SPEC 80103

ACSR/TW/AW

Aluminum Conductor, Aluminum-Clad Steel Reinforced, Trapezoidal Wire Construction

...

Construction:

  1. Core:Stranded aluminum-clad steel core, available in AW2 normal-strength and AW3 high-strength classes
  2. Stranding:Hard-drawn aluminum (1350-H19) trapezoidal-shaped wires with 61.2% conductivity

Applications and Features:

ACSR/TW/AW (Aluminum Conductor, Aluminum-Clad Steel Reinforced, Trapezoidal Wire) is a compact conductor consisting of trapezoidal-shaped hard-drawn aluminum wires surrounding an aluminum-clad steel core. The aluminum strands provide electrical conductivity, while the aluminum-clad steel core provides mechanical strength, additional conductivity, and corrosion protection.

The trapezoidal-wire design increases packing efficiency, allowing either more aluminum within a given conductor diameter or a reduced diameter for a given aluminum area. Area-equivalent designs can reduce wind and ice loading, while diameter-equivalent designs can increase aluminum area and electrical capacity.

ACSR/TW/AW is suited for overhead transmission and distribution applications requiring the strength and proven performance of ACSR, the compact geometry of trapezoidal-wire construction, and the corrosion resistance of an aluminum-clad steel core.

Continuous operating temperature - 75°C
Emergency operating temperature - 100°C

Specifications:

