SPEC 80213

35kV AL 100% TRXLPE One-Third (Based on Short Circuit) HI-DRI-PLUS® Renewable (Solar or Wind)

Moisture Blocked Aluminum Conductors. TRXLP Insulation. One-Third Concentric Neutrals. XLPE Jacket

...

Construction:

  1. Conductor:Moisture Blocked 1350 H16/H26 Aluminum, Class B Compressed or Compressed Unilay Stranded
  2. Strand Shield:Semi-conducting Crosslinked Polyethylene
  3. Insulation:Tree Retardant Crosslinked Polyethylene (TRXLP)
  4. Insulation Shield:Strippable Semi-conducting Crosslinked Polyethylene
  5. Concentric Neutral:Annealed Copper Wires Helically Applied One-Third Concentric Neutral
  6. Overall Jacket & Water Block:HI-DRI-PLUS® Water Swellable Powder Black Crosslinked Polyethylene (XLPE) with Red Extruded Stripes

Applications and Features:

  • Predominately used for renewable projects with wind or solar applications.
  • Suitable for use in wet or dry locations, direct burial, underground ducts, and exposure to direct sunlight.
  • To be used at conductor temperature not to exceed 105ºC normal operation.
  • UL listed MV-105
  • The concentric neutral counts and sizes listed in Table 1 are based on the ICEA P-45-482 short circuit calculation of an MV-90 design. The short circuit value in Table 1 is calculated using a higher thermal limit of a crosslinked XLPE jacket MV-105 design.

Specifications:

  • ASTM B231 Standard Specification for Concentric-Lay-Stranded Aluminum 1350 Conductors
  • ASTM B609 Standard Specification for Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes
  • UL 1072 Medium-Voltage Power Cables
  • ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5 - 46kV
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661
  • Sample Print Legend:

