SPEC 87100

Tracer Wire

...

Construction:

  1. Conductor:Solid bare copper per ASTM B3
  2. Insulation:Linear Low Density Polyethylene (LLDPE)

Applications and Features:

  • Used on golf course sprinkler, gas lines, direct burial applications, also can be used for animal containment
  • 45 mil Linear Low Density Polyethylene LLDPE insulation thickness.
  • Rated for 60ºC
  • Rated for 600 volt
  • For direct burial
  • Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • UL 2989 Tracer Wire
  • Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over ConductorInsul. ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.No.inchmilinchlb/1000ft
    54491141SOLID0.064450.15719
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Table 2 – Electrical and Engineering Data
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CInductive ReactanceMin Bending RadiusAllowable Ampacity In Raceway At 75°CAllowable Ampacity In Raceway At 90°C
    AWG/KcmilΩ/1000ftΩ/1000ftΩ/1000ftinchAmpAmp
    142.6313.170.0581.22025

    Table 3 Stock Code for Application

    Insulation ColorApplication18 AWG16 AWG14 AWG12 AWG10 AWG8 AWG
    RedElectrical Power Line544890454490045449104
    OrangeFiber Optic / Telecom54490035449103
    YellowNatural Gas Pipeline54489025449002544910254492025449402
    BluePotable Water Pipeline5448906544910654492065449306
    5449706
    PurpleReclaimed Water, Irrigation, or Slurry Lines54490135449207
    GreenSewer Pipeline5448905544900554492055449305
    BlackPet Containment / Invisible Fence544900854491085449208
    WhitePet Containment / Other / Misc54490015449101
    BrownPet Containment / Other / Misc5449307

    Revision: 1.000.059

    Updated On: Nov. 4, 2026, 8 p.m. UTC