  • ASTM B230 Standard Specification for Aluminum 1350-H19 Wire for Electrical Purposes
  • ASTM B500 Standard Specification for Metallic Coated or Aluminum-Clad Stranded Steel Core for Use in Overhead Electrical Conductors
  • ASTM B502 Standard Specification for Aluminum-Clad Steel Core Wire for Use in Overhead Electrical Aluminum Conductors
  • ASTM B779 Standard Specification for Shaped Wire Compact Concentric-Lay-Stranded Aluminum Conductors, Steel-Reinforced (ACSR/TW)
  • Area Equal to Standard ACSR Conductor - Weights, Measurements, Electrical and Engineering Data
    Stock NumberCode WordConductor SizeType No.StrandingCross-Sectional AreaLayers of AlDiameterWeightRated Breaking StrengthDC Resistance @ 20°C
    AW StrandsAW CoreComplete Conductor
    AlTotalAlTotalAW2AW3
    kcmilAl/AWin²in²inininlb/1000ftlb/1000ftlblbΩ/mile
    TBAPartridge/TW/AW266.81614/70.20950.243620.07880.23640.595250.6348.410,70011,2000.3251
    TBAMerlin/TW/AW336.4614/10.26420.278920.13670.13670.630315.3357.38,4208,5600.2663
    TBALinnet/TW/AW336.41616/70.26420.307220.08840.26520.659316.1439.513,40014,0000.2578
    TBAOriole/TW/AW336.42316/70.26420.325920.10590.31770.692317.6494.616,50017,1000.2532
    TBAIbis/TW/AW397.51620/70.31220.363020.09610.28830.725373.5519.215,80016,3000.2181
    TBALark/TW/AW397.52316/70.31220.385020.11510.34530.740375.3584.119,40020,1000.2143
    TBAFlicker/TW/AW477.01318/70.37460.423220.09400.28200.776447.7587.116,70017,2000.1836
    TBAHawk/TW/AW477.01618/70.37460.435620.10530.31590.790448.1623.118,80019,4000.1818
    TBAHen/TW/AW477.02320/70.37460.462020.12610.37830.820450.3701.023,20023,6000.1786
    TBAParakeet/TW/AW556.51318/70.43710.493720.10150.30450.840522.4684.819,50020,0000.1573
    TBADove/TW/AW556.51620/70.43710.508320.11380.34140.850522.9727.121,90022,6000.1558
    TBAEagle/TW/AW556.52320/70.43710.539120.13620.40860.870525.5818.126,60027,6000.1531
    TBASquab/TW/AW605.01620/70.47520.552520.11860.35580.885568.5790.223,80024,6000.1433
    TBATeal/TW/AW605.02320/190.47520.583520.08520.42600.916571.3882.628,50030,0000.1410
    TBASwift/TW/AW636.0327/10.49950.513430.13290.13290.850598.4638.113,40013,5000.1427
    TBARook/TW/AW636.01320/70.49950.564220.10850.32550.893597.0782.622,30022,9000.1377
    TBAGrosbeak/TW/AW636.01620/70.49950.580820.12160.36480.909597.6830.825,00025,4000.1363
    TBAScoter/TW/AW636.02322/70.49950.616020.14560.43680.942600.5934.729,30030,4000.1339
    TBAEgret/TW/AW636.02322/190.49950.613520.08740.43700.942600.5928.229,90031,5000.1342
    TBAStarling/TW/AW715.51620/70.56200.653520.12900.38700.958672.3934.827,70028,6000.1212
    TBARedwing/TW/AW715.52320/190.56200.690020.09260.46300.994675.6104433,60034,8000.1193
    TBATern/TW/AW795.0720/70.62440.667620.08860.26580.960745.2869.121,50022,1000.1122
    TBAPuffin/TW/AW795.01018/70.62440.685720.10560.31680.980745.9921.724,20024,8000.1112
    TBACondor/TW/AW795.01320/70.62440.705320.12130.36390.993746.3978.427,80028,2000.1101
    TBADrake/TW/AW795.01620/70.62440.726120.13600.40801.010747.0103930,80031,8000.1091
    TBAMallard/TW/AW795.02322/190.62440.766820.09770.48851.050750.6116037,40038,7000.1073
    TBACanary/TW/AW900.01320/70.70690.798520.12910.38731.055844.9110830,70031,6000.0973
    TBAPhoenix/TW/AW954.0530/70.74930.787830.08370.25111.044897.7100823,20023,7000.0944
    TBARail/TW/AW954.0732/70.74930.801130.09710.29131.061898.6104725,40025,9000.0939
    TBACardinal/TW/AW954.01320/70.74930.846420.13290.39871.080895.5117432,60033,5000.0918
    TBACanvasback/TW/AW954.02324/190.74930.920120.10700.53501.149900.8139244,90046,5000.0894
    TBASnowbird/TW/AW1033.5530/70.81170.853530.08720.26161.089972.5109225,10025,7000.0871
    TBAOrtolan/TW/AW1033.5734/70.81170.867830.10100.30301.102973.4113427,50028,1000.0867
    TBACurlew/TW/AW1033.51322/70.81170.916920.13830.41491.131970.1127234,80036,3000.0847
    TBAAvocet/TW/AW1113.0530/70.87410.919030.09040.27121.1301047117627,10027,5000.0809
    TBABluejay/TW/AW1113.0734/70.87410.934630.10490.31471.1431048122229,70030,3000.0805
    TBAFinch/TW/AW1113.01338/190.87410.985030.08620.43101.1901051137037,60039,1000.0792
    TBAOxbird/TW/AW1192.5530/70.93660.984830.09360.28081.1701122126029,00029,5000.0755
    TBABunting/TW/AW1192.5734/70.93661.001330.10850.32551.1811123130931,80032,4000.0751
    TBAGrackle/TW/AW1192.51338/190.93661.055330.08920.44601.2251126146740,20041,9000.0739
    TBAScissortail/TW/AW1272.0530/70.99901.050430.09670.29011.2031197134430,90031,4000.0708
    TBABittern/TW/AW1272.0738/70.99901.068130.11210.33631.2241198139633,90034,6000.0705
    TBAPheasant/TW/AW1272.01339/190.99901.125630.09210.46051.2601201156542,90044,1000.0693
    TBADipper/TW/AW1351.5736/71.06151.134830.11550.34651.2561273148336,00036,7000.0663
    TBAMartin/TW/AW1351.51342/191.06151.195930.09490.47451.3001276166245,60046,8000.0652
    TBABobolink/TW/AW1431.0736/71.12391.201630.11890.35671.2901348157138,10038,9000.0626
    TBAPlover/TW/AW1431.01340/191.12391.266330.09770.48851.3371351176048,30049,6000.0616
    TBALapwing/TW/AW1590.0736/71.24881.335130.12530.37591.3581498174641,80042,2000.0564
    TBAFalcon/TW/AW1590.01342/191.24881.407130.10300.51501.4101501195653,60055,1000.0554
    TBAChukar/TW/AW1780.0838/191.39801.512030.08740.43701.4451674200249,10050,7000.0501
    TBABluebird/TW/AW2156.0864/191.69331.831140.09610.48051.6082045244159,80061,1000.0417

