SPEC 85023

Multi-Conductor CU 600 V FR-XLPE LCT Shielded Thermoplastic CPE-TP Jacket Control Cable Color Method 1 Table 1

Control Cable 600 Volt Copper Conductors, Flame Retardant Cross Linked Polyethylene (FR-XLPE) Insulation Shielded Thermoplastic Chlorinated Polyethylene Chloride (CPE-TP) Jacket, Control Cable Conductor Identification Method 1 Table 1. Silicone Free

...

Construction:

  1. Conductor:7 strands class B compressed bare copper per ASTM B3 and ASTM B8
  2. Insulation:Flame Retardant Cross Linked Polyethylene (FR-XLPE), 30 Mils thick for all cable sizes
  3. Filler:Polypropylene filler on cables with 5 or less conductors
  4. Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
  5. Shield:5 mils copper Longitudinally-Applied Corrugated Tape (LCT) shield
  6. Rip Cord:Rip cord for ease of jacket removal
  7. Overall Jacket:Thermoplastic Chlorinated Polyethylene Chloride (CPE-TP)

Applications and Features:

Southwire’s 600 Volt control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. UL rated construction can be used in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. UL rated constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 1
  • ICEA S-73-532 Control, Thermocouple Extension, and Instrumentation Cables (applicable to sizes 20-9 AWG conductors)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Vertical Tray Flame Test (70,000 Btu/hr) and ICEA T-29-520 - (210,000 Btu/hr)
  • VW-1 (Vertical-Wire) Flame Test
  • Sample Print Legend:

    UL Listed
    SOUTHWIRE E75755 {UL} XX AWG X/C FR-XLPE XHHW-2 TYPE TC-ER CDRS 90C CPE JKT SHIELDED 600V SUN RES YEAR {SEQUENTIAL FOOTAGE MARKS} SEQ FEET

    Non UL Listed
    SOUTHWIRE XX AWG X/C FR-XLPE CDRS 90C CPE JKT SHIELDED 600V SUN. RES. DIRECT BURIAL YEAR SEQUENTIAL FOOTAGE MARKS SEQ FEET

    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over Cond.Insul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°CInductive RectanceMin Bending RadiusAllowable Ampacity 75°CAllowable Ampacity 90°CJacket Color
    AWGNo.strandsinchmilmilinchlb/1000ftlb/1000ftΩ/1000ftΩ/1000ftΩ/1000ftinchAmpAmp
    18 AWG
    62321918270.04625450.38737866.6698.6760.0394.6-14Black
    606669^181070.04625600.638952056.6698.6760.0397.7-7Black
    14 AWG
    60368314770.07030600.6121282562.6313.1700.0587.31417Black
    604417141970.07030800.9183105872.6313.1700.05811.01012Black
    12 AWG
    60368912270.08830450.456741401.6622.0020.0545.52530Black
    603691^12470.08830450.5121142031.6622.0020.0546.12024Black
    60369212570.08830600.5631432411.6622.0020.0546.82024Black
    62783212470.08830600.5791142211.6622.0020.0546.92024Black
    60369412770.08830600.6611873241.6622.0020.0547.91721Black
    60369712970.08830600.7782334111.6622.0020.0549.31721Black
    603699121270.08830800.8722995291.6622.0020.05410.51215Black
    618870$128190.09030600.7201963511.6622.0020.0548.61721Black
    621553&1212190.09030800.8883005361.6622.0020.05410.71215Black
    10 AWG
    62133310270.11330450.509641901.0401.2530.0506.13540Black
    60370110270.11330600.5661031981.0401.2530.0506.83540Black
    60370210370.11330600.5931352491.0401.2530.0507.13540Black
    618685^10470.11330600.6361293121.0401.2530.0507.62832Black
    603703^10470.11330600.6361622921.0401.2530.0507.62832Black
    619436^10470.11330600.6521733111.0401.2530.0507.82832Black
    662671^10570.11330600.6851613531.0401.2530.0508.22832Black
    60370710770.11330600.7372764441.0401.2530.0508.82428Black
    603709^10970.11330800.8803245601.0401.2530.05010.62428Black
    603711101270.11330800.9744557261.0401.2530.05011.71720Black
    621305$102190.11730600.566981911.0401.2530.0506.83540Black
    604324$104190.11730600.6541652721.0401.2530.0507.82832Black
    661043!&109190.11730800.8843465731.0401.2530.05010.62428Black
    604325!1012190.11730800.9834216911.0401.2530.05011.81720Black
    8 AWG
    6037148370.14145600.7301993630.6530.7860.0528.85055Black
    6043208470.14145600.7902564340.6530.7860.0529.54044Black
    62563581270.14145801.22970111130.6530.7860.05214.72527Black
    6 AWG
    6256396270.17745600.7562103630.4110.4950.0519.16575Black
    6043196370.17745600.8022784520.4110.4950.0519.66575Black
    TBA6470.17745800.9083835790.4110.4950.05110.95260Black
    4 AWG
    6043184370.22545800.9404577130.2580.3100.04811.38595Black
    TBA4470.22545801.0245868140.2580.3100.04812.36876Black
    2 AWG
    6043162270.28245801.0144476980.1620.1950.04512.2115130Black
    6043172370.28245801.08369210230.1620.1950.04513.0115130Black
    604315$12190.33355801.1225969030.1280.1540.04613.5130145Black
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    ^ UL listed part number
    ! Tinned copper conductor per ASTM B33
    $ 19 strand combination unilay conductor per ASTM B787
    & 19 strand Class C compressed conductor per ASTM B8
    * Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements. Ampacities have been adjusted for stock numbers containing more than Three Current-Carrying Conductors.
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.