    {SQFTG} SOUTHWIRE(R) HI-DRI-PLUS(R) (UL) XXX KCMIL AL 345 MILS TRXLPE TYPE MV-105 35KV 100% INSUL LEVEL -- (NESC) -- SOUTHWIRE {MMM} {YYYY} NON-CONDUCTING JACKET
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralNeutral DC Resistance 25°CJacket ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull Tension
    AWG/KcmilinchinchmilinchNo. x AWGΩ/1000ftmilinchlb/1000ftinchlb
    6297751/0 (61)0.3511.0723451.1827x160.597501.38474211.1633
    6621114/0 (19)0.4981.2183451.32813x160.321501.529102612.41269
    6263084/0 (19)0.4981.2183451.3289x140.292501.556102612.41269
    662685350 (37)0.6611.3913451.50114x140.187751.783141014.32100
    662101500 (37)0.7891.5193451.62929x160.144751.884167715.03000
    629794500 (37)0.7891.5193451.62918x140.146751.911170515.33000
    459248500 (37)0.7891.5193451.62919x140.138751.911171615.33000
    626328500 (37)0.7891.5193451.62912x120.138751.944176415.63000
    626338750 (61)0.9681.7083451.84818x120.092752.163232617.34500
    6075941000 (61)1.1171.8573451.99723x120.072752.312279118.56000
    4566921000 (61)1.1171.8573451.99715x100.069752.354286918.86000
    6077631250 (91)1.2502.0013452.14118x100.057752.498334220.07500
    4564021250 (61)1.2502.0013452.14119x100.054752.4983370207500
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Pulling tension based on pulling eye directly connected to conductor
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzCharging CurrentDielectric LossZero Sequence ImpedancePositive Sequence ImpedanceShort Circuit Current @ 30 CycleAllowable Ampacity in Duct 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftA/1000ftW/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    1/0 (61)0.1670.2110.0690.05310.2911.80.265 + j1.0960.211 + j0.4092273160195
    4/0 (19)0.0840.1050.0550.0480.3612.20.160 + j0.9400.106 + j0.2724079235280
    4/0 (19)0.0840.1050.0550.0480.3612.20.159 + j0.7330.105 + j0.0494655235280
    350 (37)0.0500.0650.0460.0450.4382.70.119 + j0.7220.065 + j0.0457242315370
    500 (37)0.0350.0460.0400.0420.4963.00.101 + j0.8200.047 + j0.1659099380445
    500 (37)0.0350.0460.0400.0420.4963.00.100 + j0.7140.046 + j0.0439311380445
    500 (37)0.0350.0460.0410.0420.4963.00.101 + j0.8290.047 + j0.0169828380445
    500 (37)0.0350.0460.0400.0420.4963.00.100 + j0.7120.046 + j0.0439862380445
    750 (61)0.0240.0330.0340.0400.5803.50.087 + j0.7050.033 + j0.04114794470530
    1000 (61)0.0180.0260.0290.0390.6083.70.080 + j0.7000.026 + j0.03918903530585
    1000 (61)0.0180.0260.0290.03950.6273.80.080 + j0.7630.026 + j0.10819597530585
    1250 (91)0.0140.0230.0280.0380.7004.20.077 + j0.6920.023 + j0.03823516
    1250 (61)0.0140.0230.0300.0370.664.030.077 + j0.6930.023 + j0.03824823
    *Ampacities for Direct Buried are based on ICEA P-117-734-2016 Single-Conductor Solid Dielectric 15-35kV. Single Circuit Flat Direct Buried Figure 3
    *Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
    *Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft.
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralNeutral DC Resistance 25°CJacket ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull Tension
    AWG/KcmilmmmmmmmmNo. x AWGΩ/kmmmmmkg/kmmmnewton
    6297751/0 (61)8.9227.238.7630.027x161.961.2735.151104281.942817
    6621114/0 (19)12.6530.948.7633.7313x161.051.2738.841527314.965647
    6263084/0 (19)12.6530.948.7633.739x140.961.2739.521527314.965647
    662685350 (37)16.7935.338.7638.1314x140.611.9145.292098363.229345
    662101500 (37)20.0438.588.7641.3829x160.471.9147.852496381.0013350
    629794500 (37)20.0438.588.7641.3818x140.481.9148.542537388.6213350
    459248500 (37)20.0438.588.7641.3819x140.451.9148.542554388.6213350
    626328500 (37)20.0438.588.7641.3812x120.451.9149.382625396.2413350
    626338750 (61)24.5943.388.7646.9418x120.301.9154.943461439.4220025
    6075941000 (61)28.3747.178.7650.7223x120.241.9158.724153469.9026700
    4566921000 (61)28.3747.178.7650.7215x100.231.9159.794270477.5226700
    6077631250 (91)31.7550.838.7654.3818x100.191.9163.454973508.0033375
    4564021250 (61)31.7550.838.7654.3819x100.181.9163.455015508.0033375
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Pulling tension based on pulling eye directly connected to conductor
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzCharging CurrentDielectric LossZero Sequence Impedance*Positive Sequence Impedance*Short Circuit Current @ 30 CycleAllowable Ampacity in Duct 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilΩ/kmΩ/kmMΩ*kmΩ/kmA/kmW/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    1/0 (61)0.54790.690.02100.17420.9555.90550.265 + j1.0960.211 + j0.4092273160195
    4/0 (19)0.27560.340.01680.15751.1847.21780.160 + j0.9400.106 + j0.2724079235280
    4/0 (19)0.27560.340.01680.15751.1847.21780.159 + j0.7330.105 + j0.0494655235280
    350 (37)0.16400.210.01400.14761.4378.85830.119 + j0.7220.065 + j0.0457242315370
    500 (37)0.11480.150.01220.13781.6279.84250.101 + j0.8200.047 + j0.1659099380445
    500 (37)0.11480.150.01220.13781.6279.84250.100 + j0.7140.046 + j0.0439311380445
    500 (37)0.11480.150.01250.13781.6279.84250.101 + j0.8290.047 + j0.0169828380445
    500 (37)0.11480.150.01220.13781.6279.84250.100 + j0.7120.046 + j0.0439862380445
    750 (61)0.07870.110.01040.13121.90311.48290.087 + j0.7050.033 + j0.04114794470530
    1000 (61)0.05910.090.00880.12801.99512.13910.080 + j0.7000.026 + j0.03918903530585
    1000 (61)0.05910.090.00880.12962.05712.46720.080 + j0.7630.026 + j0.10819597530585
    1250 (91)0.04590.080.00850.12472.29713.77950.077 + j0.6920.023 + j0.03823516
    1250 (61)0.04590.080.00910.12142.16513.22180.077 + j0.6930.023 + j0.03824823
    *Ampacities for Direct Buried are based on ICEA P-117-734-2016 Single-Conductor Solid Dielectric 15-35kV. Single Circuit Flat Direct Buried Figure 3
    *Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
    *Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft.

    Revision: 1.000.021

    Updated On: Dec. 31, 2024, 11:08 p.m. UTC

    Concentric Neutral Calculator
    QR Code