SPEC 22060

SIMpull® T90 Copper

SIMpull® THHN THWN-2 MTW / c(UL) T90 Nylon TWN75 Copper Conductor, 600V, Thermoplastic-Insulated Cable, All Sizes Rated TWN75

...

Construction:

  1. Conductor:Solid per ASTM B3 or Combination unilay-stranded copper conductors per ASTM B787.
  2. Insulation:All phases are insulated with Polyvinyl Chloride with Nylon Sheath
  3. Jacket:Polyvinyl Chloride PVC jacket utilizing SIMpull® Technology.

Applications and Features:

SIMpull® THHN, THWN-2, MTW - (UL)- Suitable for dry locations not exceeding 90°C. For Gasoline and Oil Resistant II applications not to exceed 75°C. MTW (UL) - suitable for dry locations not exceeding 90°C. For wet locations, Gasoline and Oil Resistant II applications not to exceed 60°C. T90 Nylon c(UL) - cables are primarily intended for installation in conduit (raceways) as exposed wiring in dry locations not exceeding 90°C. TWN75 c(UL) - suitable for wet or dry locations at not more than 75°C. The maximum voltage rating for all intended applications is 600 volts. Minimum installation handling temperature is limited to -25°C. Minimum operating temperature limited to -40°C. Non-SIMpull Silicone Free size 14, 12, 10.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA Certified LL90458
  • ASTM B787 19 Wire Combination Unilay-Stranded Copper Conductors
  • Canadian Electrical Code
  • CSA FT-1 Flame Test
  • Sample Print Legend:

    SOUTHWIRE SIMpull{TM} E51583 {UL} (XX AWG) XX.X{mm2} CU TYPE MTW OR THWN-2 OR THHN OR GASOLINE AND OIL RESISTANT II OR AWM 600 VOLTS VW-1 --- {CSA} T90 NYLON OR TWN75 600 VOLTS FT1 {NOM}-ANCE 90°C - (X AWG) ---RoHS PAT www.patentSW.com
    Table 1 – Weights and Measurements
    Cond. SizeCond. NumberStrand CountDiameter Over ConductorInsul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilNo. of Strandsinchmilmilinchlb/1000ftlb/1000ft
    61190.1773060.2538195
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Table 2 – Electrical and Engineering Data
    Cond. SizeCond. NumberMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity At 75°CAllowable Ampacity At 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    611.0002090.4110.4950.0516575
    * Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    * Ampacities have been adjusted for more than Three Current-Carrying Conductors.
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * Non-SIMpull Silicone Free sizes: 14, 12, 10.

    Table 3 - Stock Code Colors

    Size (Strand)ColorStock Number
    Size (Strand)ColorStock Number
    14 (Solid)BK507665
    14 (Solid)RD507699
    14 (Solid)WE507673
    14 (Solid)YW507723
    14 (Solid)OE610483
    14 (Solid)BE507707
    14 (Solid)BN553096
    14 (Solid)GN507681
    14 (19)BK472001
    14 (19)YW672659
    14 (19)WE472019
    14 (19)RD472027
    14 (19)OE687517
    14 (19)BE472043
    14 (19)GN472035
    14 (19)BN507715
    12 (Solid)BK495770
    12 (Solid)OE507632
    12 (Solid)BE495812
    12 (Solid)GN495804
    12 (Solid)BN507640
    12 (Solid)WE495788
    12 (Solid)RD495796
    12 (Solid)YW507657
    12 (19)BK472050
    12 (19)WE472068
    12 (19)YW672675
    12 (19)BE472092
    12 (19)RD472076
    12 (19)GN472084
    12 (19)OE552660
    12 (19)BN672667
    10 (Solid)RD484626
    10 (Solid)BE507756
    10 (Solid)BK507731
    10 (Solid)GN672683
    10 (Solid)WE507749
    10 (19)BK472100
    10 (19)YW552663
    10 (19)OE610486
    10 (19)GN472134
    10 (19)WE472118
    10 (19)BN552662
    10 (19)RD472126
    10 (19)BE472142
    8 (19)BK472159
    8 (19)RD611462
    8 (19)RD472175
    8 (19)WE472167
    8 (19)BE472191
    8 (19)GN472183
    6 (19)BK472209
    6 (19)WE472217
    6 (19)RD472225
    6 (19)BE472241
    6 (19)GN472233
    4 (19)BK472258
    4 (19)GN472282
    3 (19)WE484667
    3 (19)GN684068
    3 (19)BK484675
    2 (19)BK672386
    2 (19)GN684076
    2 (19)WE672394
    1 (19)BK684084
    1/0 (19)BK471979
    2/0 (19)GN688051
    2/0 (19)BK672402
    3/0 (19)WE471987
    3/0 (19)BK471995
    4/0 (19)WE677820

    Revision: 1.000.016