SPEC 70070

600V SEOPRENE® SEOOW Cord Control 105°C. Silicone-Free

600 Volt Cord. -50°C to 105°C Premium Oil Resistance, Sunlight, Water Resistance and Flame Retardant

...

Construction:

  1. Conductor:Class K stranded bare copper per ASTM B-174
  2. Insulation:Heat, moisture and oil resistant TPE
  3. Filler:Non-wicking polypropylene fillers, with a tissue-paper separator wrapped around the assembly
  4. Jacket:TPE

Applications and Features:

Southwire Type SEOOW Flexible Cords UL/ CSA listed are permitted for use as specified by Article 400 and related articles of the 2020 National Electrical Code. The cable is rated -50°C to 105°C, water, oil, and weather resistant. Southwire Type SEOOW Flexible Cords are designed for extra hard usage on industrial equipment, heavy tools, battery chargers, portable lights, welding leads, marine dockside power, power extensions and mining applications.

Specifications:

  • UL 62 Flexible Cords and Cables
  • CSA C22.2 No. 49 Flexible Cords and Cables
  • Passes CSA FT2 Flame Test
  • RoHS-3 Complies with European Directive 2015/863
  • NEC Article 400 Flexible Cords, Cables and Fixture Wire
  • NEC Article 501.140 Class I Division 2
  • Sample Print Legend:

    SOUTHWIRE® SEOPRENE® CORD X/C XX AWG (X.XXmm2) SEOOW E46194 (UL) 600V -50C TO 105C -- CSA LL90458 SEOOW 600V -50C TO 105C FT2 WATER RESISTANT

    Packaging:

