SPEC 44066

Southwire® Machine Flex® Power PVC THHN

90°C Wet or Dry. 600 Volts. Flexible Stranded Copper Conductor. PVC Insulation and Nylon Jacket (THHN/THWN-2). Oil & Gasoline Resistant. Sunlight Resistant. Rated UL VW-1 and CSA FT1 & FT4 Flame Resistant.

...

Construction:

  1. Conductor: 8 - 4/0 AWG: Class K, flexible stranded bare copper. 250 - 750 kcmil: Class I, flexible stranded bare copper
  2. Insulation: Polyvinyl Chloride (PVC) with Nylon sheath

Applications and Features:

Southwire’s Machine Flex® power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 150°C for short circuit conditions. 1/0 AWG & larger rated for CT use.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B172 Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors
  • ASTM B174 Standard Specification for Bunch-Stranded Copper
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 758 Standard for Appliance Wiring Material Style 2463 (80C, 600V)
  • UL 1063 Machine Tool Wiring (MTW)
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test (1/0 and Larger)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • CE/RoHS-2 – The CE Marking has been applied solely to express the conformance to the material restrictions identified in the RoHS-2 (2011/65/EU) Directive
  • Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661
  • Sample Print Legend:

    8AWG-1AWG
    SOUTHWIRE #P# (UL) 1 AWG (42.406 mm2) CU TYPE THHN/THWN-2 600V 90(D)C DRY/90(D)C WET PRI/GRI VW-1 OR AWM [Applicable Styles] OR MTW SUN RES --- (CSA) T90 NYLON OR TWN75 FT1 FT4 --- CE RoHS-2 Made in USA. [SEQUENTIAL FOOTAGE MARKS]

    1/0 AWG - 500 KCMIL
    SOUTHWIRE #P# (UL) 500 KCMIL (253.35mm2) CU TYPE THHN/THWN-2 600V 90(D)C DRY/90(D)C WET PRI/GRI VW-1 FOR CT USE OR AWM [Applicable Styles] OR MTW SUN RES --- (CSA) T90 NYLON OR TWN75 FT1 FT4 --- CE RoHS-2 Made in USA. [SEQUENTIAL FOOTAGE MARKS]

    600 - 1000 KCMIL
    {SQFTG} SOUTHWIRE #P# (UL) XX KCMIL XX STRAND CLASS I (XXMM2) CU TYPE THHN/THWN-2 600V 90ºC DRY/90ºC WET PRI/GRI VW-1 FOR CT USE SUN RES OR AWM 1321 OR MTW --- (CSA) T90 NYLON OR TWN75 FT1 FT4 --- (NOM)-ANCE THWN/THHN 600V 90ºC --- CE RoHS-2 MADE IN USA

