SPEC 45252

CU 600/1000V XLPE Insulation PVC Jacket XHHW-2. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free

Type TC-ER Power Cable 600 or 1000 Volt Three Conductor Copper, Cross Linked Polyethylene (XLPE) insulation XHHW-2 Polyvinyl Chloride (PVC) Jacket with 1 Copper Ground (Bare or Insulated). CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free.

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation:Cross Linked Polyethylene (XLPE) Type XHHW-2
  3. Grounding Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8. (When present, cable conductor sizes 8 & 6 AWG have an insulated green ground)
  4. Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
  5. Binder:Polyester flat thread binder tape for cable sizes larger than 2 AWG
  6. Overall Jacket:Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire’s 600 or 1000 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Sunlight Resistant - For Direct Burial - Silicone Free

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Sample Print Legend:

    Bare Ground: {SQFTG} SOUTHWIRE® {UL} XX AWG (X.XX{mm2}) 3/C TYPE TC-ER XHHW-2 CDRS 90°C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600V or 1000V {NOM}-ANCE XHHW-2 CT FT4 SR 600V 90C

    Green Ground: {SQFTG} SOUTHWIRE® {UL} XX AWG (X.XX{mm2}) CU 3/C TYPE TC-ER XHHW-2 CDRS GW 1 X X AWG CU GREEN INSULATED 90°C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600V or 1000V {NOM}-ANCE XHHW-2 CT FT4 SR 600V 90C
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberStrand CountDiameter Over ConductorInsul. ThicknessGroundJacket ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilNo. of StrandsinchmilNo. x AWGmilinchlb/1000ftlb/1000ft
    5551968370.14145- x -600.627154283
    4805908370.141451 x 10 GG600.688186327
    5551956370.17745- x -600.704245386
    4806086370.177451 x 8 GG600.782297466
    4806164370.225451 x 8600.806441612
    4806242370.282451 x 6800.982702927
    48063213190.322551 x 6801.1068641142
    4806401/03190.361551 x 6801.20010691417
    4806572/03190.405551 x 6801.29513261723
    4806653/03190.456551 x 4801.39916992065
    4806734/03190.512551 x 4801.49421092502
    4806812503370.558651 x 4801.61924692940
    6722063503370.661651 x 11151.89735354322
    4807073503370.661651 x 31151.91034384127
    5880133503370.661651 x 3/01152.09337974602
    4807154003370.705651 x 31152.01439064756
    5824355003370.789651 x 2 GG1102.15548785805
    4807235003370.789651 x 21152.16748845701
    8901485003370.789651 x 1/01152.16750075929
    5836975003370.789651 x 2/01152.27450926099
    5931736003610.865801 x 3/01152.41761367286
    6657666003610.865801 x 1/01152.41759427038
    8903886003610.865801 x 21152.41758206812
    TBA6003610.865801 x 21102.43658146950
    6657686003610.865801 x 4001152.50368607994
    6722106003610.865801 x 2501152.57863927594
    5893597503610.968801 x 4/01152.63176768996
    5544107503610.968801 x 11152.63172778597
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    GG: Green Insulated Ground
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeCond. NumberMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity At 75°CAllowable Ampacity At 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    555196832.53960.6530.7860.0525055
    480590832.83960.6530.7860.0525055
    555195632.86290.4110.4950.0516575
    480608633.16290.4110.4950.0516575
    480616433.210010.2580.3100.0488595
    480624233.915920.1620.1950.045115130
    480632135.520080.1280.1540.046130145
    4806401/036.025340.1020.1220.044150170
    4806572/036.531940.0810.0970.043175195
    4806653/037.040270.0640.0780.042200225
    4806734/037.550780.0510.0620.041230260
    48068125038.160000.0430.0530.041255290
    67220635039.584000.0310.0390.040310350
    48070735039.684000.0310.0390.040310350
    588013350312.684000.0310.0390.040310350
    480715400312.196000.0270.0350.040335380
    582435500312.9120000.0220.0290.039380430
    480723500313.0120000.0220.0290.039380430
    890148500313.0120000.0220.0290.039380430
    583697500313.6120000.0220.0290.039380430
    593173600314.5144000.0180.0250.039420475
    665766600314.5144000.0180.0250.039420475
    890388600314.5144000.0180.0250.039420475
    TBA600314.6144000.0180.0250.039420475
    665768600315.0144000.0180.0250.039420475
    672210600315.5144000.0180.0250.039420475
    589359750315.8180000.0140.0220.038475535
    554410750315.8180000.0140.0220.038475535
    *Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.

    Revision: 1.000.011

    Updated On: Dec. 31, 2024, 11:07 p.m. UTC