SPEC 45042

Southwire® Machine Flex® CU 600/1000V PVC-Nylon Insulation Shielded TPE Gray Jacket. THHN

Type TC-ER Shielded Machine Tray Control Cable 600/1000 Volt Copper Conductors, Polyvinyl Chloride (PVC) with nylon layer Insulation Thermoplastic Elastomer Jacket, 90°C Dry 75°C Wet -40°C Cold Impact Identification Method 4

...

Construction:

  1. Conductor:Class K, Flexible stranded bare annealed copper per ASTM B3, B172, and B174
  2. Insulation:Polyvinyl Chloride (PVC) with nylon layer THHN
  3. Ground:One Green Ground with Yellow Stripe THHN
  4. Drain Wire:Tinned copper sized one awg size smaller than phase conductor. Drain wire size is two gauge smaller than phase size
  5. Shielding:100% coverage Alum/Mylar/Alum Foil, overall 85% coverage tinned copper braid
  6. Jacket:Gray Thermoplastic Elastomer TPE: Other jacket colors available upon request

Applications and Features:

Southwire’s shielded Machine Flex® tray control cables 600/1000 Volt conform to NFPA 79 and are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 75°C in wet locations and 90°C in dry locations, 130°C for emergency overload, and 150°C for short circuit conditions. For uses in Class I, II, Division 2 hazardous locations per NEC® Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC® 336.10. Southwire’s shielded flexible machine tray cable is ideal for use in for use in CNC machines, grinding, cutting, metal forming, buffing, bottling equipment, conveyors, processing & packaging equipment, assembly lines, control panels, food and bever- age, oil sands, plant expansion, wind energy and data centers. Multiple approvals for multiple applications. Cable is rated for -40°C cold impact. Two conductor cables contain no green/yellow ground.

Specifications:

  • ASTM B172 Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors
  • ASTM B174 Standard Specification for Bunch-Stranded Copper
  • UL 13 Power-Limited Circuit Cables
  • UL 66 Fixture Wire
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 758 Standard for Appliance Wiring Material Style 2463 (80C, 600V)
  • UL 758 AWM Style 2587
  • UL 1063 Machine Tool Wiring (MTW)
  • UL 1277 TC-ER
  • UL 1690 Data Processing Cable (DP-1)
  • UL 2250 Instrumentation Tray Cable
  • UL 2277 Type WTTC
  • CSA C22.2 No. 210 Appliance wiring material products I/II A/B (Sizes 16 - 8AWG)
  • CSA C22.2 No.230 Tray Cables - Rated TC
  • CSA C22.2 No. 239 Control and instrumentation cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Exceeds Ecolab PM-40-1 Material Resistance Test With 30-day Exposure, UL Verified V747862
  • CE/RoHS-2 – The CE Marking has been applied solely to express the conformance to the material restrictions identified in the RoHS-2 (2011/65/EU) Directive
  • NFPA 79 Electrical Standard for Industrial Machinery
  • Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661
  • Sample Print Legend:

    18 - 12 AWG:
    SOUTHWIRE® XX AWG (X.XX mm2) XX/C PVC/NYLON SHLD TYPE TC-ER E75755 (UL) 600V 90°C DRY 75°C WET SUN RES OIL RES I/II DIR BUR -40°C OR MTW FLEXING OR DP-1 OR WTTC 1000V OR PLTC OR ITC OR AWM 2587 -- LL90458 (CSA) CIC/TC FT4 OR AWM I/II A/B 105°C 1000V -40°C FT4 -- {NOM}-ANCE PLTC-- {CE} ROHS-2 -- MADE IN USA

