SPEC 85009

Multi-Conductor CU 600 V FR-XLPE Thermoset CPE-TS Jacket Control Cable Color Method 1 Table 2

Control Cable 600 Volt Copper Conductors, Flame Retardant Cross Linked Polyethylene (FR-XLPE) Insulation Thermoset Chlorinated Polyethylene (CPE-TS) Jacket, Control Cable Conductor Identification Method 1 Table 2. Silicone Free

...

Construction:

  1. Conductor:7 strands class B compressed bare copper per ASTM B3 and ASTM B8
  2. Insulation:Flame Retardant Cross Linked Polyethylene (FR-XLPE), 30 Mils thick for all cable sizes
  3. Filler:Polypropylene filler on cables with 5 or less conductors
  4. Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
  5. Rip Cord:Rip cord for ease of jacket removal
  6. Overall Jacket:Thermoset Chlorinated Polyethylene (CPE-TS) Jacket

Applications and Features:

Southwire’s 600 Volt control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. UL rated constructions can be used in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. UL rated constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 2
  • ICEA S-73-532 Control, Thermocouple Extension, and Instrumentation Cables (applicable to sizes 20-9 AWG conductors)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Vertical Tray Flame Test (70,000 Btu/hr) and ICEA T-29-520 - (210,000 Btu/hr)
  • VW-1 (Vertical-Wire) Flame Test
  • Sample Print Legend:

    UL Listed
    SOUTHWIRE E75755 {UL} XX AWG X/C TYPE TC XHHW-2 CDRS 90C CPE JKT FT4 VW-1 600V SUN RES {MM/DD/YYYY} {SEQUENTIAL FOOTAGE MARKS} SEQ FTG

    Non UL Listed
    SOUTHWIRE XX AWG X/C FR-XLPE CDRS 90C CPE JKT 600V SUN. RES. DIRECT BURIAL YEAR{SEQUENTIAL FOOTAGE MARKS} SEQ FEET

    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over Cond.Insul. ThicknessDiameter Over InsulationJacket ThicknessApprox. ODCopper WeightApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°CInductive RectanceMin Bending RadiusAllowable Ampacity 75°CAllowable Ampacity 90°CJacket Color
    AWGNo.strandsinchmilinchmilinchlb/1000ftlb/1000ftΩ/1000ftΩ/1000ftΩ/1000ftinchAmpAmp
    18 AWG
    62213518770.046250.096450.39235906.6698.2770.0361.6-10BK
    620620^182070.046250.096600.6371012406.6698.2770.0362.5-7BK
    14 AWG
    625934^14270.071300.131450.36626732.6313.2650.0581.52025BK
    625838^14370.071300.131450.38738912.6313.2650.0581.52025BK
    625833^14470.071300.131450.421511132.6313.2650.0581.71620BK
    60752714470.071300.131600.425511152.6313.2650.0581.71620BK
    625828^14570.071300.131600.459641332.6313.2650.0581.81620BK
    625824^14770.071300.131600.499901732.6313.2650.05821418BK
    625819^14970.071300.131600.6181152382.6313.2650.0582.51418BK
    60752814970.071300.131600.6221152402.6313.2650.0582.51418BK
    625815^141270.071300.131600.6921543032.6313.2650.0582.81012BK
    625781^141570.071300.131800.7661923692.6313.2650.0583.11012BK
    607529141570.071300.131800.7711923722.6313.2650.0583.11012BK
    625807^141970.071300.131800.7982434482.6313.2650.0583.21012BK
    607526142770.071300.131800.9773466562.6313.2650.0583.9911BK
    603776$148190.073300.133600.5681022122.6313.2650.0582.31418BK
    12 AWG
    60748412270.089300.149450.40541931.6622.0630.0541.62530BK
    61993312370.089300.149450.429611201.6622.0630.0541.72530BK
    60751312470.089300.149600.476811541.6622.0630.0541.92024BK
    60752112970.089300.149600.6871833261.6622.0630.0542.71821BK
    622186121270.089300.149800.7672444161.6622.0630.0543.11215BK
    607514^121570.089300.149800.8973055471.6622.0630.0543.61215BK
    TBA122570.089300.149801.065058011.6622.0630.0545.31114BK
    10 AWG
    60751810270.113300.173600.456651231.041.2910.051.83540BK
    TBA10370.113300.173450.47971541.041.2910.051.93540BK
    60751210470.113300.173600.5621292281.041.2910.052.22832BK
    TBA10970.113300.173600.7512914321.041.2910.0532428BK
    662067101270.113300.173800.93886241.041.2910.053.61820BK
    8 AWG
    6222188270.142450.232600.6021032160.6530.810.0522.45055BK
    6222198370.142450.232600.641542960.6530.810.0522.65055BK
    6075198470.142450.232800.7042063570.6530.810.0522.84044BK
    6 AWG
    6075166270.178450.268600.6791642950.4110.510.0512.76575BK
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    ^ UL listed part number
    % Silicone binder tape
    $ 19 strand combination unilay conductor per ASTM B787
    * Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements. Ampacities have been adjusted for stock numbers containing more than Three Current-Carrying Conductors.
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

    Revision: 1.000.002

    Updated On: Dec. 31, 2024, 11:09 p.m. UTC