    Standard lengths: 250', 500' and 1,000' reels. Other lengths available upon request.
    Table 1 – Weights and Measurements
    Stock NumberCCI Part #Cond. SizeCond. NumberCond. StrandsInsul. ThicknessJacket ThicknessApprox. ODApprox. WeightAmpacityInsul. ColorJacket Color
    AWG/KcmilNo.No.milmilinchlb/1000ftAmp
    550560222251821630600.3425210BK,WEBK
    550561223251831630650.365647BK,WE,GNBK
    551469224251841630600.387745WE,BK,GN,RDBK
    569645305051851630850.4621065BK,WE,RD,GN,OEBK
    598758306051861630800.4841165BK,WE,RD,GN,OE,BEBK
    598728307051871630800.4881244BK,WE,RD,GN,OE,BE,WE/BKBK
    598729308051881630800.5171384BK,WE,RD,GN,OE,BE,WE/BK,RD/BKBK
    5987303100518101630800.6001703See TableBK
    5987313120518121630800.6131903See TableBK
    5987323140518141630800.6402143See TableBK
    5954873160518161630950.6972553See TableBK
    598733NA182441301000.8103443See TableBK
    550634222261622630600.3686313BK,WEBK
    550402NA1632630600.3877710BK,WE,GNBK
    550464224261642630600.416938BK,WE,GN,RDBK
    550555305061652630800.4921288BK,WE,RD,GN,OEBK
    598764--1652630800.4921308BK,WE,RD,GN,OEWE
    595375307061672630800.5251547BK,WE,RD,GN,OE,BE,WE/BKBK
    562791306061662630850.5331498BK,WE,RD,GN,OE,BEBK
    589888308061682630800.5601737BK,WE,RD,GN,OE,BE,WE/BK,RD/BKBK
    598734NA1692630800.6081945BK,WE,RD,GN,OE,BE,WE/BK,RD/BK,GN/BKBK
    5987353100616102630800.6382115See TableBK
    5948893120616122630950.6982595See TableBK
    5987363140616142630950.7252865See TableBK
    5987373160616162630950.7573165See TableBK
    595667NA16246530950.8644424See TableBK
    550562222271424145800.49711318BK,WEBK
    550398223271434145800.52213615BK,WE,GNBK
    550399224271444145900.59218012BK,WE,RD,GNBK
    550626NA1454145950.64221412BK,WE,RD,GN,OEBK
    598739306071464145950.69024712BK,WE,RD,GN,OE,BEBK
    598740307071474145950.69026110BK,WE,RD,GN,OE,BE,WE/BKBK
    598741308071484145950.74329810BK,WE,RD,GN,OE,BE,WE/BK,RD/BKBK
    5899213100714104145950.8353527See TableBK
    5504322222812265451050.57015825BK,WEBK
    550395223281236545950.60319320BK,WE,GNBK
    550397224281246545950.64223116BK,WE,RD,GNBK
    5504973050812565451050.70728416BK,WE,RD,GN,OEBK
    598745306081266545950.74531616BK,WE,RD,GN,OE,BEBK
    598746308081286545950.80437614BK,WE,RD,GN,OE,BE,WE/BK,RD/BKBK
    55043122229102104451000.61719630BK,WEBK
    55039322329103104451050.65224625BK,WE,GNBK
    55039422429104104451000.70330420BK,WE,RD,GNBK
    55087530509105104451050.76236320BK,WE,RD,GN,OEBK
    59875230709107104451150.84546917BK,WE,RD,GN,OE,BE,WE/BKBK
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Ampacities are based on TABLE 400.5(A)(1) of the 2023 National Electrical Code and CEC Table 12.
    Table 2 – Weights and Measurements (Metric)
    Stock NumberCCI Part #Cond. SizeCond. NumberCond. StrandsInsul. ThicknessJacket ThicknessApprox. ODApprox. WeightAmpacity *Insul. ColorJacket Color
    AWG/KcmilNo.No.mmmmmmkg/kmAmp
    55056022225182160.761.528.697710BK,WEBK
    55056122325183160.761.659.27957BK,WE,GNBK
    55146922425184160.761.529.831105WE,BK,GN,RDBK
    56964530505185160.762.1611.731585BK,WE,RD,GN,OEBK
    59875830605186160.762.0312.291735BK,WE,RD,GN,OE,BEBK
    59872830705187160.762.0312.401854BK,WE,RD,GN,OE,BE,WE/BKBK
    59872930805188160.762.0313.132054BK,WE,RD,GN,OE,BE,WE/BK,RD/BKBK
    598730310051810160.762.0315.242533See TableBK
    598731312051812160.762.0315.572833See TableBK
    598732314051814160.762.0316.263183See TableBK
    595487316051816160.762.4117.703793See TableBK
    598733NA1824410.762.5420.575123See TableBK
    55063422226162260.761.529.359413BK,WEBK
    550402NA163260.761.529.8311510BK,WE,GNBK
    55046422426164260.761.5210.571388BK,WE,GN,RDBK
    55055530506165260.762.0312.501908BK,WE,RD,GN,OEBK
    598764--165260.762.0312.501938BK,WE,RD,GN,OEWE
    59537530706167260.762.0313.332297BK,WE,RD,GN,OE,BE,WE/BKBK
    56279130606166260.762.1613.542228BK,WE,RD,GN,OE,BEBK
    58988830806168260.762.0314.222577BK,WE,RD,GN,OE,BE,WE/BK,RD/BKBK
    598734NA169260.762.0315.442895BK,WE,RD,GN,OE,BE,WE/BK,RD/BK,GN/BKBK
    598735310061610260.762.0316.213145See TableBK
    594889312061612260.762.4117.733855See TableBK
    598736314061614260.762.4118.424265See TableBK
    598737316061616260.762.4119.234705See TableBK
    595667NA1624650.762.4121.956584See TableBK
    55056222227142411.142.0312.6216818BK,WEBK
    55039822327143411.142.0313.2620215BK,WE,GNBK
    55039922427144411.142.2915.0426812BK,WE,RD,GNBK
    550626NA145411.142.4116.3131812BK,WE,RD,GN,OEBK
    59873930607146411.142.4117.5336812BK,WE,RD,GN,OE,BEBK
    59874030707147411.142.4117.5338810BK,WE,RD,GN,OE,BE,WE/BKBK
    59874130807148411.142.4118.8744310BK,WE,RD,GN,OE,BE,WE/BK,RD/BKBK
    589921310071410411.142.4121.215247See TableBK
    55043222228122651.142.6714.4823525BK,WEBK
    55039522328123651.142.4115.3228720BK,WE,GNBK
    55039722428124651.142.4116.3134416BK,WE,RD,GNBK
    55049730508125651.142.6717.9642316BK,WE,RD,GN,OEBK
    59874530608126651.142.4118.9247016BK,WE,RD,GN,OE,BEBK
    59874630808128651.142.4120.4256014BK,WE,RD,GN,OE,BE,WE/BK,RD/BKBK
    550431222291021041.142.5415.6729230BK,WEBK
    550393223291031041.142.6716.5636625BK,WE,GNBK
    550394224291041041.142.5417.8645220BK,WE,RD,GNBK
    550875305091051041.142.6719.3554020BK,WE,RD,GN,OEBK
    598752307091071041.142.9221.4669817BK,WE,RD,GN,OE,BE,WE/BKBK
    * Ampacities are based on TABLE 400.5(A)(1) of the 2023 National Electrical Code and CEC Table 12

