SPEC 80150

Bare Copper Wire and Cable

Solid and Stranded

...

Construction:

Bare copper, solid or stranded.
Available in tempers hard, medium-hard, or soft.
Stranded conductors are concentrically stranded in hard and medium-hard tempers and are Combination Unilay stranded in the soft-drawn temper.

Applications and Features:

Solid and stranded (classes AA and A) bare copper are suitable for overhead transmission and distribution applications. Stranded conductor of greater flexibility (classes B and C) are suitable for uninsulated hook up, jumpers, and grounds in electrical construction. Soft Drawn copper is unilay construction.

Specifications:

  • ASTM B1 Hard-Drawn Copper
  • ASTM B2 Medium-Hard Drawn Copper Wire
  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • Stranded
    Stock NumberSizeStrandingStranding ClassWeightIndividual Wires DiameterComplete Conductor DiameterHard Drawn: Rated StrengthHard Drawn: DC Resistance @ 20ºCMedium-Hard Drawn: Rated StrengthMedium-Hard Drawn: DC Resistance @ 20ºCSoft-Drawn (Annealed): Rated StrengthSoft-Drawn (Annealed): DC Resistance @ 20ºCAllowable Ampacity+
    AWGlbs/1000’milsmilslbsohms/1000’lbsohms/1000’lbsohms/1000’
    87B51491467770.66636100.66294990.640895
    67B816118412280.41919590.41697940.403130
    47A, B128.97723219380.263615050.262213200.2534170
    37A B162.58726024330.20918850.207916700.201200
    27A, B204.99729230500.16623600.16521100.1578230
    17A258.410932838010.131629550.130925520.1252265
    1/07A, AA326.112336847520.104237050.103732210.1002310
    2/07A, AA410.913841459260.0826746400.0822440620.07949355
    2/019B410.98441866900.0826747650.0822440240.07949355
    3/07A, AA518.115546473660.0655658120.0652251180.06304410
    3/019B5201014547648*0.0726*5653*0.0723*4819*0.06431410
    4/07A, AA653.317452291540.0519972780.0517264590.04999480
    4/019B653.310652896170.0519974790.0517264530.04999480
    25019A771.9115574113600.04488360.0437876270.04231530
    25037B771.982575116000.04489520.0437879400.04231530
    30019A926.2126628135100.03667105300.0364891600.03526590
    30037B926.290630137140.0353106100.035393810.0353590
    35019A1080.6136679155900.03143122000.03127106800.03022650
    35037B1080.697681156200.0302122870.0302107730.0302650
    50037A, B1543.8116814225100.022175500.02189152400.02116810
    60037A, AA1852.5127891270200.01834210600.01825183000.01763910
    60061B1852.5103893270700.01834211130.01825183000.01763910
    75061A, B2315.6111998340900.01467265100.01459228900.01411040
    100061A, B3087.51281152450300.011351000.01094305000.010581240
    +Ampacity based on 75°C conductor temperature; 25°C ambient temperature; 2 ft./sec. wind in sun.
    * Interpolated value
    Solid
    SizeWeightDiameterCircular Mil AreaHard-Drawn: Rated Strength>Hard-Drawn: DC Resistance @ 20ºCMedium-Hard Drawn: Rated StrengthMedium-Hard Drawn: DC Resistance @ 20ºCSoft-Drawn (Annealed): Rated StrengthSoft-Drawn (Annealed): DC Resistance @ 20ºCAllowable Ampacity+
    AWGlbs/1000’milsmilslbsohms/1000’lbsohms/1000’lbsohms/1000’
    1412.464.14110213.52.626166.62.613124.22.525--
    1315.77251802682.083208.82.072156.62.003--
    1219.880.86530336.91.652261.21.643197.51.588--
    1124.990.78230422.91.31327.61.3032491.26--
    1031.4101.910380529.21.039410.41.0333140.999--
    939.6114.413090661.20.824514.20.82380.50.792--
    850128.5165108260.653643.90.65479.80.62895
    763144.32082010300.518806.60.5156050.498105
    679.41622624012800.41110100.409762.90.395125
    5100.2181.93309015910.32612650.324961.90.313145
    4126.3204.34174019700.25815840.25712130.249170
    3159.3229.45262024390.20519840.20415300.197195
    2200.9257.66636030030.16324500.16219290.156225
    1253.3289.38369036880.12930240.12824320.124260
    +Ampacity based on 75°C conductor temperature; 25°C ambient temperature; 2 ft./sec. wind in sun.

    Revision: 1.000.003

    Updated On: Jan. 26, 2026, 3:22 p.m. UTC