SPEC 10015

SIMpull XHHW-2®/RW90 Aluminum with AlumaFlex® Brand Conductors

Power Cable 600 or 1000 Volts. Alumaflex® Brand Aluminum Alloy (AA-8176) Conductor. Cross-linked Polyethylene (XLPE) Insulation. Moisture Resistant High Heat.

...

Construction:

  1. Conductor:Class B compact stranded bare aluminum per ASTM B800 and ASTM B801
  2. Insulation:Heat and moisture resistant cross-linked polyethylene (XLPE) insulation in various colors

Applications and Features:

Southwire SIMpull XHHW-2®/RW90 with AlumaFlex® Brand Conductors Wire & Cable with Alumaflex® Brand conductors are primarily used in conduit and cable trays for services, feeders and branch circuits in commercial or industrial applications as specified in the National Electrical Code. XHHW-2/RW90 conductors is suitable for use in dry locations at temperatures not to exceed 90°C. Voltage for all applications is up to 1000 volts. Suitable for use in Health Care Facilities per section 517.160 of the NEC where a dielectric constant of 3.5 or less may be specified. This cable can be installed without application of pulling lubricant. RW90 is for open wiring and use in raceways (except cable troughs and ventilated flexible cableways) in dry or wet locations as per Canadian Electrical Code. For open wiring exposed to the weather.

Southwire Aluminum SIMpull® XHHW-2/RW90 conductors comply with the following:
- Federal Specification AA-59544
- NOM-ANCE, XHHW-2, 90ºC
- CT Rated- Sizes 1/0 AWG and larger
- FT4 350 Kcmil and larger
- National Electrical Code
- Gas and Oil Resistant II- All sizes
- Sunlight Resistant- Sizes 6 AWG and larger
- RoHS/Reach Compliant

Specifications:

  • ASTM B800 8000 Series Aluminum Alloy Wire
  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • CSA C22.2 No. 38 Thermoset-insulated wires and cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • NMX-J-451-ANCE Thermoset insulated wires and cables
  • NOM-063-SCFI Electrical Products – Conductors – Safety Requirements
  • Sample Print Legend:

    6 AWG thru 1 AWG
    {SQFTG} SOUTHWIRE{R} {NOLUBE}{R} {SIMPULL}{R} {ALUMAFLEX}{R} E30117 {UL} TYPE XHHW-2 6 AWG (13.3{MM2}) AL AA8176 600V/1000V SR GRII PRII - LL90458 {CSA} RW90 XLPE 6 AWG (13.3{mm2}) AL AA8176 600V GRI PRI -40{D}C SR FT1 - {NOM}-ANCE LS - PAT WWW.PATENTSW.COM

    1/0 AWG thru 300 kcmil
    {SQFTG} SOUTHWIRE{R} {NOLUBE}{R} {SIMPULL}{R} {ALUMAFLEX}{R} E30117 {UL} TYPE XHHW-2 1/0 AWG (53.5{MM2}) AL AA8176 600V/1000V SR FOR CT USE GRII PRII - LL90458 {CSA} RW90 XLPE 1/0 AWG (53.5{mm2}) AL AA8176 600V GRI PRI -40{D}C SR FT1 - {NOM}-ANCE LS - PAT WWW.PATENTSW.COM

    350 kcmil and Larger
    {SQFTG} SOUTHWIRE{R} {NOLUBE}{R} {SIMPULL}{R} {ALUMAFLEX}{R} E30117 {UL} TYPE XHHW-2 350 KCMIL (177{MM2}) AL AA8176 600V/1000V SR FOR CT USE GRII PRII FT4 - LL90458 {CSA} RW90 XLPE 350 KCMIL (177{mm2}) AL AA8176 600V GRI PRI -40{D}C SR FT4 - {NOM}-ANCE LS - PAT WWW.PATENTSW.COM
    Table 1 – Weights and Measurements
    Cond. SizeCond. NumberStrand CountDiameter Over ConductorInsul. ThicknessApprox. ODAluminum WeightApprox. Weight
    AWG/KcmilNo. of Strandsinchmilinchlb/1000ftlb/1000ft
    8170.134450.2301528
    6170.169450.2652440
    4170.212450.3093958
    2160.268450.3646286
    1180.298550.41578110
    1/01100.336550.45299134
    2/01120.376550.492125163
    3/01150.422550.539158201
    4/01190.474550.591199247
    2501220.520650.658235297
    3001210.569650.708282351
    3501350.615650.754329402
    4001350.659650.797376454
    5001340.735650.876471557
    6001370.812800.981565681
    7001580.877801.045659783
    7501610.908801.076706835
    9001580.999801.1678611003
    10001581.060801.2289421092
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    Table 2 – Electrical and Engineering Data
    Cond. SizeCond. NumberMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity At 75°CAllowable Ampacity At 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    810.9991.0721.2900.0524045
    611.11570.6740.8120.0515055
    411.22500.4240.5100.0486575
    211.53980.2670.3210.04590100
    111.75020.2110.2540.046100115
    1/011.86330.1680.2010.044120135
    2/012.07980.1330.1600.043135150
    3/012.210060.1050.1260.042155175
    4/012.412690.0840.1000.041180205
    25012.615000.0710.0860.041205230
    30012.818000.0590.0710.041230260
    35013.021000.0500.0620.040250280
    40013.224000.0440.0540.040270305
    50013.530000.0350.0440.039310350
    60013.936000.0290.0370.039340385
    70015.242000.0250.0330.038375425
    75015.445000.0240.0310.038385435
    90015.854000.0200.0270.037425480
    100016.160000.0180.0250.037445500
    *Ampacities based upon 2023 NEC Table 310.16 Raceway or Cable, Not more than 3 copper conductors on an ambient temperature of 30°C.
    *Ampacities derived from the 2021 Canadian Electrical Code. - Table 4 - for Raceway or Cable. Not more than 3 aluminum conductors on an ambient temperature of 30°C.
    * Inductive Reactance is based on non-ferrous conduit with one diameter spacing center-to-center.

    Table 3 - Stock Code Colors

    Size (strand)BlackRedBlueWhiteBrownOrangeYellowGrayGreenPurplePinkTan
    8 (7)455950138627
    6 (7)112706643836643837591212591209591210591211585321
    4 (7)112714591114591115591116591201591202591203598051585320
    2 (6)112722643620643621592621591213591214591215598052585319
    1 (8)112730591204591205591206591207591208591216596497585318
    1/0 (10)112748591284591285591286585291585292585293585294585290596423
    2/0 (12)112755591288591289591290585296585297585298585300585295596422
    3/0 (16)112763585302585303585304585305585306585308585309585301
    4/0 (19)576531585317585316585314585313585312585311585310567439
    250 (22)278341576390576391576392576385576386576387576388567440592468
    300 (21)278358576382576383576384576133576134576135576136576361593380
    350 (35)278366576378576379576380576374576375576376576377567437592562669682669683
    400 (35)278374576370576372576373576127576129576130576131567384593379455994455995
    500 (34)278382576367576368576369576362576364576365576366576394589196669675669681
    600 (37)278390576350576351576352576345576346576347576349567375589197
    700 (58)278408591293591294591295576341576342576343576344591296
    750 (61)278416592233592234592235567432567433567434567435567436592469
    900 (56)554059671912671915671918560445560446560447560448
    1000 (58)278424138626138625672168662187662321662186662541653124

    Revision: 1.000.090

    Updated On: Nov. 13, 2024, 10:02 p.m. UTC