SPEC 85030

Multi-Conductor CU 600 V Shielded PE/PVC Insulation PVC Jacket Control Cable Color Method 1 Table 1

Control Cable 600 Volt Copper Conductors, Polyethylene Polyvinyl Chloride (PE/PVC) Insulation Shielded Polyvinyl Chloride (PVC) Jacket, Control Cable Conductor Identification Method 1 Table 1. Silicone Free

...

Construction:

  1. Conductor:7 strands class B compressed bare copper per ASTM B3 and ASTM B8
  2. Insulation:Polyethylene (PE) and Polyvinyl Chloride (PVC)
  3. Filler:Polypropylene filler on cables with 5 or less conductors
  4. Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
  5. Shielding:5 mil copper Helically-Applied Tape shield
  6. Rip Cord:Rip cord for ease of jacket removal
  7. Overall Jacket:Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire’s 600 Volt control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 75°C for normal operation in wet and dry locations, 90°C for emergency overload, and 150°C for short circuit conditions.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA CSA marking is available upon request
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 1
  • ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • Sample Print Legend:

    SOUTHWIRE XX AWG X/C PE/PVC CDRS 600V SHIELDED PVC JKT SUN. RES. DIRECT BURIAL {MM/DD/YYYY} {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over Cond.Insul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°CInductive RectanceMin Bending RadiusAllowable Ampacity 75°CAllowable Ampacity 90°C
    AWGNo.strandsinchmilmilinchlb/1000ftlb/1000ftΩ/1000ftΩ/1000ftΩ/1000ftinchAmpAmp
    18 AWG
    60678518370.04525450.32632666.6698.0350.0363.9-14
    60678918770.04525450.414581166.6698.0350.0365-9
    606790181270.04525450.515901696.6698.0350.0366.2-7
    14 AWG
    60676714770.07030450.5141191982.6313.1700.0586.21417
    618969141270.07030600.6901943312.6313.1700.0588.31012
    12 AWG
    61872112270.08830450.421641141.6622.0020.0545.12530
    61872212370.08830450.445861461.6622.0020.0545.32530
    61872312470.08830450.4841091821.6622.0020.0545.82024
    61872412770.08830600.6041762871.6622.0020.0547.21721
    617106121270.08830800.8102904681.6622.0020.0549.71215
    10 AWG
    60676810270.11330450.464911551.0401.2530.0505.63540
    61916210370.11330450.4911251961.0401.2530.0505.93540
    61710510470.11330600.5581602461.0401.2530.0506.72832
    62088110470.11330600.5621682601.0401.2530.0506.72832
    60676910570.11330600.6151963021.0401.2530.0507.42832
    61896810770.11330600.6592643871.0401.2530.0507.92428
    62229610770.11330600.6632663911.0401.2530.05082428
    60677010970.11330600.7783354901.0401.2530.0509.32428
    606771101270.11330800.9114386631.0401.2530.05010.91720
    8 AWG
    6067738270.14160600.6861422750.6530.7860.0528.25055
    6203018370.14160600.7291953530.6530.7860.0528.75055
    6073978570.14160800.9163085530.6530.7860.052114044
    6 AWG
    6067746270.17770600.7982113680.4110.4950.0519.66575
    TBA6370.17770800.8873235620.4110.4950.05110.66575
    6263046470.17770800.9753816640.4110.4950.05111.75260
    6008996570.17770801.0504717770.4110.4950.05112.65260
    2 AWG
    TBA2370.28245800.9886768980.1620.1950.04511.9115130
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements. Ampacities have been adjusted for stock numbers containing more than Three Current-Carrying Conductors.

    Revision: 1.000.002

    Updated On: July 3, 2024, 10:14 p.m. UTC