SPEC 46102
CU Compressed 5/8kV NLEPR Insulation 133/100% IL SIM-PVC Jacket. MV 105 - Tray Rated - Sunlight Resistant - For Direct Burial
Type MV-105 Single Conductor Copper, 5kV 133% /8KV 100% 115 Mils No Lead Ethylene Propylene Rubber (NL-EPR) Insulation Level, Tape Shield, SIMpull Polyvinyl Chloride (PVC) Jacket, Dual Rated UL/CSA.

Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8. Tinned copper optional per ASTM B33
- Conductor Shield:Semi-conducting cross-linked copolymer
- Insulation:5kV 133% /8KV 100% Insulation Level 115 Mils No Lead Ethylene Propylene Rubber (NL-EPR)
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
- Overall Jacket:Polyvinyl Chloride (PVC)
Applications and Features:
Southwire’s 5kV 133% /8KV 100% cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial when installed with a grounding conductor in close proximity that conforms to NEC section 311.36 and 250.4(A)(5), aerially supported by a messenger and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated at -40°C for cold bend and cold impact. Marked with "LTDD" CSA listed. PVC jacket is made with SIM technology and has a coefficient of friction COF of 0.2. Cable can be installed in conduit without the aid of lubrication. Rated for 1000 lbs./FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemicals, oils and acids and are flame retardant.
Specifications:
Sample Print Legend:
{SQFTG_DUAL} SOUTHWIRE SIMpull{R} POWER CABLE {UL} XXX KCMIL CU 115 MILS NL-EPR 5KV 133%/8KV 100% INS LEVEL 25%TS MV-105 FOR CT USE SUN RES {NESC} -- {CSA} XXX KCMIL CU 2.92mm (115 mils) NL-EPR 5KV 133%/8KV 100% INS LEVEL 25%TS MV68.10 SR TC-ER 105{D}C FT4 -40{D}C LTGG -- PAT www.patentSW.com -- RoHS
Table 1 – Weights and Measurements
| Stock Number | Cond. Size | Strand Count | Diameter Over Conductor | Diameter Over Insulation | Diameter Over Insulation Shield | Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Max Pull Tension | Min Bending Radius | Conduit Size |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. of Strands | inch | inch | inch | mil | inch | lb/1000ft | lb/1000ft | lb | inch | inch | |
| 954636◊ | 2 | 7 | 0.282 | 0.545 | 0.605 | 55 | 0.755 | 255 | 454 | 530 | 9.0 | 2.5 |
| 954644 | 1 | 19 | 0.322 | 0.590 | 0.650 | 55 | 0.800 | 311 | 527 | 669 | 9.6 | 2.5 |
| 955005◊ | 1/0 | 19 | 0.361 | 0.630 | 0.690 | 80 | 0.870 | 383 | 639 | 844 | 10.4 | 2.5 |
| 955013◊ | 2/0 | 19 | 0.405 | 0.674 | 0.734 | 80 | 0.914 | 471 | 745 | 1064 | 10.9 | 3.0 |
| 955021 | 3/0 | 19 | 0.456 | 0.724 | 0.784 | 80 | 0.964 | 582 | 877 | 1342 | 11.5 | 3.0 |
| 955088◊ | 4/0 | 19 | 0.512 | 0.780 | 0.840 | 80 | 1.020 | 721 | 1039 | 1692 | 12.2 | 3.0 |
| 955039◊ | 250 | 37 | 0.558 | 0.818 | 0.878 | 80 | 1.058 | 843 | 1179 | 2000 | 12.6 | 3.0 |
| 955047◊ | 350 | 37 | 0.661 | 0.937 | 0.997 | 80 | 1.177 | 1162 | 1548 | 2800 | 14.1 | 3.5 |
| 955054◊ | 500 | 37 | 0.789 | 1.042 | 1.102 | 80 | 1.282 | 1632 | 2063 | 4000 | 15.3 | 4.0 |
| 679638 | 600 | 61 | 0.865 | 1.152 | 1.212 | 80 | 1.392 | 1949 | 2431 | 4800 | 16.7 | 4.0 |
| 955096◊ | 750 | 61 | 0.968 | 1.254 | 1.314 | 80 | 1.494 | 2419 | 2946 | 6000 | 17.9 | 4.5 |
| 955070 | 1000 | 61 | 1.117 | 1.403 | 1.463 | 80 | 1.643 | 3202 | 3793 | 8000 | 19.7 | 5.0 |
| 552012 | 2000 | 127 | 1.583 | 1.953 | 2.013 | 110 | 2.153 | 6323 | 7207 | 16000 | 25.8 | 6.0 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Conduit size based on 3 phase 40% fill-factor without ground
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Cond. Size | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Shield Short Circuit Current 6 Cycles | Allowable Ampacity In Duct 90/105°C | Allowable Ampacity In Air 90/105°C |
|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 2 | 0.162 | 0.204 | 0.034 | 0.044 | 0.346 + j0.234 | 0.024 + j0.037 | 1920 | 145/155 | 190/215 |
| 1 | 0.128 | 0.162 | 0.031 | 0.042 | 0.347 + j0.219 | 0.034 + j0.040 | 2044 | 170/180 | 225/250 |
| 1/0 | 0.102 | 0.128 | 0.028 | 0.042 | 0.348 + j0.214 | 0.040 + j0.043 | 2165 | 195/210 | 260/290 |
| 2/0 | 0.081 | 0.102 | 0.026 | 0.040 | 0.348 + j0.230 | 0.027 + j0.035 | 2302 | 220/235 | 300/330 |
| 3/0 | 0.064 | 0.081 | 0.024 | 0.039 | 0.348 + j0.230 | 0.027 + j0.036 | 2459 | 250/270 | 345/385 |
| 4/0 | 0.051 | 0.065 | 0.021 | 0.038 | 0.351 + j0.227 | 0.034 + j0.039 | 2633 | 290/310 | 400/445 |
| 250 | 0.043 | 0.056 | 0.020 | 0.037 | 0.348 + j0.234 | 0.027 + j0.040 | 2800 | 320/345 | 445/495 |
| 350 | 0.031 | 0.041 | 0.018 | 0.035 | 0.349 + j0.245 | 0.020 + j0.034 | 3120 | 385/415 | 550/615 |
| 500 | 0.022 | 0.030 | 0.015 | 0.033 | 0.350 + j0.246 | 0.020 + j0.033 | 3516 | 470/505 | 695/775 |
| 600 | 0.018 | 0.026 | 0.014 | 0.033 | 0.464 + j0.490 | 0.102 + j0.041 | 3782 | 505/544 | 777/865 |
| 750 | 0.014 | 0.023 | 0.013 | 0.032 | 0.351 + j0.227 | 0.034 + j0.040 | 4102 | 585/630 | 900/1000 |
| 1000 | 0.011 | 0.019 | 0.011 | 0.031 | 0.350 + j0.246 | 0.020 + j0.033 | 4563 | 670/720 | 1075/1200 |
| 2000 | 0.005 | 0.017 | 0.010 | 0.030 | 0.527 + j0.347 | 0.167 + j0.049 | 6174 | 1070/1150 | 1605/1790 |
* NEC ampacities are based on:
* For Duct: Table 310.60(C)(11) Detail 1.
* For Free Air: Table 310.60(C)(3).
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft, Spacing: one diameter spacing center-to-center..
* Capacitive Reactance is between Phase-to-Shield.
* For Duct: Table 310.60(C)(11) Detail 1.
* For Free Air: Table 310.60(C)(3).
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft, Spacing: one diameter spacing center-to-center..
* Capacitive Reactance is between Phase-to-Shield.