    Table 1 – Weights and Measurements
    Stock NumberCond. SizeColorDiameter Over ConductorConductor StrandingInsulation ThicknessApprox. ODCopper WeightOverall Weight
    AWG/Kcmilinchmilsinchlbs/1000ftlbs/1000ft
    TBA8BK0.153168350.2235262
    TBA6BK0.190273350.2648398
    6728674BK0.235413500.335130153
    TBA2BK0.302665500.402210243
    TBA1BK0.329836600.449260302
    6773681/0BK0.4001044600.520334374
    TBA2/0BK0.4301330600.520381426
    4571203/0BK0.4901672600.608535599
    6796074/0BK0.5502109600.664676746
    649414250BK0.605627700.747763857
    672866300BK0.638741700.7809291024
    649415350BK0.670893600.81210841172
    648948500BK0.8581221700.99815141641
    649416600BK0.9631480701.12718592033
    649549750BK1.0941850801.25823672569
    6744591000BK1.1902516801.35030453255
    6746674GN0.235413500.335130153
    6642293GN0.270525500.366169197
    4562581GN0.329836600.449260302
    6746681/0GN0.4001044600.520334374
    4562572/0GN0.4301330600.520381426
    6642173/0BN0.4901672600.608535599
    6642263/0GY0.4901672600.608535599
    6642203/0OE0.4901672600.608535599
    6642233/0YW0.4901672600.608535599
    4571213/0RD0.4901672600.608535599
    4562534/0BN0.5502109600.664676746
    4562564/0GN0.5502109600.664676746
    4562544/0OE0.5502109600.664676746
    4562554/0YW0.5502109600.664676746
    672218250BN0.605627700.747763857
    673791250GN0.605627700.747763857
    673792250GY0.605627700.747763857
    672217250OE0.605627700.747763857
    672219250YW0.605627700.747763857
    674116300BN0.638741700.7809291024
    674121300GN0.638741700.7809291024
    674120300GY0.638741700.7809291024
    674117300OE0.638741700.7809291024
    674118300YW0.638741700.7809291024
    674662350BN0.670893600.81210841172
    652964350GN0.670893600.81210841172
    674666350GY0.670893600.81210841172
    674664350OE0.670893600.81210841172
    138181350RD0.670893600.81210841172
    674665350YW0.670893600.81210841172
    646978500BN0.8581221700.99815141641
    677701500GN0.8581221700.99815141641
    646981500GY0.8581221700.99815141641
    456464500GY/PE0.8581221700.99815141641
    646979500OE0.8581221700.99815141641
    456462500PE0.8581221700.99815141641
    456461500PK0.8581221700.99815141641
    456463500TN0.8581221700.99815141641
    646980500YW0.8581221700.99815141641
    678431600BN0.9631480701.12718592033
    673748600GN0.9631480701.12718592033
    678435600GY0.9631480701.12718592033
    678432600OE0.9631480701.12718592033
    678434600YW0.9631480701.12718592033
    677721750BN1.0941850801.25823672569
    671518750GN1.0941850801.25823672569
    677725750GY1.0941850801.25823672569
    677722750OE1.0941850801.25823672569
    677723750YW1.0941850801.25823672569
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin. Bend RadiusMax Pull TensionDC Resistance at 25°CAC Resistance at 75°CInductive Reactance @ 60HzAllowable Ampacity Raceway 75°CAllowable Ampacity Raceway 90°C
    AWG/KcmilInchesLbsΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    80.81320.7150.8610.0525055
    61.02090.4500.5410.0516575
    41.33330.2820.3400.0488595
    21.65300.1790.2160.045115130
    11.66690.1370.1640.046130145
    1/02.08440.1130.1360.044150170
    2/02.010640.0900.1080.043175195
    3/02.413420.0720.0870.042200225
    4/02.616920.0570.0690.041230260
    2502.920000.0470.0570.041255290
    3003.124000.0390.0480.041285320
    3503.228000.0330.0420.040310350
    5003.940000.0230.0310.039380430
    6005.648000.0190.0270.039420475
    7506.260000.0160.0240.038475535
    10006.780000.0120.0200.037545615
    41.33330.2820.3400.0488595
    31.64200.2260.2720.047100115
    11.66690.1370.1640.046130145
    1/02.08440.1130.1360.044150170
    2/02.010640.0900.1080.043175195
    3/02.413420.0720.0870.042200225
    3/02.413420.0720.0870.042200225
    3/02.413420.0720.0870.042200225
    3/02.413420.0720.0870.042200225
    3/02.413420.0720.0870.042200225
    4/02.616920.0570.0690.041230260
    4/02.616920.0570.0690.041230260
    4/02.616920.0570.0690.041230260
    4/02.616920.0570.0690.041230260
    2502.920000.0470.0570.041255290
    2502.920000.0470.0570.041255290
    2502.920000.0470.0570.041255290
    2502.920000.0470.0570.041255290
    2502.920000.0470.0570.041255290
    3003.124000.0390.0480.041285320
    3003.124000.0390.0480.041285320
    3003.124000.0390.0480.041285320
    3003.124000.0390.0480.041285320
    3003.124000.0390.0480.041285320
    3503.228000.0330.0420.040310350
    3503.228000.0330.0420.040310350
    3503.228000.0330.0420.040310350
    3503.228000.0330.0420.040310350
    3503.228000.0330.0420.040310350
    3503.228000.0330.0420.040310350
    5003.940000.0230.0310.039380430
    5003.940000.0230.0310.039380430
    5003.940000.0230.0310.039380430
    5003.940000.0230.0310.039380430
    5003.940000.0230.0310.039380430
    5003.940000.0230.0310.039380430
    5003.940000.0230.0310.039380430
    5003.940000.0230.0310.039380430
    5003.940000.0230.0310.039380430
    6005.648000.0190.0270.039420475
    6005.648000.0190.0270.039420475
    6005.648000.0190.0270.039420475
    6005.648000.0190.0270.039420475
    6005.648000.0190.0270.039420475
    7506.260000.0160.0240.038475535
    7506.260000.0160.0240.038475535
    7506.260000.0160.0240.038475535
    7506.260000.0160.0240.038475535
    7506.260000.0160.0240.038475535
    † Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    † Ampacities have been adjusted for more than Three Current-Carrying Conductors.
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.

    Stock Codes and Colors

    Size (Strand)BlackRedBrownOrangeYellowGrayGreenPinkPurpleTanGray/PurpleGreen/Yellow
    4 (413)672867674667
    3 (525)664229
    2 (665)
    1 (836)456258
    1/0 (1044)674668677368
    2/0 (1330)456257
    3/0 (1672)457120457121664217664220664223664226
    4/0 (2109)679607456253456254456255456256679606
    250 (627)649414672218672217672219673792673791677370
    300 (741)672866674116674117674118674120674121
    350 (893)649415138181674662674664674665674666652964672017
    500 (1221)648948646978646979646980646981677701456461456462456463456464646982
    600 (1480)649416678431678432678434678435673748678436
    750 (1850)649549677721677722677723677725671518677726
    1000 (2516)674459

    Revision: 1.000.019

    Updated On: Dec. 3, 2024, 2:17 p.m. UTC