SPEC 80140
ACAR
Aluminum Conductor. Aluminum Alloy Reinforced. Bare.

Construction:
- Conductor:Aluminum 1350-H19 wires, concentrically stranded about an aluminum-alloy 6201-T81 core.
- Although the alloy strands generally comprise the core of the conductor, in some constructions they are distributed in layers throughout the aluminum 1350-H19 strands.
Applications and Features:
Used as bare overhead transmission cable and as primary and secondary distribution cable. A good strength-to-weight ratio makes ACAR applicable where both ampacity and strength are prime considerations in line design; for equal weight, ACAR offers higher strength and ampacity than ACSR.
Specifications:
Table 1 – Weights and Measurements
| Stock Number | Size | Stranding | Indiv. Wire 6201 Dia. | Indiv. Wire 1350 Dia. | Overall OD | Overall Weight |
|---|---|---|---|---|---|---|
| (AWG or kcmil) | EC/6201 | inch | inch | inch | lbs/1,000' | |
| 504027 | 355 | 12/7 | 0.1367 | 0.1367 | 0.683 | 332.1 |
| 465.9 | 12/7 | 0.1566 | 0.1566 | 0.783 | 435.8 | |
| 503.6 | 12/7 | 0.1628 | 0.1628 | 0.814 | 471.1 | |
| 653.1 | 12/7 | 0.1854 | 0.1854 | 0.927 | 611 | |
| 739.8 | 30/7 | 0.1414 | 0.1414 | 0.99 | 692.7 | |
| 739.8 | 18/19 | 0.1414 | 0.1414 | 0.99 | 691.6 | |
| 853.7 | 30/7 | 0.1519 | 0.1519 | 1.063 | 799.3 | |
| 853.7 | 18/19 | 0.1519 | 0.1519 | 1.063 | 798 | |
| 927.2 | 30/7 | 0.1583 | 0.1583 | 1.108 | 868.2 | |
| 927.2 | 18/19 | 0.1583 | 0.1583 | 1.108 | 866.7 | |
| 488551 | 1024.5 | 30/7 | 0.1664 | 0.1664 | 1.165 | 959.3 |
| 1024.5 | 18/19 | 0.1664 | 0.1664 | 1.165 | 957.7 | |
| 1081 | 30/7 | 0.1709 | 0.1709 | 1.196 | 1012.1 | |
| 1081 | 18/19 | 0.1709 | 0.1709 | 1.196 | 1010.5 | |
| 1109 | 30/7 | 0.1731 | 0.1731 | 1.212 | 1038.4 | |
| 1109 | 18/19 | 0.1731 | 0.1731 | 1.212 | 1036.6 | |
| 1172 | 30/7 | 0.178 | 0.178 | 1.246 | 1097.3 | |
| 1172 | 18/19 | 0.178 | 0.178 | 1.246 | 1095.5 | |
| 1197 | 30/7 | 0.1799 | 0.1799 | 1.259 | 1120.8 | |
| 1197 | 18/19 | 0.1799 | 0.1799 | 1.259 | 1118.9 | |
| 1280 | 30/7 | 0.186 | 0.186 | 1.302 | 1198.5 | |
| 1280 | 18/19 | 0.186 | 0.186 | 1.302 | 1196.5 | |
| 1361 | 42/19 | 0.1494 | 0.1494 | 1.344 | 1273.6 | |
| 1527 | 42/19 | 0.1582 | 0.1582 | 1.424 | 1428.8 | |
| 1703 | 42/19 | 0.1671 | 0.1671 | 1.504 | 1593.5 | |
| 1933 | 42/19 | 0.178 | 0.178 | 1.602 | 1808.8 | |
| 2267 | 42/19 | 0.1928 | 0.1928 | 1.735 | 2142 | |
| 2493 | 72/19 | 0.1655 | 0.1655 | 1.821 | 2356.9 | |
| 2493 | 54/37 | 0.1655 | 0.1655 | 1.821 | 2354.5 |
Table 2 - Electrical and Engineering Data
| Stock Number | Size | Rated Strength | DC Resistance @ 20C | AC Resistance @ 75C | Allowable Ampacity+ |
|---|---|---|---|---|---|
| (AWG or kcmil) | lbs | Ohms/1,000' | Ohms/1,000' | Amps | |
| 504027 | 355 | 8500 | 0.0514 | 0.0624 | 519 |
| 465.9 | 11000 | 0.0392 | 0.0477 | 616 | |
| 503.6 | 11900 | 0.0362 | 0.0441 | 646 | |
| 653.1 | 15400 | 0.0279 | 0.0342 | 760 | |
| 739.8 | 15300 | 0.024 | 0.0296 | 831 | |
| 739.8 | 18800 | 0.0252 | 0.0308 | 814 | |
| 853.7 | 17500 | 0.0208 | 0.0257 | 907 | |
| 853.7 | 21500 | 0.0218 | 0.0268 | 890 | |
| 927.2 | 19000 | 0.0192 | 0.0238 | 955 | |
| 927.2 | 23400 | 0.0201 | 0.0247 | 936 | |
| 488551 | 1024.5 | 20900 | 0.0173 | 0.0216 | 1015 |
| 1024.5 | 25800 | 0.0182 | 0.0225 | 995 | |
| 1081 | 22100 | 0.0164 | 0.0205 | 1048 | |
| 1081 | 27200 | 0.0172 | 0.0213 | 1028 | |
| 1109 | 22700 | 0.016 | 0.02 | 1065 | |
| 1109 | 27900 | 0.0168 | 0.0208 | 1044 | |
| 1172 | 24000 | 0.0152 | 0.019 | 1101 | |
| 1172 | 29500 | 0.0159 | 0.0198 | 1080 | |
| 1197 | 24500 | 0.0148 | 0.0187 | 1115 | |
| 1197 | 30200 | 0.0156 | 0.0194 | 1094 | |
| 1280 | 26200 | 0.0139 | 0.0175 | 1160 | |
| 1280 | 32200 | 0.0146 | 0.0182 | 1139 | |
| 1361 | 30300 | 0.0133 | 0.0168 | 1196 | |
| 1527 | 33600 | 0.0118 | 0.0151 | 1314 | |
| 1703 | 37500 | 0.0106 | 0.0137 | 1363 | |
| 1933 | 42500 | 0.00936 | 0.0123 | 1465 | |
| 2267 | 49900 | 0.00806 | 0.0108 | 1594 | |
| 2493 | 50400 | 0.00722 | 0.0099 | 1687 | |
| 2493 | 57600 | 0.00743 | 0.0101 | 1670 |
+ Conductor temperature of 75°C, ambient temperature 25°C, emissivity 0.5, wind 2 ft./sec., in sun.