SPEC 85020

Multi-Conductor CU 600 V FR-XLPE Shielded PVC Jacket Control Cable Color Method 1 Table 2

Control Cable 600 Volt Copper Conductors, Flame Retardant Cross Linked Polyethylene (FR-XLPE) Insulation Shielded Polyvinyl Chloride (PVC) Jacket, Control Cable Conductor Identification Method 1 Table 2. Silicone Free

...

Construction:

  1. Conductor:7 strands class B compressed bare copper per ASTM B3 and ASTM B8
  2. Insulation:Flame Retardant Cross Linked Polyethylene (FR-XLPE), 30 Mils thick for all cable sizes
  3. Filler:Polypropylene filler on cables with 5 or less conductors
  4. Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
  5. Shielding:5 mil copper Helically-Applied Tape shield
  6. Rip Cord:Rip cord for ease of jacket removal
  7. Overall Jacket:Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire’s 600 Volt control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. UL rated constructions can be used in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. UL rated constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • CSA CSA marking is available upon request
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 2
  • ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • VW-1 (Vertical-Wire) Flame Test
  • Sample Print Legend:

    UL Listed
    SOUTHWIRE E75755 {UL} XX AWG X/C FR-XLPE CDRS 90°C PVC JKT TYPE TC-ER SHIELDED 600V SUN. RES. DIRECT BURIAL {YYYY} {SEQUENTIAL FOOTAGE MARKS} SEQ FEET

    Non UL Listed
    SOUTHWIRE XX AWG X/C FR-XLPE CDRS 90C PVC JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600V {SEQUENTIAL FOOTAGE MARKS} SEQ FEET

    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over Cond.Insul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°CInductive RectanceMin Bending RadiusAllowable Ampacity 75°CAllowable Ampacity 90°C
    AWGNo.strandsinchmilmilinchlb/1000ftlb/1000ftΩ/1000ftΩ/1000ftΩ/1000ftinchAmpAmp
    14 AWG
    TBA14270.07030450.37248922.6313.1700.0584.52025
    TBA14370.07030450.392621122.6313.1700.0584.72025
    TBA14470.07030450.426781302.6313.1700.0585.11620
    TBA14570.07030450.463931542.6313.1700.0585.61620
    TBA14670.07030450.5021101792.6313.1700.0586.01620
    623664^14770.07030450.5061192022.6313.1700.0586.11417
    TBA14870.07030600.5721392382.6313.1700.0586.91417
    TBA14970.07030600.6111562652.6313.1700.0587.31417
    TBA141070.07030600.6621722922.6313.1700.0587.91012
    TBA141270.07030600.6822003312.6313.1700.0588.21012
    TBA141570.07030600.7542443992.6313.1700.0589.01012
    TBA141970.07030600.7922994782.6313.1700.0589.51012
    TBA142070.07030800.8723155382.6313.1700.05810.51012
    TBA142570.07030800.9623866472.6313.1700.05811.5911
    TBA143070.07030801.0154557492.6313.1700.05812.2911
    TBA143770.07030801.0925528932.6313.1700.05813.1810
    12 AWG
    TBA12270.08830450.408661171.6622.0020.0544.92530
    662580^12370.08830450.436841461.6622.0020.0545.22530
    618928^12470.08830450.4691081751.6622.0020.0545.62024
    TBA12570.08830450.5111362051.6622.0020.0546.12024
    TBA12670.08830600.5861602561.6622.0020.0547.02024
    618929^12770.08830600.5871752881.6622.0020.0547.01721
    TBA12870.08830600.6312043171.6622.0020.0547.61721
    672088^12970.08830600.6852213611.6622.0020.0548.21721
    TBA121070.08830600.7342543901.6622.0020.0548.81215
    604105^121270.08830600.7522884511.6622.0020.0549.01215
    618930^121270.08830600.7582894571.6622.0020.0549.11215
    620555121270.08830600.7682914581.6622.0020.0549.21215
    TBA121570.08830800.8793655771.6622.0020.05410.51215
    618893^121970.08830800.9563996831.6622.0020.05411.51215
    TBA122070.08830800.9674747291.6622.0020.05411.61215
    TBA122570.08830801.0705858851.6622.0020.05412.81113
    TBA123070.08830801.13069210311.6622.0020.05413.61113
    TBA123770.08830801.21884112351.6622.0020.05414.61012
    10 AWG
    62068010270.11330450.450911471.0401.2530.0503.23540
    604107^10370.11330450.4871251991.0401.2530.0503.43540
    618932^10470.11330600.5581602621.0401.2530.0503.92832
    620684^10470.11330600.5661612591.0401.2530.0504.02832
    628507^10570.11330600.6151943071.0401.2530.0504.32832
    618933^10770.11330600.6592643981.0401.2530.0504.62428
    TBA10670.11330600.6612393521.0401.2530.0504.62832
    623305^10870.11330600.7203014521.0401.2530.0505.02428
    620683^10970.11330600.7793305051.0401.2530.0505.52428
    TBA101070.11330800.8743835781.0401.2530.05010.51720
    618935^101270.11330800.8904396671.0401.2530.05010.71720
    620681^101270.11330800.9034416781.0401.2530.05010.81720
    628501^101270.11330800.9034386731.0401.2530.05010.81720
    TBA101570.11330800.9965558041.0401.2530.05012.01720
    TBA102070.11330801.10072510261.0401.2530.05013.21720
    TBA102570.11330801.22089812531.0401.2530.05014.61518
    TBA103070.11330801.290106614671.0401.2530.05015.51518
    TBA103770.11330801.393130017661.0401.2530.05016.71416
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    ^ UL listed part number
    * Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements. Ampacities have been adjusted for stock numbers containing more than Three Current-Carrying Conductors.

    Revision: 1.000.002

    Updated On: July 3, 2024, 10:14 p.m. UTC