SPEC 10080

Bare Copper Solid, Compressed Class B and C

...

Construction:

  1. Conductor:Bare copper solid or compressed class B or C per ASTM B3 and ASTM B8

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrand ClassStrand CountCond. CmilCond. ShapeDiameter Over ConductorApprox. ODApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°CRated Strength
    AWG/kcmilNo. of Strandscmilinchinchlb/1000ftΩ/1000ftΩ/1000ftlb
    10614614Solid14110Bare0.0640.064122.6313.17032
    10620312Solid16530Bare0.0800.080201.6622.00252
    10626010Solid110380Bare0.1010.101321.0401.25383
    1063288Solid116510Bare0.1280.128500.6530.786132
    TBA7Solid120820Bare0.1440.144640.5190.625166
    1063856Solid126240Bare0.1620.162810.4110.495209
    TBA5Solid133090Bare0.1810.1811020.3250.391264
    1064434Solid141740Bare0.2040.2041280.2580.310333
    TBA3Solid152620Bare0.2290.2291620.2050.246420
    1065002Solid166360Bare0.2570.2572040.1620.195530
    TBA1Solid183690Bare0.2890.2892580.1280.154669
    TBA1/0Solid1105600Bare0.3240.3243250.1020.122844
    TBA2/0Solid1133100Bare0.3640.3644100.0810.0971064
    TBA3/0Solid1167800Bare0.4090.4095180.0640.0781342
    TBA4/0Solid1211600Bare0.4600.4606530.0510.0621692
    TBA14B74110Bare0.0700.070122.6313.17032
    TBA12B76530Bare0.0880.088201.6622.00252
    TBA10B710380Bare0.1130.113321.0401.25383
    1065678B716510Bare0.1410.141500.6530.786132
    TBA7B720820Bare0.1590.159640.5190.625166
    1066586B726240Bare0.1770.177810.4110.495209
    TBA5B733090Bare0.2000.2001020.3250.391264
    1067404B741740Bare0.2250.2251280.2580.310333
    TBA3B752620Bare0.2520.2521620.2050.246420
    1068642B766360Bare0.2820.2822040.1620.195530
    TBA1B1983690Bare0.3220.3222580.1280.154669
    1361681/0B19105600Bare0.3610.3613250.1020.122844
    1445192/0B19133100Bare0.4050.4054100.0810.0971064
    1445273/0B19167800Bare0.4560.4565180.0640.0781342
    1367394/0B19211600Bare0.5120.5126530.0510.0621692
    TBA250B37250000Bare0.5580.5587710.0430.0532000
    TBA300B37300000Bare0.6100.6109260.0360.0452400
    TBA350B37350000Bare0.6610.66110810.0310.0392800
    TBA400B37400000Bare0.7050.70512350.0270.0353200
    TBA450B37450000Bare0.7490.74913890.0240.0313600
    107193500B37500000Bare0.7890.81315440.0220.0294000
    TBA550B61550000Bare0.8280.82816980.0200.0264400
    TBA600B61600000Bare0.8650.86518530.0180.0254800
    TBA650B61650000Bare0.9010.90120070.0170.0235200
    TBA700B61700000Bare0.9350.93521610.0150.0225600
    107250750B61750000Bare0.9680.96823160.0140.0226000
    TBA800B61800000Bare1.0001.00024700.0130.0216400
    TBA900B61900000Bare1.0601.06027790.0120.0207200
    1072841000B611000000Bare1.1171.11730880.0110.0188000
    TBA14C194110Bare0.0730.073122.6313.17032
    TBA12C196530Bare0.0900.090201.6622.00252
    TBA10C1910380Bare0.1170.117321.0401.25383
    TBA8C1916510Bare0.1430.143500.6530.786132
    TBA7C1920820Bare0.1650.165640.5190.625166
    TBA6C1926240Bare0.1790.179810.4110.495209
    TBA5C1933090Bare0.2080.2081020.3250.391264
    TBA4C1941740Bare0.2260.2261280.2580.310333
    TBA3C1952620Bare0.2540.2541620.2050.246420
    TBA2C1966360Bare0.2860.2862040.1620.195530
    TBA1C3783690Bare0.3330.3332580.1280.154669
    TBA1/0C37105600Bare0.3730.3733250.1020.122844
    TBA2/0C37133100Bare0.4200.4204100.0810.0971064
    TBA3/0C37167800Bare0.4710.4715180.0640.0781342
    1401524/0C37211600Bare0.5290.5296530.0510.0621692
    TBA250C61250000Bare0.5750.5757710.0430.0532000
    TBA300C61300000Bare0.6300.6309260.0360.0452400
    207852350C61350000Bare0.6810.68110810.0310.0392800
    TBA400C61400000Bare0.7280.72812350.0270.0353200
    TBA450C61450000Bare0.7730.77313890.0240.0313600
    TBA500C61500000Bare0.8140.81415440.0220.0294000
    TBA550C91550000Bare0.8540.85416980.0200.0264400
    TBA600C91600000Bare0.8930.89318530.0180.0254800
    TBA650C91650000Bare0.9290.92920070.0170.0235200
    TBA700C91700000Bare0.9640.96421610.0150.0225600
    TBA750C91750000Bare0.9980.99823160.0140.0226000
    TBA800C91800000Bare1.0311.03124700.0130.0216400
    TBA900C91900000Bare1.0931.09327790.0120.0207200
    TBA1000C911000000Bare1.1521.15230880.0110.0188000
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item

    Revision: 1.000.020

    Updated On: Aug. 21, 2024, 8:23 p.m. UTC