SPEC 45042

Southwire® Machine Flex® CU 600/1000V THHN Insulation Shielded Gray TPE Jacket. Silicone-Free

Type TC-ER Shielded Machine Tray Control Cable 600/1000 Volt Copper Conductors, Polyvinyl Chloride (PVC) with nylon layer Insulation Thermoplastic Elastomer Jacket, 90°C Dry 75°C Wet -40°C Cold Impact Identification Method 4. Silicone-Free

...

Construction:

  1. Conductor:Class K, Flexible stranded bare annealed copper per ASTM B3, B172, and B174
  2. Insulation:Polyvinyl Chloride (PVC) with nylon layer THHN
  3. Ground:One Green Ground with Yellow Stripe THHN
  4. Drain Wire:Tinned copper sized one awg size smaller than phase conductor. Drain wire size is two gauge smaller than phase size
  5. Shielding:100% coverage Alum/Mylar/Alum Foil, overall 85% coverage tinned copper braid
  6. Jacket:Gray Thermoplastic Elastomer TPE: Other jacket colors available upon request

Applications and Features:

Southwire’s shielded Machine Flex® tray control cables 600/1000 Volt conform to NFPA 79 and are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 75°C in wet locations and 90°C in dry locations, 130°C for emergency overload, and 150°C for short circuit conditions. For uses in Class I, II, Division 2 hazardous locations per NEC® Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC® 336.10. Southwire’s shielded flexible machine tray cable is ideal for use in for use in CNC machines, grinding, cutting, metal forming, buffing, bottling equipment, conveyors, processing & packaging equipment, assembly lines, control panels, food and bever- age, oil sands, plant expansion, wind energy and data centers. Multiple approvals for multiple applications. Cable is rated for -40°C cold impact. Two conductor cables contain no green/yellow ground.

Specifications:

  • ASTM B172 Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors
  • ASTM B174 Standard Specification for Bunch-Stranded Copper
  • UL 13 Power-Limited Circuit Cables
  • UL 66 Fixture Wire
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 758 Standard for Appliance Wiring Material Style 2463 (80C, 600V)
  • UL 758 AWM Style 2587
  • UL 1063 Machine Tool Wiring (MTW)
  • UL 1277 TC-ER
  • UL 1690 Data Processing Cable (DP-1)
  • UL 2250 Instrumentation Tray Cable
  • UL 2277 Type WTTC
  • CSA C22.2 No. 210 Appliance wiring material products I/II A/B
  • CSA C22.2 No.230 Tray Cables - Rated TC
  • CSA C22.2 No. 239 Control and instrumentation cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Exceeds Ecolab PM-40-1 Material Resistance Test With 30-day Exposure, UL Verified V747862
  • CE/RoHS-2 – The CE Marking has been applied solely to express the conformance to the material restrictions identified in the RoHS-2 (2011/65/EU) Directive
  • NFPA 79 Electrical Standard for Industrial Machinery
  • Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661
  • Sample Print Legend:

    18 - 12 AWG:
    SOUTHWIRE® XX AWG (X.XX mm2) XX/C PVC/NYLON SHLD TYPE TC-ER E75755 (UL) 600V 90°C DRY 75°C WET SUN RES OIL RES I/II DIR BUR -40°C OR MTW FLEXING OR DP-1 OR WTTC 1000V OR PLTC OR ITC OR AWM 2587 -- LL90458 (CSA) CIC/TC FT4 OR AWM I/II A/B 105°C 1000V -40°C FT4 -- {NOM}-ANCE PLTC-- {CE} ROHS-2 -- MADE IN USA