    10 AWG and Larger:
    {SQFTG} SOUTHWIRE® XX AWG (X.XX{mm2}) X/C PVC/NYLON SHLD TYPE TC E75755 {UL} 600V 90{D}C DRY 75{D}C WET SUN RES OIL RES I/II DIR BUR -40{D}C OR MTW FLEXING OR DP-1 OR WTTC 1000V OR AWM 2587 -- LL90458 {CSA} CIC/TC FT4 OR AWM I/II A/B 105{D}C 1000V -40{D}C FT4 --{NOM}-ANCE 90{D}C PVC/NYLON PVC-TPE THHN/THWN FT4 600V -- {CE} ROHS-2 -- MADE IN USA
    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over Cond.Insul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°CInductive RectanceMin Bending RadiusAllowable Ampacity 75°CAllowable Ampacity 90°CJacket Color
    AWGNo.strandsinchmilmilinchlb/1000ftlb/1000ftΩ/1000ftΩ/1000ftΩ/1000ftinchAmpAmp
    18 AWG
    677081182160.04415450.29324527.1488.6130.0363.5-14GY
    588460183160.04415450.32030637.1488.6130.0363.8-14GY
    588461184160.04415450.32636707.1488.6130.0363.9-11GY
    588462185160.04415450.35343827.1488.6130.0364.2-11GY
    588463187160.04415450.378551007.1488.6130.0364.5-9GY
    630837189160.04415450.442681297.1488.6130.0365.3-9GY
    5884641812160.04415450.478861557.1488.6130.0365.7-7GY
    5986251818160.04415600.5761192227.1488.6130.0366.9-7GY
    5986261825160.04415600.6581612897.1488.6130.0367.8-6GY
    16 AWG
    677082162260.05915450.32134664.4875.4060.0333.8-18GY
    588465163260.05915450.33143784.4875.4060.0333.9-18GY
    588466164260.05915450.36053934.4875.4060.0334.3-14GY
    588467165260.05915450.391631104.4875.4060.0334.6-14GY
    588468167260.05915450.427801354.4875.4060.0335.1-12GY
    630836169260.05915450.4911001714.4875.4060.0335.8-12GY
    5884691612260.05915600.5621282204.4875.4060.0336.7-9GY
    5986271618260.05915600.6461853034.4875.4060.0337.7-9GY
    5986281625260.05915600.7462483984.4875.4060.0338.9-8GY
    14 AWG
    677083142410.07315450.34948842.8143.3910.0584.12025GY
    588470143410.07315450.363621022.8143.3910.0584.32025GY
    588471144410.07315450.402761252.8143.3910.0584.81620GY
    588472145410.07315450.431911442.8143.3910.0585.11620GY
    588473147410.07315450.4661191782.8143.3910.0585.51417GY
    5986291412410.07315600.6231922972.8143.3910.0587.41012GY
    5986301418410.07315600.7202774122.8143.3910.0588.61012GY
    5986311425410.07315800.8753845822.8143.3910.05810.5911GY
    12 AWG
    677084122650.09415450.387701121.7742.1370.0544.62530GY
    677194123650.09415450.416911421.7742.1370.0544.92530GY
    588474124650.09415450.4501141721.7742.1370.0545.42024GY
    588476125650.09415450.4891382071.7742.1370.0545.82024GY
    588477127650.09415600.5551812681.7742.1370.0546.61721GY
    10 AWG
    6770851021050.11720600.4551021591.1111.3390.0505.43540GY
    6771961031050.11720600.5441362181.1111.3390.0506.53540GY
    5884781041050.11720600.5741772681.1111.3390.0506.82832GY
    5884791051050.11720600.6082123161.1111.3390.0507.22832GY
    5884801071050.11720600.6582803941.1111.3390.0507.82428GY
    8 AWG
    643354841680.15330600.7422924380.7150.8610.0528.94044GY
    6 AWG
    643356642590.19830600.8854636680.4500.5410.05110.65260GY
    4 AWG
    643358444200.23540801.0576749970.2820.3400.04812.66876GY
    2 AWG
    643360246510.30240801.237106014330.1790.2160.04514.892104GY
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    *Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    *Ampacities have been adjusted for more than Three Current-Carrying Conductors.
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

    Revision: 1.000.012

    Updated On: March 3, 2025, 3:32 p.m. UTC