SPEC 48007

TCU 600V LSZH XHHW-2 SOLONONplus™ FT4, VW-1

SOLONONplus™ 600 Volt Single Conductor Tinned Copper Cross Linked Polyolefin Low Smoke Zero Halogen (XLPO LSZH) Insulation Type XHHW-2

...

Construction:

  1. Conductor:Class B compressed stranded tinned copper per ASTM B3 and B33
  2. Insulation:SOLONONplus™ Cross Linked Polyolefin Low Smoke Zero Halogen (XLPO LSZH) Type XHHW-2

Applications and Features:

APPLICATION
Southwire’s 600 Volt SOLONONplus™ Type XHHW-2 cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, and aerially when supported by a messenger. These cables are ideal for use in establishments where low smoke and low acid emissions are desired for public safety and health and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions.

FEATURES
  1. NEC compliant
  2. The halogen content is less than 0.2% and Acid gas less than 2.0%
  3. UL listed VW-1
  4. UL listed FT4/IEEE 1202 and ST-1
  5. UL listed for CT use on 1/0 AWG and larger
  6. -40°C Cold impact and cold bend
  7. Oil Resistant I and II
  8. Gasoline Resistance I and II
  9. Sunlight Resistant

Specifications:

  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • ASTM B170 Oxygen Free Electrolytic Copper (available upon request)
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test (1/0 and Larger)
  • UL 2885 Acid Gas, Acidity and conductivity of combusted materials and assessment of halogens
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • ICEA T-33-655/MIL-C-24643 Low Smoke Halogen Free (LSHF) Polymeric Jackets
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • RoHS-2 (European Directive 2011/65/EU)
  • ISO 9001 Quality management
  • NFPA 130 Standard for Fixed Guideway Transit and Passenger Rail Systems
  • NFPA 502 Standard for Road Tunnels, Bridges, and Other Limited Access Highways (non-emergency circuits only)
  • Sample Print Legend:

    14 AWG thru 1 AWG
    SOUTHWIRE SOLONONplus{TM} LSZH XLPO E30117 (UL) XX AWG TCU TYPE XHHW-2-HF VW-1 600V PRI PRII GRI GRII -40°C SR FT4 ST-1

    1/0 AWG and Larger
    {SQFTG} SOUTHWIRE SOLONONplus{TM} LSZH XLPO E30117 {UL} XX AWG/KCMIL TCU TYPE XHHW-2-HF VW-1 600V PRI PRII GRI GRII -40°C SR FT4 ST-1 CT
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrand ClassStrand CountCond. CmilDiameter Over ConductorInsul. ThicknessJacket ColorApprox. ODApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°CMax Pull Tension
    AWG/kcmilNo. of Strandscmilinchmilinchlb/1000ftΩ/1000ftΩ/1000ftlb
    TBA14B741100.07030BK0.133202.6313.17033
    45967812B765300.08730BK0.153291.6622.00252
    45967710B7103800.11330BK0.177431.0401.25383
    TBA8B7165100.14245BK0.236720.6530.786132
    TBA6B7262400.17845BK0.2721060.4110.495210
    4596824B7417400.22545BK0.3191590.2580.310334
    4596813B7526200.25245BK0.3461960.2050.246421
    4596792B7663600.27745BK0.3772420.1620.154531
    4596751B19836900.32255BK0.4383110.1280.154670
    4596761/0B191056000.36255BK0.4783850.1020.122845
    TBA2/0B191331000.40655BK0.5224760.0810.0971065
    TBA3/0B191678000.45655BK0.5725910.0640.0791342
    4596834/0B192116000.49855BK0.6287340.0510.0621693
    459680250B372500000.54265BK0.6948730.0430.0532000
    TBA300B373000000.59465BK0.73010340.0360.0452400
    TBA350B373500000.64165BK0.77711970.0310.0382800
    459684400B374000000.68565BK0.84213620.0270.0333200
    TBA500B375000000.76665BK0.90216810.0220.0324000
    TBA600B616000000.84080BK1.00820380.0180.0254800
    TBA750B617500000.96880BK1.13625270.0140.0216000
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

    Revision: 1.000.002

    Updated On: April 6, 2026, 3:12 p.m. UTC