
    5697973508550.760950.97012720.0337.8310350
    57916850012250.858951.09617310.0238.8380430
    58048150012250.858951.09617310.0238.8380430
    57878750012250.858951.09617310.0238.8380430
    56962750012250.858951.10017370.0238.8380430
    58370750012250.858951.10017370.0238.8380430
    56962650012250.858951.10017370.0238.8380430
    56962850012250.858951.10017370.0238.8380430
    57149850012250.858951.10017430.0238.8380430
    57173575018501.0941101.33227110.01610.7475535
    56960675018501.0941101.33227110.01610.7475535
    57622675018501.0941101.33227110.01610.7475535
    56960775018501.0941101.33627170.01610.7475535
    56960975018501.0941101.33627170.01610.7475535
    56960575018501.0941101.33627170.01610.7475535
    56961075018501.0941101.33627170.01610.7475535
    56960375018501.0941101.33627240.01610.7475535
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    *Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    *Inductive Reactance is based on non-ferrous conduit with one diameter spacing.
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

    TESTING:

    Physical and electrical tests in accordance with the requirements of UL Standard 44, Standard 758 and CSA Standard C22.2 No. 210-11 as AWM.

    LABELS

    UL and CSA tags and labels shall be applied to all packages.

    Stock Numbers and Colors

    Size (All Items are Not Braided)GrayGreenBlueRed
    GrayGreenBlueRed
    1464884701592862015886820158868001
    1264884601592861015886790158867801
    1064446301592860015886860158867701
    856987601571784015783330156987701
    657158301569860015714470157126401
    456981901569821015698180157128601
    256974501569748015697500156975401
    1/056966001571449015714930156966201
    2/056977201569774015714950157149401
    4/056983901569841015712840157128301
    35056980101569803015697990156980401
    50056962701583707015696260156962801
    75056960701569609015696050156961001

    Size (All Items are Not Braided)BlackRed - Black TracerBlue - Black TracerGray - Black Tracer
    BlackRed/BlackBlue/BlackGray/Black
    14588685015890420158904001
    1259532301589041015890430164931701
    1058867601592683015926840164931601
    8569875015698780159285901
    656985801571266015777240156985901
    456981701569823015715290156982001
    256975301569755015697510156975201
    1/056965901569663015714180156966101
    2/056977001577849015697710156977301
    4/057128501571496015698380156984001
    35056979701569805015698000156980201
    50057149801579168015804810157878701
    75056960301571735015696060157622601

    Revision: 1.000.003

    Updated On: Aug. 27, 2025, 1:02 p.m. UTC