SPEC 45352
CU 600/1000V XLPE Insulation ARMOR-X® PVC Jacket XHHW-2. CT Rated -Sunlight Resistant - For Direct Burial - Silicone Free
Type MC-HL Power Cable 600 or 1000 Volt Four Copper Conductor, Cross Linked Polyethylene (XLPE) Insulation Type XHHW-2, Continuous Corrugated Welded Armor - ARMOR-X®, Polyvinyl Chloride (PVC) Jacket with One Bare Copper Ground

Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and B8
- Insulation:Cross Linked Polyethylene (XLPE) Type XHHW-2
- Grounding Conductor:Class B compressed stranded bare copper per ASTM B3 and B8
- Filler:Polypropylene filler
- Binder:Polypropylene tape
- Armor:ARMOR-X® Continuous Corrugated Welded armor
- Overall Jacket:Polyvinyl Chloride (PVC)
Applications and Features:
Southwire’s 600 Volt Type MC-HL ARMOR-X® power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, 250°C for short circuit conditions, and -50°C for cold bend. For uses in Class I, II, and III, Division 1 and 2 hazardous locations per NEC Article 501, 502, and 503.
Specifications:
Sample Print Legend:
{SQFTG_DUAL} SOUTHWIRE ARMOR-X® {UL} TYPE MC-HL 4/C XXX AWG or KCMIL (XX.X{MM2}) CU XHHW-2 GW 1 X XX AWG 90°C JACKET -40°C SUN. RES. DIR. BUR. FOR CT USE 600V/1KV IEEE1202/FT4 -- {CSA} RA90-HL AG14 XLPE -40°C 600V FT4 SR 90°C -- CWCMC -- {NOM}-ANCE Tipo MC XHHW-2 CT FT4 -- USA
Table 1 – Weights and Measurements
| Stock Number | Cond. Size | Cond. Number | Strand Count | Diameter Over Conductor | Insul. Thickness | Diameter Over Insulation | Ground | Diameter Over Armor | Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Jacket Color |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. of Strands | inch | mil | inch | No. x AWG | inch | mil | inch | lb/1000ft | lb/1000ft | |||
| 890527 | 8 | 4 | 7 | 0.142 | 45 | 0.232 | 1 x 10 | 0.79 | 50 | 0.896 | 238 | 466 | BK |
| 890528 | 6 | 4 | 7 | 0.178 | 45 | 0.268 | 1 x 8 | 0.92 | 50 | 1.026 | 379 | 651 | BK |
| 890529 | 4 | 4 | 7 | 0.225 | 45 | 0.315 | 1 x 8 | 1.06 | 50 | 1.166 | 569 | 920 | BK |
| 890530 | 2 | 4 | 7 | 0.283 | 45 | 0.373 | 1 x 6 | 1.22 | 50 | 1.326 | 910 | 1297 | BK |
| 890531 | 1/0 | 4 | 19 | 0.362 | 55 | 0.472 | 1 x 6 | 1.47 | 50 | 1.576 | 1399 | 1965 | BK |
| 890532 | 2/0 | 4 | 19 | 0.405 | 55 | 0.515 | 1 x 4 | 1.54 | 60 | 1.666 | 1790 | 2438 | BK |
| 582265 | 3/0 | 4 | 19 | 0.456 | 55 | 0.566 | 1 x 4 | 1.76 | 60 | 1.886 | 2223 | 2958 | BK |
| 890533 | 4/0 | 4 | 19 | 0.512 | 55 | 0.622 | 1 x 4 | 1.845 | 60 | 1.971 | 2770 | 3544 | BK |
| 890534 | 250 | 4 | 37 | 0.558 | 65 | 0.688 | 1 x 4 | 2.04 | 60 | 2.166 | 3249 | 4223 | BK |
| 890535 | 350 | 4 | 37 | 0.661 | 65 | 0.791 | 1 x 3 | 2.2 | 60 | 2.326 | 4530 | 5589 | BK |
| 890536 | 500 | 4 | 37 | 0.789 | 65 | 0.919 | 1 x 2 | 2.67 | 75 | 2.828 | 6444 | 7758 | BK |
| 592727 | 600 | 4 | 61 | 0.866 | 80 | 1.026 | 1 x 2 | 2.88 | 75 | 3.038 | 7691 | 9194 | BK |
| 890537 | 750 | 4 | 61 | 0.968 | 80 | 1.128 | 1 x 1 | 3.22 | 85 | 3.398 | 9616 | 11891 | BK |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Stock Number | Cond. Size | Cond. Number | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 75°C | Inductive Reactance @ 60Hz | Allowable Ampacity At 75°C | Allowable Ampacity At 90°C |
|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | ||
| 890527 | 8 | 4 | 6.3 | 528 | 0.653 | 0.81 | 0.052 | 40 | 44 |
| 890528 | 6 | 4 | 7.2 | 839 | 0.411 | 0.51 | 0.051 | 52 | 60 |
| 890529 | 4 | 4 | 8.2 | 1335 | 0.258 | 0.32 | 0.048 | 68 | 76 |
| 890530 | 2 | 4 | 9.3 | 2123 | 0.162 | 0.201 | 0.045 | 92 | 104 |
| 890531 | 1/0 | 4 | 11 | 3379 | 0.102 | 0.127 | 0.044 | 120 | 136 |
| 890532 | 2/0 | 4 | 11.7 | 4259 | 0.082 | 0.102 | 0.043 | 140 | 156 |
| 582265 | 3/0 | 4 | 13.2 | 5369 | 0.064 | 0.079 | 0.042 | 160 | 180 |
| 890533 | 4/0 | 4 | 13.8 | 6771 | 0.051 | 0.063 | 0.041 | 184 | 208 |
| 890534 | 250 | 4 | 15.2 | 8000 | 0.043 | 0.053 | 0.041 | 204 | 232 |
| 890535 | 350 | 4 | 16.3 | 11200 | 0.031 | 0.039 | 0.04 | 248 | 280 |
| 890536 | 500 | 4 | 19.8 | 16000 | 0.021 | 0.027 | 0.039 | 304 | 344 |
| 592727 | 600 | 4 | 21.3 | 19200 | 0.018 | 0.024 | 0.039 | 336 | 380 |
| 890537 | 750 | 4 | 23.8 | 24000 | 0.014 | 0.019 | 0.038 | 380 | 428 |
* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.