SPEC 13076

Multi Conductor CL3P/FPLP/CMP Shielded

300V, 75°C, Multi-Conductor, Shielded, Stranded Copper, CL3P/FPLP/CMP. Minimum Operating Temperature -10°C, Maximum Operating Temperature 75°C

...

Construction:

  1. Conductor:Stranded bare copper per ASTM B3 and B8
  2. Insulation:Low Smoke Polyvinyl Chloride (LS-PVC)
  3. Shield:Aluminum foil shield with 24 AWG tinned drain wire
  4. Rip Cord:Rip cord for ease of jacket removal
  5. Jacket:White Low Smoke Polyvinyl Chloride (LS-PVC)

Applications and Features:

For use in Remote Control, Signaling, and Power-Limited circuits per NEC Article 725. Sizes 22 AWG - 16 AWG can also be used as communication circuits per NEC Article 800. Can be used in security, sound and audio, speaker cable, public address, intercom, sound reinforcement, alarm and access control circuits and power-limited controls. The conductors are cabled together; lay length varies depending on conductor count and gauge size.

Specifications:

  • UL 1424 Cables for Power-Limited Fire-Alarm Circuits
  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 13 Power-Limited Circuit Cables
  • UL 444 Communications Cables (22 AWG - 16 AWG)
  • NFPA 262
  • Sample Print Legend:

    XXAWG XX/C E57497 c{UL}US CMP/CL3P/FPLP 75°C -- CMP FT6 MADE IN USA ROHS-2 COMPLIANT -- {MM/DD/YY} {HH:MM} {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over Cond.Insul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°CJacket Color
    AWGNo.strandsinchmilmilinchlb/1000ftlb/1000ftΩ/1000ftΩ/1000ft
    22 AWG
    P20032-122270.0225150.12451116.72320.15White
    P20043-122370.0225150.13371416.72320.15White
    P20270-122470.0225150.14291716.72320.15White
    P20019-122670.0225150.168142416.72320.15White
    P20037-122870.0225150.185183116.72320.15White
    P20023-1221270.0225150.226274416.72320.15White
    20 AWG
    P30006-120270.0365150.13581410.50312.65White
    P30003-120470.0365150.156142310.50312.65White
    18 AWG
    P40133-118270.0459150.16111196.6698.035White
    P40032-118370.0459150.16516256.6698.035White
    P40073-118470.0459150.18621336.6698.035White
    P40040-118670.0459150.22332466.6698.035White
    P40070-118870.0459150.24542606.6698.035White
    P40041-1181070.0455150.28951746.6698.035White
    16 AWG
    P50002-1162190.0569150.18517254.1815.037White
    P50023-1164190.0565150.22033464.1815.037White
    14 AWG
    P60022-1142190.0705150.21626362.6313.170White
    12 AWG
    P70006-1122190.0885150.25641551.6622.002White
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item

    Revision: 1.000.009

    Updated On: April 15, 2026, 7:41 p.m. UTC