SPEC 60140

Duraclad® Type MC 277/480V Colors

14 AWG through 10 AWG Copper THHN/THWN Insulated Singles. Green Copper THHN Insulated Grounding Conductor. UL Listed. 600 Volts. Rated VW-1. Lightweight Steel Interlocked Armor. Also available in Blue Steel Armor.

...

Construction:

  1. Conductor:Solid copper per ASTM B3 or 19-strand class C compressed copper and ASTM B3 and B8
  2. Insulation:Polyvinyl Chloride with Nylon Sheath Type THHN/THWN
  3. Ground:Green Polyvinyl Chloride with Nylon Sheath Type THHN/THWN insulated ground conductor
  4. Binder:Mylar tape with print legend wrapped around assembly
  5. Armor:Light weight galvanized steel interlocked armor

Applications and Features:

Southwire Duraclad® Type MC Cable is suitable for use as follows:
• Branch and service power distribution in commercial, industrial, institutional, and multi-residential buildings
• Fished or embedded in plaster
• Concealed or exposed installations
• Environmental air-handling spaces per NEC 300.22 (C)
• Places of Assembly per NEC 518.4 and theaters per NEC 520.5
• Installation in cable tray and approved raceways
• Under raised floors for information technology equipment conductors and cables per NEC Article 645
• Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations
• Binder tape with print legend wrapped around assembly
• Type THHN/THWN rated 90ºC dry
• Unjacketed Type MC cables are rated for dry, indoor locations only per NEC 330.10(A)(10)
• Anti-Short bushing not required

Southwire Duraclad® Type MC Cable meets or exceeds the following requirements:
• UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
• Federal Specification A-A59544 (formerly J-C-30B)
• NFPA 70 (National Electrical Code), Article 330
• Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 1569 Metal-Clad Cables
  • UL 1479 Standard for Safety Fire Tests of Penetration Firestops
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • RoHS-2 (European Directive 2011/65/EU)
  • Buy American: Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j); specify “Made in the USA Only!” when ordering to ensure your project receives American made products.
  • VW-1 (Vertical-Wire) Flame Test
  • Sample Print Legend:

    SOUTHWIRE E96627 {UL} TYPE MC XX AWG THHN OR THWN CDRS FOR USE IN CABLE TRAYS 600 VOLTS
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeConductor NumberColorDiameter Over ConductorConductor StrandingInsulation ThicknessGround SizeDiameter Over ArmorCopper WeightOverall Weight
    AWG/KcmilinchmilsNo. x AWGinchlbs/1000ftlbs/1000ft
    12 AWG | SOLID Strands
    553242122OE,GY,GN0.081SOLID151x120.48460154
    551774122BN,GY,GN0.081SOLID151x120.48460154
    553243122YW,GY,GN0.081SOLID151x120.48460154
    553111122BN,GY,GN0.081SOLID151x120.48460154
    556205122PE,GY,GN0.081SOLID151x120.48460154
    553251123BN,YW,GY,GN0.081SOLID151x120.51580184
    553272123PE,BN,GY,GN0.081SOLID151x120.51580184
    553241123GY,BN,OE,GN0.081SOLID151x120.51580184
    678479124OE,YW,GY/OE,GY/YW,GN0.081SOLID151x120.55100278
    678480124BN,YW,GY/BN,GY/YW,GN0.081SOLID151x120.55100278
    553244124BN,OE,YW,GY,GN0.081SOLID151x120.55100213
    678478124BN,OE,GY/BN,GY/OE,GN0.081SOLID151x120.55100278
    12 AWG | 19 Strands
    586374122YW,GY,GN0.08919151x120.50560161
    586372122OE,GY,GN0.08919151x120.50560161
    559749122BN,GY,GN0.08919151x120.50560161
    10 AWG | SOLID Strands
    551782102YW,GY,GN0.102SOLID201x100.55193270
    553250102BN,GY,GN0.102SOLID201x100.55193270
    551783102OE,GY,GN0.102SOLID201x100.55193270
    551787103BN,YW,GY,GN0.102SOLID201x100.59124251
    553252103BN,OE,GY,GN0.102SOLID201x100.59124252
    587525104BN,YW,GY/BN,GY/YW,GN0.102SOLID201x100.634155374
    553245104BN,OE,YW,GY,GN0.102SOLID201x100.634155297
    649653106BN,OE,YW,GY/BN,GY/OE,GY/YW,GN0.102SOLID201x100.68217382
    64458713BN,OE,YW,GN0.32219501x61.2578641400
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Note: Conductor number = number of phase conductors plus neutrals (if any). Does not include green ground.
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeConductor NumberMin. Bend RadiusDC Resistance at 25°CAC Resistance at 75°CInductive Reactance @ 60HzAllowable Ampacity Raceway 75°CAllowable Ampacity Raceway 90°C
    AWG/KcmilInchesΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    12 AWG | SOLID Strands
    1223.41.6622.0630.0542530
    1223.41.6622.0630.0542530
    1223.41.6622.0630.0542530
    1223.41.6622.0630.0542530
    1223.41.6622.0630.0542530
    1233.61.6622.0630.0542530
    1233.61.6622.0630.0542530
    1233.61.6622.0630.0542530
    1243.91.6622.0630.0542024
    1243.91.6622.0630.0542024
    1243.91.6622.0630.0542024
    1243.91.6622.0630.0542024
    12 AWG | 19 Strands
    1223.51.6622.0630.0542530
    1223.51.6622.0630.0542530
    1223.51.6622.0630.0542530
    10 AWG | SOLID Strands
    1023.91.041.2910.053540
    1023.91.041.2910.053540
    1023.91.041.2910.053540
    1034.11.041.2910.053540
    1034.11.041.2910.053540
    1044.41.041.2910.052832
    1044.41.041.2910.052832
    1064.81.041.2910.052832
    138.80.1280.1590.046130145
    * Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    * Ampacities have been adjusted for more than Three Current-Carrying Conductors.

    Revision: 1.000.008