    Diameter Equal to Standard ACSR Conductor - Weights, Measurements, Electrical and Engineering Data
    Stock NumberCode WordConductor SizeType No.StrandingACSR with Equal DiameterCross-Sectional AreaLayers of AlDiameterWeightRated Breaking StrengthDC Resistance @ 20°C
    AW StrandsAW CoreComplete Conductor
    Code WordSizeStrandingAlTotalAlTotalAW2AW3
    kcmilAl/AWkcmilAl/AWin²in²inininlb/1000ftlb/1000ftlblbΩ/mile
    TBAMonongahela/TW/AW405.1614/1Merlin336.418/10.31820.336320.15200.15200.680379.7431.410,00010,2000.2210
    TBACalumet/TW/AW565.31620/7Hawk477.026/70.44400.516220.11460.34380.860531.2738.322,30022,9000.1534
    TBAMohawk/TW/AW571.71318/7Flicker477.024/70.44900.507320.10300.30900.850536.6703.820,00020,6000.1532
    TBAOswego/TW/AW664.81620/7Dove556.526/70.52210.607220.12440.37320.927624.6868.726,20026,6000.1304
    TBAMystic/TW/AW666.61320/7Parakeet556.524/70.52350.591420.11110.33330.913625.7820.523,30024,0000.1314
    TBAWabash/TW/AW762.81620/7Grosbeak636.026/70.59910.696520.13310.39930.990716.7996.129,60030,5000.1137
    TBAMaumee/TW/AW768.21320/7Rook636.024/70.60330.681820.11950.35850.977721.0946.226,90027,7000.1140
    TBANechako/TW/AW768.9327/1Swift636.036/10.60390.622030.15200.15200.930723.5775.216,30016,4000.1180
    TBAFraser/TW/AW946.71034/7Puffin795.022/70.74350.816730.11540.34621.077892.5110328,90029,6000.0938
    TBAKettle/TW/AW957.2732/7Tern795.045/70.75180.803830.09730.29191.060901.6105125,50026,0000.0936
    TBASuwannee/TW/AW959.61622/7Drake795.026/70.75370.876220.14930.44791.110901.7125336,00037,2000.0904
    TBAColumbia/TW/AW966.21322/7Condor795.054/70.75890.857320.13380.40141.092907.0118933,40034,3000.0906
    TBAGenesee/TW/AW1158.0734/7Rail954.045/70.90950.973430.10780.32341.1651091127431,00031,6000.0774
    TBAHudson/TW/AW1158.41324/7Cardinal954.054/70.90981.028120.14670.44011.1961087142638,50039,6000.0756
    TBACheyenne/TW/AW1168.1530/7Phoenix954.042/70.91740.964530.09260.27781.1551099123428,40028,8000.0771
    TBAYukon/TW/AW1233.61338/19Curlew1033.554/70.96891.092530.09100.45501.2451165152041,70042,9000.0714
    TBANelson/TW/AW1257.1736/7Ortolan1033.545/70.98731.055630.11150.33451.2131184138033,50034,2000.0713
    TBACatawba/TW/AW1272.0530/7Snowbird1033.542/70.99901.050430.09670.29011.2031197134430,90031,4000.0708
    TBAThames/TW/AW1334.61338/19Finch1113.054/191.04821.181230.09440.47201.2901260164245,00046,3000.0660
    TBAMackenzie/TW/AW1359.7738/7Bluejay1113.045/71.06791.141830.11590.34771.2601281149336,20037,0000.0659
    TBATruckee/TW/AW1372.5530/7Avocet1113.042/71.07801.133430.10040.30121.2481292145132,90033,4000.0656
    TBAMerrimack/TW/AW1433.61339/19Grackle1192.554/191.12591.268630.09780.48901.3401354176448,40049,7000.0615
    TBAMiramichi/TW/AW1455.3736/7Bunting1192.545/71.14301.222230.12000.36001.3021371159838,80039,2000.0616
    TBASt. Croix/TW/AW1467.8533/7Oxbird1192.542/71.15281.212430.10410.31231.2921381155235,20035,8000.0613
    TBARio Grande/TW/AW1533.31338/19Pheasant1272.054/191.20431.357130.10120.50601.3801448188751,80053,2000.0575
    TBAPotomac/TW/AW1557.4736/7Bittern1272.045/71.22321.307930.12410.37231.3501467171041,50041,9000.0575
    TBAPlatte/TW/AW1569.0533/7Scissortail1272.042/71.23231.295730.10740.32221.3341476165837,60038,2000.0574
    TBAPecos/TW/AW1622.01339/19Martin1351.554/191.27391.442830.10640.53201.4201531201755,90057,5000.0542
    TBASchuylkill/TW/AW1657.4736/7Dipper1351.545/71.30171.391830.12800.38401.3861561182043,60044,0000.0541
    TBAJames/TW/AW1730.61339/19Plover1431.054/191.35921.531630.10750.53751.4701634213057,80059,4000.0509
    TBAPee Dee/TW/AW1758.6738/7Bobolink1431.045/71.38121.476830.13190.39571.4301656193045,80046,7000.0510
    TBACumberland/TW/AW1926.91342/19Falcon1590.054/191.51341.705030.11330.56651.5501819237064,30066,0000.0457
    TBAAthabaska/TW/AW1949.6744/7Lapwing1590.045/71.53121.637730.13920.41761.5041836214250,30051,9000.0460
    TBAPowder/TW/AW2153.8864/19Chukar1780.084/191.69161.829440.09610.48051.5962043243959,80061,1000.0417
    TBASantee/TW/AW2627.3864/19Bluebird2156.084/192.06352.231840.10620.53101.7612492297673,00074,5000.0342

    Revision: 1.000.006

    Updated On: Oct. 26, 2026, 3:42 p.m. UTC