SPEC 84013

3-Layer 15kV AAAC CAMV™ Covered Conductor (Tree Wire or Spacer Cable)

An Alternative and Robust Design to Bare AAAC Conductors to Harden the Electrical Grid.
3-Layer, 15kV, Covered Conductor, Concentrically Stranded AAAC, Track-Resistant Crosslinked Polyethylene.

...

Construction:

  1. Conductor:Concentrically stranded aluminum-alloy 6201-T81 wires AAAC
  2. Strand Shield:Semi-conducting cross linked polymer
  3. Inner Layer:Low-Density Crosslinked Polyethylene (LDXLPE)
  4. Outer Layer:High-Density Track-Resistant Crosslinked Polyethylene (HDTRXLPE)

Applications and Features:

  • Used for primary and secondary overhead distribution where limited space is available or desired for rights-of-way. Installed the same as bare conductors, however, covering is effective in preventing direct shorts and instantaneous flashovers should tree limbs or other objects contact conductors in such close proximity.
  • Tree Wire - Used for spans where trees crowd the right-of-way, such as in wooded residential areas, when a minimum of interference with the environment is desired. Covering minimizes power outages due to conductor contact with tree limbs, reducing the need for frequent or severe trimming.
  • Covered Aerial MV Cable (CAMV)/Spacer Cable - Installed with other Covered Aerial MV cables and a supporting messenger through a series of space-maintaining devices (spacers). The resulting close-proximity configuration minimizes the amount of space and hardware required for line installation, particularly useful in congested areas.
  • Specifications:

  • ASTM B398 Standard Specification for Aluminum-Alloy 6201-T81 and 6201-T83 Wire for Electrical Purposes
  • ASTM B400 Standard Specification for Compact Round Concentric-Lay-Stranded, Aluminum 1350 Conductors
  • ICEA S-121-733 Tree Wire and Messenger Supported Spacer Cable
  • Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. StrandsDiameter Over ConductorConductor Shield ThicknessInner Layer ThicknessOuter Layer ThicknessApprox. ODApprox. WeightRated StrengthAllowable Ampacity In Air 90°C†
    AWG/Kcmil#inchmilmilmilinchlb/1000ftlbAmp
    TBA48.6970.251575750.581371584163
    TBA77.4770.3161575750.6161672520217
    142448123.370.3981575750.7282364014289
    TBA155.470.4471575750.7772834851333
    TBA195.770.5021575750.8323346111384
    622448246.970.5631575750.8633857704444
    TBA312.8190.6421575750.9724739900
    TBA394.5190.721575751.0556811970
    All dimensions are nominal and subject to normal manufacturing tolerances
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.