SPEC 10034

Romex® Control & Signal Cable

Class 2 Cable for Low-Voltage Power-Limited Lighting Control and Dimming. 150 Volts. Copper Conductors. SIMpull® Jacket Designed for Easier Pulling.

...

Construction:

  1. Conductor:Solid copper per ASTM B3
  2. Insulation:All phases are insulated with Polyvinyl Chloride (PVC)
  3. Jacket:Polyvinyl Chloride (PVC) jacket utilizing SIMpull® Technology. Colored light: Blue

Applications and Features:

ROMEX® SIMpull® Low-Voltage Control & Signal Cable is a class 2 power-limited circuit cable for use in lighting control and dimming applications. Rated for 150 volts per NEC Article 725. Temperature range is -20°C to +60°C. Sunlight Resistant

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • UL 13 Power-Limited Circuit Cables
  • UL 2556 Standard for Safety Wire and Cable Test Methods
  • Sample Print Legend:

    SOUTHWIRE{R} 16 AWG CU 2/C E57497 (UL) TYPE CL2
    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over Cond.Insul. ThicknessDiameter Over InsulationJacket ThicknessApprox. ODCopper WeightApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°CInductive RectanceMin Bending RadiusAllowable Ampacity 75°CAllowable Ampacity 90°C
    AWGNo.strandsinchmilinchmilinchlb/1000ftlb/1000ftΩ/1000ftΩ/1000ftΩ/1000ftinchAmpAmp
    16 AWG
    643505162SOLID0.051200.091200.106x0.18616224.1815.1890.0330.7-18
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item

    Revision: 1.000.008