SPEC 83023

Triple Parallel 600 Volt USE-2 Underground Service Entrance

...

Construction:

  1. Conductor:Conductors are stranded, compressed 1350-H16/H26 (3/4 Hard) aluminum
  2. Insulation:Cross Linked Polyethylene (XLPE)
  3. Neutral:Cross Linked Polyethylene (XLPE) with three Yellow Extruded Stripes (YES)

For information about our Cable-Rejuvenation Services please visit us at:  Cable-Rejuvenation Services
You can email us at: Cable-Rejuvenation Services

Applications and Features:

Conductors are stranded, compressed 1350-H16/H26 (3/4 Hard) aluminum, insulated with cross-linked polyethylene. Neutrals are identified by three yellow extruded stripes. Cables with “YES” neutrals have sequential footage markers. Conductors are durably surface printed for identification. Two-phase conductors and one neutral conductor are triple paralleled. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions.

Specifications:

  • ASTM B231 Standard Specification for Concentric-Lay-Stranded Aluminum 1350 Conductors
  • ASTM B609 Standard Specification for Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes
  • ASTM B901 Standard Specification for Compressed Round Stranded Aluminum Conductors Using Single Input Wire Construction. (The number of strands for both phase and neutral may differ)
  • UL 854 Service Entrance Cable
  • ICEA S-105-692 Standard For 600 Volt Single Layer Thermoset Insulated Utility Underground Distribution Cables
  • Table 1 – Weights and Measurements
    Stock NumberCode WordPhase Cond. SizePhase StrandDia. Over Phase ConductorPhase Insul. ThicknessDia. Over Phase InsulationNeutral Cond. SizeNeutral StrandNeutral Insul. ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.inchmilinchAWG/KcmilNo.milinchlb/1000ft
    TBAKittrell870.141600.26186600.566136
    TBADon Bosco670.177600.29766600.644189
    TBAAsbury470.225600.34546600.747268
    TBALasell270.282600.40246600.870363
    TBASussex270.282600.40226600.870386
    TBARosary1/0190.361800.52126801.127594
    TBALuther1/0190.361800.5211/07801.127630
    TBAPeace2/0190.405800.56517801.222717
    TBALehman2/0190.405800.5652/011801.222762
    TBAMarywood3/0190.456800.6161/011801.333868
    TBANyack3/0190.456800.6163/015801.333929
    TBABelmont4/0190.512800.6722/011801.4541054
    TBAGlassboro4/0190.512800.6724/017801.4541126
    TBABaruch250370.558950.7483/015951.6181296
    TBAGrinnell350370.661950.8514/017951.8401698
    TBAAntioch500370.789950.97930018952.1172314
    TBATrenton500370.789950.97935024952.1172367
    All dimensions are nominal and subject to normal manufacturing tolerances
    1. The actual number of strands may differ for single input wire per ASTM B901
    Table 2 – Electrical and Engineering Data
    Code WordPhase Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity in Duct 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmp
    Kittrell82.32971.0711.2900.05240 / 45
    Don Bosco62.64720.6740.8120.05150 / 55
    Asbury43.07510.4240.5110.04865 / 75
    Lasell23.511940.2660.3200.04590 / 100
    Sussex23.511940.2660.3200.04590 / 100
    Rosary1/05.619000.1670.2010.044120 / 135
    Luther1/05.619000.1670.2010.044120 / 135
    Peace2/06.123950.1330.1590.043135 / 150
    Lehman2/06.123950.1330.1590.043135 / 150
    Marywood3/06.730200.1050.1260.042155 / 175
    Nyack3/06.730200.1050.1260.042155 / 175
    Belmont4/07.338080.0840.1000.041180 / 205
    Glassboro4/07.338080.0840.1000.041180 / 205
    Baruch2508.145000.0710.0860.041205 / 230
    Grinnell3509.263000.0500.0620.040250 / 280
    Antioch50012.790000.0350.0440.039310 / 350
    Trenton50012.790000.0350.0440.039310 / 350
    Notes:
    1. Inductive reactance assumes cables are cradled in conduit, and the neutral is carrying no current.
    2. Triple parallel inductive reactance calculation assumes the phase conductors are adjacent to one another.
    3. Conductors assumed to be reverse lay stranded, compressed construction.
    4. Phase spacing assumes cables are touching.
    5. Resistances shown are for the Phase conductors only.
    6. Ampacity based on 90°C conductor temperature, 20°C ambient, RHO 90, 100% load factor.

    Revision: 1.000.000

    Updated On: July 3, 2024, 9:53 p.m. UTC