SPEC 83354
Covered Line Wire With Thermoplastic Polyethylene (PE)
Aluminum Conductor Covered with Black Polyethylene (PE)

Construction:
- Conductor:Conductors are solid or stranded compressed aluminum
- Covering:Black Polyethylene (PE)
Applications and Features:
Aluminum alloy 1350-H19 or 6201 concentrically stranded. Covered with Black Polyethylene (PE). Used primarily for, but not limited to, overhead secondary distribution lines. Installed on insulators, otherwise treated as a bare conductor. Black Polyethylene (PE) covered line wires have the below temperature ratings:
Normal Service temperature of 75ºC Emergency Overload of 95ºC Short Circuit temperature of 150ºC
Specifications:
Table 1 – Weights and Measurements
| Stock Number | Code Word | Phase Cond. Size | Phase Strand | Phase Insul. Thickness | Approx. OD | Approx. Weight |
|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | mil | inch | lb/1000ft | ||
| 102442 | HORNBEAM | 48.69 | 7 | 30 | 0.31 | 59 |
| 102467 | OILNUT | 123.3 | 7 | 60 | 0.518 | 158 |
| 102491 | PLANETREE | 246.9 | 7 | 60 | 0.683 | 295 |
| 102236 | MOLLES | 397.5 | 19 | 80 | 0.861 | 459 |
| 102244 | HUCKLEBERRY | 477 | 37 | 80 | 0.931 | 540 |
| 102269 | PERSIMMON | 795 | 61 | 95 | 1.187 | 885 |
| TBA | APPLE | 6 | SOLID | 45 | 0.252 | 41 |
| TBA | PLUM | 6 | 7 | 45 | 0.268 | 42 |
| TBA | PEAR | 4 | SOLID | 45 | 0.294 | 58 |
| 102145 | APRICOT | 4 | 7 | 30 | 0.285 | 50 |
| TBA | CHERRY | 2 | SOLID | 45 | 0.348 | 85 |
| TBA | LINDEN | 2 | 7 | 45 | 0.373 | 87 |
| 102152 | PEACH | 2 | 7 | 45 | 0.373 | 83 |
| TBA | NECTARINE | 1 | 7 | 60 | 0.442 | 118 |
| 102160 | QUINCE | 1/0 | 7 | 60 | 0.477 | 134 |
| TBA | WATERASH | 2/0 | 7 | 60 | 0.525 | 171 |
| TBA | ORANGE | 2/0 | 7 | 60 | 0.525 | 171 |
| 102186 | FIG | 3/0 | 7 | 60 | 0.57 | 202 |
| TBA | SHELLBARK | 3/0 | 7 | 60 | 0.576 | 209 |
| 102194 | OLIVE | 4/0 | 7 | 60 | 0.626 | 248 |
| TBA | POMEGRANATE | 4/0 | 19 | 60 | 0.632 | 255 |
| 102228 | ANNONA | 336.4 | 19 | 60 | 0.766 | 375 |
| 621974 | ANNONA | 336.4 | 19 | 60 | 0.786 | 388 |
All dimensions are nominal and subject to normal manufacturing tolerances
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Code Word | Phase Cond. Size |
|---|---|
| AWG/Kcmil | |
| HORNBEAM | 48.69 |
| OILNUT | 123.3 |
| PLANETREE | 246.9 |
| MOLLES | 397.5 |
| HUCKLEBERRY | 477 |
| PERSIMMON | 795 |
| APPLE | 6 |
| PLUM | 6 |
| PEAR | 4 |
| APRICOT | 4 |
| CHERRY | 2 |
| LINDEN | 2 |
| PEACH | 2 |
| NECTARINE | 1 |
| QUINCE | 1/0 |
| WATERASH | 2/0 |
| ORANGE | 2/0 |
| FIG | 3/0 |
| SHELLBARK | 3/0 |
| OLIVE | 4/0 |
| POMEGRANATE | 4/0 |
| ANNONA | 336.4 |
| ANNONA | 336.4 |
* Ampacity ratings based on 75ºC conductor temperature 40ºC ambient temperature. Wind speed 2 ft./sec. in sun.
* Diameter equivalent to ACSR construction or 1350 aluminum equivalent.
* Diameter equivalent to ACSR construction or 1350 aluminum equivalent.
Revision: 1.000.009
Updated On: Feb. 5, 2025, 2:48 a.m. UTC
