SPEC 44104
5/C CU 2000V EPDM/CPE Type W Industrial Grade Cable 90°C. MSHA Approved
Flexible Copper conductors, Ethylene Propylene Diene Monomer (EPDM) insulation, Single Layer Chlorinated Polyethylene (CPE) Jacket

Construction:
- Conductor:Bare, soft drawn, annealed, flexible, rope-lay stranded copper per ASTM B3/B172
- Separator Tape:Non-conducting tape applied between the conductor and insulation to facilitate stripping
- Insulation:Ethylene Propylene Diene Monomer (EPDM). Color coded black, white, red, green, orange
- Fillers:Jute fillers applied as needed to round the cable core
- Reinforcement Binder:Reinforcing binder with twine applied over the core
- Jacket:Black, flame resistant, thermosetting Chlorinated Polyethylene (CPE)
Applications and Features:
Southwire Type W cable is a heavy-duty industrial cable for use in flexible, portable, and extra-hard usage applications per NEC Article 400. Suitable for continuous submersion in water – ideal for submersible pumps. Also suitable for use in light to medium-duty mining applications. Sunlight and oil resistant. Highly flexible and easy to work with in cold conditions. Not for use as permanent building wiring. Meets FT-5 Flame Test. cUL listing on select items only.
Specifications:
Sample Print Legend:
SOUTHWIRE(R) ROYAL(R) XXX AWG (XX.Xmm2) X/C TYPE W PORTABLE POWER CABLE E172226 (UL) 2000V 90C DRY 90C WET SUN RES -- 156205 CSA TYPE W 2000V -40C FT1 FT5 P-07-KA100010-MSHA
Table 1 – Weights and Measurements
| Stock Number | Cond. Size | Cond. Number | Cond. Strands | Diameter Over Conductor | Insul. Thickness | Jacket Thickness | Approx. OD | Approx. Weight | Jacket Color |
|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | No. | inch | mil | mil | inch | lb/1000ft | ||
| 571259 | 8 | 5 | 71 | 0.145 | 60 | 138 | 1.044 | 663 | BK |
| 570257† | 6 | 5 | 65 | 0.186 | 60 | 171 | 1.206 | 930 | BK |
| 570255 | 4 | 5 | 112 | 0.235 | 60 | 189 | 1.382 | 1339 | BK |
| 571483 | 2 | 5 | 168 | 0.291 | 60 | 187 | 1.593 | 1826 | BK |
| TBA | 1 | 5 | 224 | 0.3 | 80 | 205 | 1.655 | 1257 | BK |
| 570097 | 1/0 | 5 | 259 | 0.379 | 80 | 226 | 1.973 | 2962 | BK |
| 571470 | 2/0 | 5 | 324 | 0.4 | 80 | 226 | 2.066 | 3393 | BK |
| 571472 | 3/0 | 5 | 418 | 0.48 | 80 | 226 | 2.203 | 4063 | BK |
| 570253 | 4/0 | 5 | 532 | 0.53 | 80 | 242 | 2.41 | 5257 | BK |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
† Wax paper filler (instead of jute filler)
† Wax paper filler (instead of jute filler)
Table 2 – Electrical and Engineering Data
| Cond. Size | DC Resistance @ 25°C | AC Resistance @ 90°C | Inductive Reactance | Max Pull Tension | Min Bending Radius | Allowable Ampacity In Air 60°C | Allowable Ampacity In Air 75°C | Allowable Ampacity In Air 90°C |
|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | Ω/1000ft | Ω/1000ft | Ω/1000ft | lb | inch | Amp | Amp | Amp |
| 8 | 0.654 | 0.812 | 0.052 | 660 | 5.2 | 38 | 46 | 52 |
| 6 | 0.419 | 0.52 | 0.051 | 1049 | 6 | 50 | 62 | 70 |
| 4 | 0.263 | 0.326 | 0.048 | 1669 | 6.9 | 67 | 81 | 91 |
| 2 | 0.166 | 0.206 | 0.045 | 2654 | 8 | 90 | 106 | 122 |
| 1 | 0.132 | 0.164 | 0.046 | 3347 | 8.3 | 105 | 125 | 142 |
| 1/0 | 0.105 | 0.13 | 0.044 | 4224 | 9.9 | 121 | 145 | 164 |
| 2/0 | 0.084 | 0.104 | 0.043 | 5324 | 12.4 | 139 | 166 | 190 |
| 3/0 | 0.066 | 0.082 | 0.042 | 6712 | 13.2 | 161 | 193 | 219 |
| 4/0 | 0.053 | 0.066 | 0.041 | 8464 | 14.5 | 186 | 222 | 253 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
Revision: 1.000.006
Updated On: May 6, 2025, 6:51 p.m. UTC


