SPEC 70126

300V ROYAL® SJOOW Cord with Black Jacket 90°C.

300 Volt, 90°C Flexible Cord. Heat, Moisture and Oil Resistant EPDM Rubber Insulation and Sunlight, Heat, Moisture and Oil Resistant Flexible CPE Jacket

...

Construction:

  1. Conductor:Class K stranded bare copper per ASTM B-174
  2. Insulation:Heat, moisture and oil resistant EPDM
  3. Filler:Waxed paper fillers, with a tissue-paper separator wrapped around the assembly
  4. Jacket:Black Sunlight, Heat, Moisture and Oil Resistant Flexible CPE (Other colors available upon request)

Applications and Features:

Southwire Type SJOOW Flexible Cords UL/ CSA listed are permitted for use as specified by Article 400 and related articles of the 2014 National Electrical Code. The cable is rated -40°C to 90°C, water, oil, and weather resistant, designed for hard usage on industrial equipment, heavy tools, battery chargers, portable lights welding leads, marine dockside power, power extensions and mining applications.

Specifications:

  • UL 62 Flexible Cords and Cables
  • CSA C22.2 No. 49 Flexible Cords and Cables
  • Passes CSA FT2 Flame Test
  • RoHS-3 Complies with European Directive 2015/863
  • NEC Article 400 Flexible Cords, Cables and Fixture Wire
  • NEC Article 501.140 Class I Division 2
  • Federal Specification J-C-580B
  • Sample Print Legend:

    SOUTHWIRE® ROYAL® CORD XX/C XX AWG (XXmm2) SJOOW E46194 (UL) 300V -40C TO 90C -- CSA LL90458 SJOOW 300V -40C TO 90C FT2 WATER RESISTANT

    Packaging:

    Standard lengths: 250', 500' and 1,000' reels. Other lengths available upon request.
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberCond. StrandsInsul. ThicknessJacket ThicknessApprox. ODApprox. WeightAmpacityDC ResistanceInsul. ColorJacket Color
    AWG/KcmilNo.No.milmilinchlb/1000ftAmpΩ/1000ft
    5579611824130400.2946106.659BK,WEBK
    5581161821630400.28851106.659BK,WEBK
    5581171831630400.316176.659BK,WE,GNBK
    5581201841630400.3336966.659BK,WE,RD,GNBK
    5581181622630400.31358134.181BK,WEBK
    5602541626530400.32566134.181BK,WEBK
    5580851632630400.33572104.181BK,WE,GNBK
    5581191642630350.368484.181BK,WE,RD,GNBK
    5581211424130400.34373182.621BK,WEBK
    5580861434130450.37398152.621BK,WE,GNBK
    5581231444130400.4121122.621BK,WE,RD,GNBK
    5600151226530600.43114251.652BK,WEBK
    5580871236530600.45145201.652BK,WE,GNBK
    5581241246530500.498179161.652BK,WE,RD,GNBK
    55837810210445700.558182301.04BK,WEBK
    55812510310445750.574234251.04BK,WE,GNBK
    55812610410445700.63290201.04BK,WE,RD,GNBK
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Ampacities are based on TABLE 400.5(A)(1) of the 2023 National Electrical Code and CEC Table 12.
    ** Not a Federal and Military Specification JC-580B
    ***No Fillers or Separator
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Weights and Measurements (Metric)
    Stock NumberCond. SizeCond. NumberCond. StrandsInsul. ThicknessJacket ThicknessApprox. ODApprox. WeightAmpacity *DC ResistanceInsul. ColorJacket Color
    AWG/KcmilNo.No.mmmmmmkg/kmAmpΩ/km
    557961182410.761.027.37681021.85BK,WEBK
    558116182160.761.027.32761021.85BK,WEBK
    558117183160.761.027.8791721.85BK,WE,GNBK
    558120184160.761.028.46103621.85BK,WE,RD,GNBK
    558118162260.761.027.95861313.72BK,WEBK
    560254162650.761.028.25981313.72BK,WEBK
    558085163260.761.028.511071013.72BK,WE,GNBK
    558119164260.760.899.14125813.72BK,WE,RD,GNBK
    558121142410.761.028.71109188.60BK,WEBK
    558086143410.761.149.47146158.60BK,WE,GNBK
    558123144410.761.0210.16180128.60BK,WE,RD,GNBK
    560015122650.761.5210.92170255.42BK,WEBK
    558087123650.761.5211.43216205.42BK,WE,GNBK
    558124124650.761.2712.65266165.42BK,WE,RD,GNBK
    5583781021041.141.7814.17271303.41BK,WEBK
    5581251031041.141.9114.58348253.41BK,WE,GNBK
    5581261041041.141.7816.00432203.41BK,WE,RD,GNBK
    * Ampacities are based on TABLE 400.5(A)(1) of the 2023 National Electrical Code and CEC Table 12.