SPEC 48005

TCU 600V LSZH RHH/RHW-2/RW90 SOLONONplus™

SOLONONplus™ 600 Volt Single Conductor Tinned Copper Cross Linked Polyolefin Low Smoke Zero Halogen (XLPO LSZH) Insulation Type RHH/RHW-2/RW90

...

Construction:

  1. Conductor:Class B compressed stranded tinned copper per ASTM B3 and B33
  2. Insulation:Black SOLONONplus™ Cross Linked Polyolefin Low Smoke Zero Halogen (XLPO LSZH) Type RHH/RHW-2/RW90

Applications and Features:

Southwire’s 600 Volt SOLONONplus™ Type RHH/RHW-2/RW90 cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, and as otherwise permitted by the NEC® for Type RHH/RHW-2 or the CE Code for Type RW90. These cables are ideal for use in establishments where low smoke and low acid emissions are desired for public safety and health and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions.

  1. NEC compliant
  2. The halogen content is less than 0.2% and Acid gas less than 2.0%
  3. 70,000 BTU/Hr. Vertical Flame Test
  4. UL listed for CT use on 1/0 AWG and larger
  5. UL listed FT4 and ST-1 (limited smoke)
  6. -40°C Cold impact and cold bend
  7. Gasoline and Oil Resistant GRI and GRII
  8. UV/Sunlight resistant

Specifications:

  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • ASTM B170 Oxygen Free Electrolytic Copper (available upon request)
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test (1/0 and Larger)
  • UL 2885 Acid Gas, Acidity and conductivity of combusted materials and assessment of halogens
  • CSA C22.2 No. 38 Thermoset-insulated wires and cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • ICEA T-33-655/MIL-C-24643 Low Smoke Halogen Free (LSHF) Polymeric Jackets
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • RoHS-2 (European Directive 2011/65/EU)
  • ISO 9001 Quality management
  • ISO 14001 Environmental management systems standard
  • NFPA 130 Standard for Fixed Guideway Transit and Passenger Rail Systems
  • NFPA 502 Standard for Road Tunnels, Bridges, and Other Limited Access Highways (non-emergency circuits only)
  • Sample Print Legend:

    {SQFTG} SOUTHWIRE SOLONONplus{TM} E30117 (UL) XX AWG (X.XXmm2) TCU LSZH XLPO TYPE RHH OR RHW-2 -40°C FT4 ST1 SR PRI PRII GRI GRII 600V --- (CSA) LL90458 TYPE RW90 600V -40°C FT4 ST1 TC-ER SR PRI PRII GRI GRII
    Table 1 – Weights and Measurements
    Cond. SizeStrand ClassStrand CountCond. CmilDiameter Over ConductorInsul. ThicknessJacket ColorApprox. ODApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°CMax Pull Tension
    AWG/kcmilNo. of Strandscmilinchmilinchlb/1000ftΩ/1000ftΩ/1000ftlb
    14B741100.07045BK0.165242.6313.17032
    12B765300.08845BK0.183331.6622.00252
    10B7103800.11345BK0.207471.0401.25383
    8B7165100.14160BK0.268770.6530.786132
    6B7262400.17760BK0.3041120.4110.495209
    4B7417400.22560BK0.3511670.2580.310333
    3B7526200.25260BK0.3782040.2050.246420
    2B7663600.28260BK0.4092510.1620.195530
    1B19836900.32280BK0.4903290.1280.154669
    1/0B191056000.36180BK0.5304040.1020.122844
    2/0B191331000.40580BK0.5744970.0810.0971064
    3/0B191678000.45680BK0.6246140.0640.0781342
    4/0B192116000.51280BK0.6807590.0510.0621692
    250B372500000.55895BK0.7589090.0430.0532000
    350B373500000.66195BK0.84112360.0310.0392800
    500B375000000.78995BK0.98917310.0220.0294000
    600B616000000.865110BK1.07220840.0180.0254800
    750B617500000.968110BK1.20025790.0140.0226000
    1000B6110000001.117110BK1.34933880.0110.0188000
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

    Revision: 1.000.002

    Updated On: April 3, 2026, 2:26 p.m. UTC