SPEC 80226
MV-105 35kV AL 100% TRXLPE Two-Fifth Concentric Neutral (Based on Short Circuit) HI-DRI-PLUS® Renewable (Solar or Wind)
Moisture Blocked Aluminum Conductors. TRXLP Insulation. Copper Two-Fifth Concentric Neutrals. XLPE Jacket

Construction:
- Conductor:Moisture Blocked 1350 H16/H26 Aluminum, Class B Compressed or Compressed Unilay Stranded
- Strand Shield:Semi-conducting Crosslinked Polyethylene
- Insulation:Tree Retardant Crosslinked Polyethylene (TRXLP)
- Insulation Shield:Strippable Semi-conducting Crosslinked Polyethylene
- Concentric Neutral:Annealed Copper Wires Helically Applied Two-Fifth Concentric Neutral
- Overall Jacket & Water Block:HI-DRI-PLUS® Water Swellable Powder Black Crosslinked Polyethylene (XLPE) with Red Extruded Stripes
Applications and Features:
- Predominately used for renewable projects with wind or solar applications.
- Suitable for use in wet or dry locations, direct burial, underground ducts, and exposure to direct sunlight.
- To be used at conductor temperature not to exceed 105ºC normal operation.
- UL listed MV-105
- The concentric neutral count and size listed in Table 1 are based on the ICEA P-45-482 short circuit calculation of an MV-90 design. The short circuit value in Table 1 is calculated using a higher thermal limit of a crosslinked XLPE jacket MV-105 design.
Specifications:
Sample Print Legend:
SOUTHWIRE(R) HI-DRI-PLUS(R) (UL) XXXX KCMIL AL 345 MILS TRXLPE TYPE MV-105 35KV 100% INSUL LEVEL -- (NESC) -- SOUTHWIRE {MMM} {YYYY} NON-CONDUCTING JACKET
Table 1 – Weights and Measurements
| Stock Number | Cond. Size | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Neutral DC Resistance 25°C | Jacket Thickness | Approx. OD | Approx. Weight | Min Bending Radius | Max Pull Tension |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | inch | mil | inch | No. x AWG | Ω/1000ft | mil | inch | lb/1000ft | inch | lb | |
| 662909 | 4/0 (19) | 0.498 | 1.218 | 345 | 1.328 | 11x14 | 0.295 | 50 | 1.556 | 1049 | 7.8 | 1269 |
| 662818^ | 1000 (61) | 1.084 | 1.857 | 345 | 1.997 | 20x10 | 0.064 | 75 | 2.355 | 3019 | 14.1 | 6000 |
| 662816^ | 1250 (61) | 1.212 | 2 | 345 | 2.14 | 25x10 | 0.051 | 75 | 2.498 | 3549 | 15 | 7500 |
| 663836 | 1250 (61) | 1.212 | 2 | 345 | 2.14 | 25x10 | 0.051 | 75 | 2.498 | 3549 | 15 | 7500 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
^ Non-UL listed
^^ Hi-Dri Plus
^^ Hi-Dri Plus
Table 2 – Electrical and Engineering Data
| Cond. Size | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Short Circuit Current @ 30 Cycle | Allowable Ampacity in Duct 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 4/0 (19) | 0.084 | 0.115 | 0.056 | 0.048 | 0.359+j0.130 | 0.117+j0.053 | 5696 | 235 | 280 |
| 1000 (61) | 0.017 | 0.025 | 0.033 | 0.04 | 0.088+j0.026 | 0.033+j0.041 | 26130 | 550 | 625 |
| 1250 (61) | 0.014 | 0.022 | 0.031 | 0.038 | 0.073+j0.023 | 0.031+j0.039 | 32662 | ||
| 1250 (61) | 0.014 | 0.022 | 0.031 | 0.038 | 0.073+j0.023 | 0.031+j0.039 | 32662 |
*Ampacities for Direct Buried are based on ICEA P-117-734-2016 Single-Conductor Solid Dielectric 15-35kV. Single Circuit Flat Direct Buried Figure 3
*Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
*Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft.
*Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
*Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft.
Table 3 – Weights and Measurements (Metric)
| Stock Number | Cond. Size | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Neutral DC Resistance 25°C | Jacket Thickness | Approx. OD | Approx. Weight | Min Bending Radius | Max Pull Tension |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | mm | mm | mm | mm | No. x AWG | Ω/km | mm | mm | kg/km | mm | newton | |
| 662909 | 4/0 (19) | 12.65 | 30.94 | 8.76 | 33.73 | 11x14 | 0.97 | 1.27 | 39.52 | 1561 | 198.12 | 5647 |
| 662818^ | 1000 (61) | 27.53 | 47.17 | 8.76 | 50.72 | 20x10 | 0.21 | 1.91 | 59.82 | 4493 | 358.14 | 26700 |
| 662816^ | 1250 (61) | 30.78 | 50.80 | 8.76 | 54.36 | 25x10 | 0.17 | 1.91 | 63.45 | 5281 | 381.00 | 33375 |
| 663836 | 1250 (61) | 30.78 | 50.80 | 8.76 | 54.36 | 25x10 | 0.17 | 1.91 | 63.45 | 5281 | 381.00 | 33375 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
^ Non-UL listed
^^ Hi-Dri Plus
^^ Hi-Dri Plus
Table 4 – Electrical and Engineering Data (Metric)
| Cond. Size | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance* | Positive Sequence Impedance* | Short Circuit Current @ 30 Cycle | Allowable Ampacity in Duct 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 4/0 (19) | 0.2756 | 0.38 | 0.0171 | 0.1575 | 0.359+j0.130 | 0.117+j0.053 | 5696 | 235 | 280 |
| 1000 (61) | 0.0558 | 0.08 | 0.0101 | 0.1312 | 0.088+j0.026 | 0.033+j0.041 | 26130 | 550 | 625 |
| 1250 (61) | 0.0459 | 0.07 | 0.0094 | 0.1247 | 0.073+j0.023 | 0.031+j0.039 | 32662 | ||
| 1250 (61) | 0.0459 | 0.07 | 0.0094 | 0.1247 | 0.073+j0.023 | 0.031+j0.039 | 32662 |
*Ampacities for Direct Buried are based on ICEA P-117-734-2016 Single-Conductor Solid Dielectric 15-35kV. Single Circuit Flat Direct Buried Figure 3
*Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
*Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft.
*Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
*Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft.
Revision: 1.000.022
Updated On: Oct. 15, 2026, 2:56 p.m. UTC
Concentric Neutral Calculator