    Color Table ( / means stripe RD/WE is Red with White Stripe)

    Stock NumberSize (AWG)Conductor NumberInsulation ColorFiller/Binder
    5987301810BK,WH,RD,GN,OE,BE,WE/BK,RD/BK,GN/BK,OE/BKPoly/Paper
    5987311812BK,WH,RD,GN,OE,BE,WE/BK,RD/BK,GN/BK,OE/BK,BE/BK,BK/WEPoly/Paper
    5987321814BK,WH,RD,GN,OE,BE,WE/BK,RD/BK,GN/BK,OE/BK,BE/BK,BK/WE,RD/WE,GN/WEPoly/Paper
    5954871816BK,WH,RD,GN,OE,BE,WE/BK,RD/BK,GN/BK,OE/BK,BE/BK,BK/WE,RD/WE,GN/WE,BE/WE,BK/RDPoly/Paper
    5987331824BK,WH,RD,GN,OE,BE,WE/BK,RD/BK,GN/BK,OE/BK,BE/BK,BK/WE,RD/WE,GN/WE,BE/WE,BK/RD,WE/RD,OE/RD,BE/RD,RD/GN,OE/GN,BK/WE,WE/BK,RD/BKPoly/Paper
    5987351610BK,WH,RD,GN,OE,BE,WE/BK,RD/BK,GN/BK,OE/BKPoly/Paper
    5948891612BK,WH,RD,GN,OE,BE,WE/BK,RD/BK,GN/BK,OE/BK,BE/BK,BK/WEPoly/Paper
    5987361614BK,WH,RD,GN,OE,BE,WE/BK,RD/BK,GN/BK,OE/BK,BE/BK,BK/WE,RD/WE,GN/WEPoly/Paper
    5987371616BK,WH,RD,GN,OE,BE,WE/BK,RD/BK,GN/BK,OE/BK,BE/BK,BK/WE,RD/WE,GN/WE,BE/WE,BK/RDPoly/Paper
    5956671624BK,WH,RD,GN,OE,BE,WE/BK,RD/BK,GN/BK,OE/BK,BE/BK,BK/WE,RD/WE,GN/WE,BE/WE,BK/RD,WE/RD,OE/RD,BE/RD,RD/GN,OE/GN,BK/WE,WE/BK,RD/BKPoly/Paper
    5899211410BK,WH,RD,GN,OE,BE,WE/BK,RD/BK,GN/BK,OE/BKPoly/Paper

    Revision: 1.000.014

    Updated On: Aug. 27, 2025, 2:15 p.m. UTC