    10 AWG and Larger:
    {SQFTG} SOUTHWIRE® XX AWG (X.XX{mm2}) X/C PVC/NYLON SHLD TYPE TC E75755 {UL} 600V 90{D}C DRY 75{D}C WET SUN RES OIL RES I/II DIR BUR -40{D}C OR MTW FLEXING OR DP-1 OR WTTC 1000V OR AWM 2587 -- LL90458 {CSA} CIC/TC FT4 OR AWM I/II A/B 105{D}C 1000V -40{D}C FT4 --{NOM}-ANCE 90{D}C PVC/NYLON PVC-TPE THHN/THWN FT4 600V -- {CE} ROHS-2 -- MADE IN USA
    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over Cond.Insul. ThicknessDiameter Over InsulationJacket ThicknessApprox. ODCopper WeightApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°CInductive RectanceMin Bending RadiusAllowable Ampacity 75°CAllowable Ampacity 90°CJacket Color
    AWGNo.strandsinchmilinchmilinchlb/1000ftlb/1000ftΩ/1000ftΩ/1000ftΩ/1000ftinchAmpAmp
    18 AWG
    677081182160.044150.074450.29325536.6598.2650.0361.2-14GY
    588460◊183160.044150.074450.3230636.6598.2650.0361.3-14GY
    588461◊184160.044150.074450.32637706.6598.2650.0361.3-11GY
    588462◊185160.044150.074450.3643826.6598.2650.0361.4-11GY
    588463◊187160.044150.074450.395551026.6598.2650.0361.6-10GY
    630837◊189160.044150.074500.442691306.6598.2650.0361.8-10GY
    588464◊1812160.044150.074500.478861566.6598.2650.0361.9-7GY
    598625◊1818160.044150.074600.5761202226.6598.2650.0362.3-7GY
    598626◊1825160.044150.074600.6581622906.6598.2650.0362.6-6GY
    16 AWG
    677082162260.059150.089450.32134664.1815.1890.0331.3-18GY
    588465◊163260.059150.089450.33144784.1815.1890.0331.3-18GY
    588466◊164260.059150.089450.3652914.1815.1890.0331.4-14GY
    588467◊165260.059150.089450.391621094.1815.1890.0331.6-14GY
    588468◊167260.059150.089500.427811354.1815.1890.0331.7-13GY
    630836◊169260.059150.089500.4911011714.1815.1890.0332-13GY
    588469◊1612260.059150.089600.5621292204.1815.1890.0332.2-9GY
    598627◊1618260.059150.089600.6461853034.1815.1890.0332.6-9GY
    598628◊1625260.059150.089600.7462473974.1815.1890.0333-8GY
    14 AWG
    677083142410.073150.103450.34949842.6213.2530.0581.42025GY
    588470◊143410.073150.103450.363631022.6213.2530.0581.52025GY
    588471◊144410.073150.103500.401771252.6213.2530.0581.61620GY
    588472145410.073150.103500.438921472.6213.2530.0581.81620GY
    588473◊147410.073150.103450.4661201782.6213.2530.0581.91418GY
    598629◊1412410.073150.103600.6231932982.6213.2530.0582.51012GY
    598630◊1418410.073150.103600.722784122.6213.2530.0582.91012GY
    598631◊1425410.073150.103800.8753845832.6213.2530.0583.5911GY
    12 AWG
    677084122650.094150.124450.387701121.6522.050.0541.52530GY
    677194◊123650.094150.124500.419921431.6522.050.0541.72530GY
    588474◊124650.094150.124500.4511141731.6522.050.0541.82024GY
    588476125650.094150.124500.4891392071.6522.050.05422024GY
    588477127650.094150.124600.5551822691.6522.050.0542.21821GY
    10 AWG
    6770851021050.117200.157450.4551031601.041.2910.051.83540GY
    677196◊1031050.117200.157600.5161412191.041.2910.052.13540GY
    588478◊1041050.117200.157600.5741782681.041.2910.052.32832GY
    5884791051050.117200.157600.6082133171.041.2910.052.42832GY
    5884801071050.117200.157600.6582803951.041.2910.052.62428GY
    8 AWG
    643354◊841680.153300.213650.7422934440.6660.8270.05234044GY
    6 AWG
    643356◊642590.198300.258800.8854636570.4190.520.0513.55260GY
    4 AWG
    643358◊444200.235400.315851.05768310090.2630.3260.0485.36876GY
    2 AWG
    643360◊246510.302400.382851.237106214050.1670.2070.0456.292104GY
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Cond. Number includes green/yellow ground conductor. Constructions with only 2/C do not have a green/yellow ground conductor.
    * Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    * Ampacities have been adjusted for more than Three Current-Carrying Conductors.
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.