SPEC 60366

Armorlite® Type MC THHN/THWN Aluminum Conductor Feeder Cable with Green Insulated Ground 277/480V Colors

Aluminum THHN/THWN-2 Insulated Singles with 8000 series Triple E™ Aluminum Alloy. Green Insulated AlumaFlex™ Aluminum Alloy Grounding Conductor. UL Listed. 600 Volts. Rated VW-1. Lightweight Aluminum Interlocked Armor.

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B801or ASTM B836
  2. Insulation:All phases are insulated with Polyvinyl Chloride with Nylon Sheath Type THHN/THWN
  3. Ground:Green Insulated aluminum ground
  4. Filler:Fillers as needed
  5. Binder:Mylar tape
  6. Armor:Aluminum Interlocked Armor

Applications and Features:

Southwire Armorlite® Type MC Feeder cable is suitable for use as follows:
- Feeder and service power distribution in commercial, industrial, institutional, and multi-residential buildings.
- Fished or embedded in plaster.
- Concealed or exposed installations.
- Suitable for power and lighting circuits.
- Places of Assembly per NEC 518.4 and theaters per NEC 520.5.
- Environmental air-handling spaces per NEC 300.22 (C).
- Installation in cable tray and approved raceways, or as aerial cable on a messenger.
- Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) & 645.5(E)
- Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations.
- Type THHN/THWN rated 90ºC Dry
- Anti-short bushings are not required for use with MC cable per NEC and UL

Southwire Armorlite® Type MC Feeder Cable - meets or exceeds the following requirements:
- UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
- Federal Specification A-A59544 (formerly J-C-30B)
- NFPA 70 (National Electrical Code), Article 330
- Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems

Color Code - 3/C: Brown, Orange, Yellow
- 4/C: Brown, Orange, Yellow, Gray

Specifications:

  • ASTM B800 8000 Series Aluminum Alloy Wire
  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 1569 Metal-Clad Cables
  • UL 1479 Standard for Safety Fire Tests of Penetration Firestops
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • RoHS Compliant Lead-Free, Silicone-Free
  • Buy American: Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j); specify “Made in the USA Only!” when ordering to ensure your project receives American made products.
  • Sample Print Legend:

    E96627 {UL} TYPE MC AWG XX THHN OR THWN CDRS FOR USE IN CABLE TRAYS 600 VOLTS
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeConductor NumberColorDiameter Over ConductorConductor StrandingInsulation ThicknessGround SizeDiameter Over ArmorOverall Weight
    AWG/KcmilinchmilsNo. x AWGinchlbs/1000ft
    6717151/03BN,OE,YW,GN0.33619601x41.250645
    6433404/03BN,OE,YW,GN0.47419601x21.6301130
    6407312503BN,OE,YW,GN0.52022701x11.7401340
    6722164003BN,OE,YW,GN0.65935701x3/02.1901988
    6418325003BN,OE,YW,GN0.73535701x12.2102225
    5862275003BN,OE,YW,GN0.73535701x2/02.2082299
    6757375003BN,OE,YW,GN0.73534701x3502.5682596
    6683995003BN,OE,YW,GN0.73534701x3/02.2532316
    5864886003BN,OE,YW,GN0.81241801x4002.5263124
    6748436003BN,OE,YW GN0.81241801x3/02.4482753
    5864896003BN,OE,YW,GN0.81241801x3502.5383046
    6748931/04BN,OE,YW,GY,GN0.33619601x41.370795
    5936022504BN,OE,YW,GY,GN0.52022701x11.9901755
    1390152504BN,OE,YW,GY,GN0.52022701x21.9161713
    6746473504BN,OE,YW,GY,GN0.61635701x22.1632180
    4578235004BN,OE,YW,GY,GN0.73535701x2502.5602541
    5901005004BN,OE,YW,GY,GN0.73534701x2/02.5522984
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeConductor NumberMin. Bend RadiusMax Pull TensionDC Resistance at 25°CAC Resistance at 75°CInductive Reactance @ 60HzAllowable Ampacity Raceway 75°CAllowable Ampacity Raceway 90°C
    AWG/KcmilInchesLbsΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    1/038.819000.1680.2010.044120135
    4/038.819000.0840.1000.041180205
    250312.245000.0710.0860.041205230
    400315.372000.0440.0540.040270305
    500315.590000.0350.0440.039310350
    500315.590000.0350.0440.039310350
    500318.090000.0350.0440.039310350
    500315.890000.0350.0440.039310350
    600317.7108000.0290.0370.039340385
    600317.1108000.0290.0370.039340385
    600317.8108000.0290.0370.039340385
    1/049.620270.1680.2010.04496108
    250413.948000.0710.0860.041164184
    250413.448000.0710.0970.027164184
    350415.167200.0510.0690.026200224
    500417.996000.0350.0440.039248280
    500417.896000.0350.0440.039248280
    * Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
    * Ampacities have been adjusted for more than Three Current-Carrying Conductors.