SPEC 25066

DURAGROUND™ CU 600V XLPE Insulation. RHH/RHW-2/RW90 UL & CSA

Single Copper Conductors, XLPE Insulation, Sunlight Resistant, 600V, 90°C MAX, -40°C MIN, Gasoline & Oil Resistant

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation:Cross Linked Polyethylene (XLPE) Type RW90

Applications and Features:

Suitable for installation in Cable Trays and Underground Duct Banks - As per CE Code limitations (see Rule 12-2202) for grounding and bonding applications.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • CSA C22.2 No. 38 Thermoset-insulated wires and cables
  • CSA SUN RES - for Sunlight Resistant rating
  • CT USE Sizes 1/0 AWG and Larger
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • RoHS-2 (European Directive 2011/65/EU)
  • Sample Print Legend:

    E30117 {UL} XXXX KCMIL CU RHH-RHW-2 600V FOR CT USE FT4 SR PR I OR PR II 90°C WET OR DRY -40°C --- {CSA} LL90458 XXXX KCMIL (XXX mm2) RW90 600V FT4 SR -40°C XLPE --- RoHS {MMM/DD/YYYY}
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandInsul. ThicknessInsulation ColorApprox. ODApprox. WeightMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C
    AWG/KcmilNo.milinchlb/1000ftinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmp
    TBA8760Black0.261691.01320.6530.7860.05255
    6490336760Black0.3001081.22090.4110.4950.05175
    TBA4760Black0.3451551.33330.2580.3100.04895
    6490392760Black0.4032451.65300.1620.1950.045130
    TBA1/01980Black0.5213822.08440.1020.1220.044170
    6490412/01980Black0.5744872.210640.0810.0970.043195
    TBA3/01980Black0.6165882.413420.0640.0780.042225
    6490434/01980Black0.6667452.616920.0510.0620.041260
    TBA2503795Black0.7488722.920000.0430.0530.041290
    6490543503795Black0.84112183.328000.0310.0390.040350
    6490565003795Black0.96617053.840000.0220.0290.039430
    64905875061110Black1.20025496.060000.0140.0220.038535
    649060100061110Black1.34933546.780000.0110.0180.037615
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    †Ampacities derived from the 2015 Canadian Electrical Code - Table 1 - For single conductor in free air and based on an ambient temperature of 30°C. - Table 2 - for Cable in Conduit. Not more than 3 aluminum conductors in a conduit and based on an ambient temperature of 30°C.
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandInsul. ThicknessInsulation ColorApprox. ODApprox. WeightMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C
    AWG/KcmilNo.mmmmkg/kmmmnewtonΩ/kmΩ/kmΩ/kmAmp
    TBA871.52Black6.6310325.405872.142.580.170655
    649033671.52Black7.6216130.489301.351.620.167375
    TBA471.52Black8.7623133.0214820.851.020.157595
    649039271.52Black10.2436540.6423590.530.640.1476130
    TBA1/0192.03Black13.2356850.8037560.330.400.1444170
    6490412/0192.03Black14.5872555.8847350.270.320.1411195
    TBA3/0192.03Black15.6587560.9659720.210.260.1378225
    6490434/0192.03Black16.92110966.0475290.170.200.1345260
    TBA250372.41Black19.00129873.6689000.140.170.1345290
    649054350372.41Black21.36181383.82124600.100.130.1312350
    649056500372.41Black24.54253796.52178000.070.100.1280430
    649058750612.79Black30.483793152.40267000.050.070.1247535
    6490601000612.79Black34.264991170.18356000.040.060.1214615
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    †Ampacities derived from the 2015 Canadian Electrical Code - Table 1 - For single conductor in free air and based on an ambient temperature of 30°C. - Table 2 - for Cable in Conduit. Not more than 3 aluminum conductors in a conduit and based on an ambient temperature of 30°C.
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

    Revision: 1.000.006

    Updated On: Dec. 31, 2024, 11:07 p.m. UTC