SPEC 83351

Transformer Riser Wire, Protected Ground Wire (PGW), Cathodic Protection (CP) Cables, XLPE

Black Cross Linked Polyethylene Covered. Solid or Stranded Soft Drawn Copper Conductor

...

Construction:

  1. Conductor:Conductors are solid or stranded compressed copper
  2. Covering:Black Cross Linked Polyethylene (XLPE)

Applications and Features:

Used as covered grounding conductors, protected ground wires (PGW), cathodic protection (CP) cables, or on transformers as connection between line conductor and transformer primary bushing in applications where protection from momentary contact from wildlife is needed. Although not treated as an insulation, the XLPE covering does provide an increased level of protection from momentary grounded contacts caused by wildlife, excessive wind and tree limbs or other grounded objects in the proximity of the high voltage lead. May be used on distribution system voltages up to 35kV line-to-line.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ICEA S-70-547 Weather Resistant Polyethylene Covers Conductors
  • Table 1 – Weights and Measurements
    Stock NumberPhase Cond. SizePhase StrandDia. Over Phase ConductorPhase Insul. ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.inchmilinchlb/1000ft
    4963726SOLID0.1781100.382117
    625281670.1781100.398122
    1391784SOLID0.2251100.424170
    663619470.2251100.445177
    TBA2SOLID0.258450.348229
    440800270.2831100.503262
    All dimensions are nominal and subject to normal manufacturing tolerances
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Phase Cond. SizeDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzGMRAllowable Ampacity In Air 75/90°C
    AWG/KcmilΩ/1000ftΩ/1000ftΩ/1000ftftAmp
    60.4110.510.0510.06795/105
    60.4110.510.0510.06795/105
    40.2580.320.0480.084125/140
    40.2580.320.0480.084125/140
    20.1620.2010.0450.105170/190
    20.1620.2010.0450.105170/190