SPEC 44100
1/C CU 2000V EPDM/CPE Type W RHH/RHW-2 Industrial Grade Cable 90°C. MSHA Approved
Flexible Copper Conductors, Ethylene Propylene Diene Monomer (EPDM) Insulation, Single Layer Chlorinated Polyethylene (CPE) Jacket. Type RHH/RHW-2 90°C Wet and Dry

Construction:
- Conductor:Bare, soft drawn, annealed, flexible, rope-lay stranded copper per ASTM B3/B172
- Separator Tape:Non-conducting tape applied between the conductor and insulation to facilitate stripping
- Insulation:Ethylene Propylene Diene Monomer (EPDM)
- Reinforcement Binder:Reinforcing twine.
- Jacket:Black, flame resistant, thermosetting Chlorinated Polyethylene (CPE)
Applications and Features:
Southwire Type W cable is a heavy-duty industrial cable for use in flexible, portable, and extra-hard usage applications per NEC Article 400. Suitable for continuous submersion in water ideal for submersible pumps. Also suitable for use in light to medium-duty mining applications. Sunlight and oil resistant. Highly flexible and easy to work with in cold conditions. Approved for use per the NEC® as Type RHH/RHW-2 90°C wet or dry. Meets FT-1 and FT-5 Flame Tests.
Specifications:
Sample Print Legend:
SOUTHWIRE{R} ROYAL{R} XXX AWG (XX{mm2}) TYPE W PORTABLE POWER CABLE E172226 MASTER-DESIGN {UL} RHH/RHW-2 2000V 90{D}C DRY 90{D}C WET SUN RES -- LL90458 {CSA} TYPE W 2000V -40{D}C FT1 FT5 P-07-KA100009-MSHA
Table 1 – Weights and Measurements
| Stock Number | Cond. Size | Cond. Number | Cond. Strands | Diameter Over Conductor | Insul. Thickness | Jacket Thickness | Approx. OD | Approx. Weight | Jacket Color |
|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | No. | inch | mil | mil | inch | lb/1000ft | ||
| 599664 | 8 | 1 | 168 | 0.145 | 60 | 83 | 0.465 | 141 | BK |
| 599718 | 6 | 1 | 273 | 0.186 | 60 | 105 | 0.542 | 202 | BK |
| 640807 | 4 | 1 | 427 | 0.235 | 60 | 105 | 0.592 | 267 | BK |
| 640810 | 2 | 1 | 259 | 0.291 | 60 | 105 | 0.686 | 366 | BK |
| 641392 | 1 | 1 | 259 | 0.3 | 80 | 105 | 0.726 | 441 | BK |
| 641395 | 1/0 | 1 | 259 | 0.379 | 80 | 105 | 0.779 | 530 | BK |
| 641398 | 2/0 | 1 | 324 | 0.4 | 80 | 105 | 0.848 | 637 | BK |
| 641388 | 3/0 | 1 | 418 | 0.48 | 80 | 105 | 0.864 | 758 | BK |
| 641402 | 4/0 | 1 | 532 | 0.53 | 80 | 105 | 0.921 | 912 | BK |
| 641405 | 250 | 1 | 608 | 0.605 | 95 | 105 | 1.031 | 1079 | BK |
| 641409 | 350 | 1 | 893 | 0.67 | 95 | 105 | 1.13 | 1434 | BK |
| 641412 | 500 | 1 | 1221 | 0.858 | 95 | 105 | 1.274 | 1923 | BK |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
Table 2 – Electrical and Engineering Data
| Cond. Size | DC Resistance @ 25°C | AC Resistance @ 90°C | Inductive Reactance | Max Pull Tension | Min Bending Radius | Allowable Ampacity In Air 60°C | Allowable Ampacity In Air 75°C | Allowable Ampacity In Air 90°C |
|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | Ω/1000ft | Ω/1000ft | Ω/1000ft | lb | inch | Amp | Amp | Amp |
| 8 | 0.654 | 0.812 | 0.052 | 132 | 1.9 | 55 | 50 | 40 |
| 6 | 0.419 | 0.52 | 0.051 | 209 | 2.2 | 75 | 65 | 55 |
| 4 | 0.263 | 0.326 | 0.048 | 333 | 2.4 | 95 | 85 | 70 |
| 2 | 0.166 | 0.206 | 0.045 | 530 | 2.7 | 130 | 115 | 95 |
| 1 | 0.132 | 0.164 | 0.046 | 669 | 2.9 | 145 | 130 | 110 |
| 1/0 | 0.105 | 0.13 | 0.044 | 844 | 3.1 | 170 | 150 | 125 |
| 2/0 | 0.084 | 0.104 | 0.043 | 1064 | 3.4 | 195 | 175 | 145 |
| 3/0 | 0.066 | 0.082 | 0.042 | 1342 | 3.5 | 225 | 200 | 165 |
| 4/0 | 0.053 | 0.066 | 0.041 | 1692 | 3.7 | 260 | 230 | 195 |
| 250 | 0.045 | 0.056 | 0.041 | 2000 | 5.2 | 290 | 255 | 215 |
| 350 | 0.032 | 0.041 | 0.04 | 2800 | 5.6 | 350 | 310 | 260 |
| 500 | 0.022 | 0.029 | 0.039 | 4000 | 6.4 | 430 | 380 | 320 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
Revision: 1.000.007
Updated On: May 6, 2025, 6:45 p.m. UTC




