SPEC 87006

EPEC 40 (Schedule 40) With 1250 lb Mule Tape

...

Construction:

• High-Density Polyethylene (HDPE)
• 1250 lb Mule Tape

Applications and Features:

Designed to house and protect wire and cable products in various underground applications for commercial constructions, EV infrastructure expansions, Utility grid-hardening efforts, airports, mass transit, renewables, petrochemical, agriculture, and data centers. May be installed directly buried or encased in concrete as permitted by The National Electrical Code® Article 353. For above ground applications, HDPE conduit must be encased in a minimum of 2 inches of concrete.

Specifications:

  • ASTM D3350 Standard Specification for Polyethylene Plastics Pipe and Fittings Materials
  • ASTM F2160 Standard Specification for Solid Wall High Density Polyethylene (HDPE) Conduit Based on Controlled Outside Diameter (OD)
  • UL 651A High Density Polyethylene (HPDE) Conduit
  • CSA CSA marking is available upon request
  • Buy American: Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j); specify “Made in the USA Only!” when ordering to ensure your project receives American made products.
  • NEMA TC-7 Smooth-Wall Coilable Electrical Polyethylene Conduit
  • Sample Print Legend:

    {SQFTG} FEET (LOGO) SOUTHWIRE CONDUIT (UL) HDPE X" SCH40 NEMA TC 7 / ASTM F2160 {MMM/DD/YYYY} {MACH/SHFT/OP}
    Table 1 – Physical and Electrical Data
    Stock NumberDescriptionDuct Nominal SizeDuct Nominal Outside Dia.Duct Min. Wall ThicknessDuct Nominal Inside Dia.Duct Min. Bending RadiusDuct Max. Pull TensionDuct ColorApprox. Cable and Duct Weight
    inchinchinchinchinchlblb/1000ft
    632029EPEC 40 (SCHEDULE 40) WITH 1250 LB MULE TAPE0.751.050.1130.80412710BK149
    632998EPEC 40 (SCHEDULE 40) WITH 1250 LB MULE TAPE0.751.050.1130.80412710GY149
    633568EPEC 40 (SCHEDULE 40) WITH 1250 LB MULE TAPE11.3150.1331.029141050BK/3-OE STRIPES219
    632007EPEC 40 (SCHEDULE 40) WITH 1250 LB MULE TAPE11.3150.1331.029141050BK/3-BE STRIPES219
    631244EPEC 40 (SCHEDULE 40) WITH 1250 LB MULE TAPE11.3150.1331.029141050BK219
    632321EPEC 40 (SCHEDULE 40) WITH 1250 LB MULE TAPE11.3150.1331.029141050GY219
    633273EPEC 40 (SCHEDULE 40) WITH 1250 LB MULE TAPE1.251.660.141.36181420GY297
    632344EPEC 40 (SCHEDULE 40) WITH 1250 LB MULE TAPE1.251.660.141.36181420BK297
    632345EPEC 40 (SCHEDULE 40) WITH 1250 LB MULE TAPE1.51.90.1451.59211700BK/3-RD STRIPES354
    631013EPEC 40 (SCHEDULE 40) WITH 1250 LB MULE TAPE1.51.90.1451.59211700BK354
    633531EPEC 40 (SCHEDULE 40) WITH 1250 LB MULE TAPE22.3750.1542.047262280BK/3-OE STRIPES475
    632112EPEC 40 (SCHEDULE 40) WITH 1250 LB MULE TAPE22.3750.1542.047262280OE475
    631245EPEC 40 (SCHEDULE 40) WITH 1250 LB MULE TAPE22.3750.1542.047262280BK475
    633612EPEC 40 (SCHEDULE 40) WITH 1250 LB MULE TAPE2.52.8750.2032.445323615GY749
    633070EPEC 40 (SCHEDULE 40) WITH 1250 LB MULE TAPE2.52.8750.2032.44532365RD749
    632173EPEC 40 (SCHEDULE 40) WITH 1250 LB MULE TAPE33.50.2163.042394740BK/3-RD STRIPES981
    TBAEPEC 40 (SCHEDULE 40) WITH 1250 LB MULE TAPE44.50.2373.998506745OPTIONAL1396
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

    Cell Classification for HDPE Conduit

    PropertyTest MethodValue
    DensityD48830.953 g/cc
    Melt IndexD12380.25 g/10 min
    Flexural ModulusD790168,000 psi
    Tensile StrengthD6383900 yield @ 2 in/min
    SP-NCLS ESCRF2136>1000 hrs
    Hydrostatic Design BasisD2837N/A

  • (PE436580C-BK), (PE436580E-Colors)
  • Revision: 1.000.012

    Updated On: Dec. 31, 2024, 11:09 p.m. UTC