SPEC 83001
Single 600 Volt USE-2 Aluminum Underground Service Entrance

Construction:
- Conductor:Conductors are stranded, compressed 1350-H16/H26 (3/4 Hard) aluminum
- Insulation:Cross Linked Polyethylene (XLPE) Type USE-2
For information about our Cable-Rejuvenation Services please visit us at: Cable-Rejuvenation Services
You can email us at: Cable-Rejuvenation Services
Applications and Features:
Conductors are stranded, compressed 1350-H16/H26 (3/4 Hard) aluminum, insulated with cross-linked polyethylene UL listed as Type USE-2 . These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions.
Specifications:
Table 1 – Weights and Measurements
| Stock Number | Code Word | Phase Cond. Size | Phase Strand | Dia. Over Phase Conductor | Phase Insul. Thickness | Dia. Over Phase Insulation | Approx. OD | Approx. Weight |
|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | inch | mil | inch | inch | lb/1000ft | ||
| 154435 | PRINCETON | 6 | 7 | 0.178 | 60 | 0.298 | 0.298 | 43 |
| 105437 | MERCER | 4 | 7 | 0.225 | 60 | 0.345 | 0.345 | 62 |
| 105445! | CLEMSON | 2 | 7 | 0.283 | 60 | 0.403 | 0.403 | 90 |
| 105452! | KENYON | 1 | 9 | 0.322 | 80 | 0.482 | 0.473 | 121 |
| 105460! | HARVARD | 1/0 | 9 | 0.362 | 80 | 0.522 | 0.512 | 146 |
| 105478! | YALE | 2/0 | 11 | 0.405 | 80 | 0.565 | 0.555 | 176 |
| 105486! | TUFTS | 3/0 | 17 | 0.456 | 80 | 0.616 | 0.603 | 213 |
| 105494! | BELOIT | 4/0 | 18 | 0.512 | 80 | 0.672 | 0.658 | 261 |
| 161877! | HOFSTRA | 250 | 22 | 0.558 | 95 | 0.748 | 0.726 | 314 |
| 105502 | GONZAGA | 300 | 37 | 0.611 | 95 | 0.801 | 0.784 | 367 |
| 105510! | RUTGERS | 350 | 30 | 0.661 | 95 | 0.851 | 0.831 | 421 |
| 105528! | EMORY | 500 | 34 | 0.789 | 95 | 0.979 | 0.95 | 576 |
| 245480 | EMORY | 500 | 37 | 0.789 | 95 | 0.979 | 0.956 | 578 |
| 105536 | DUKE | 600 | 61 | 0.866 | 110 | 1.086 | 1.086 | 703 |
| 105551 | SEWANEE | 750 | 55 | 0.968 | 110 | 1.188 | 1.159 | 852 |
| 258954 | FORDHAM | 1000 | 61 | 1.117 | 110 | 1.337 | 1.337 | 1116 |
All dimensions are nominal and subject to normal manufacturing tolerances
1. The actual number of strands may differ for single input wire per ASTM B901
! Conductor is ASTM B901
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
! Conductor is ASTM B901
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Code Word | Phase Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 75°C | Inductive Reactance @ 60Hz | Allowable Ampacity in Duct or Buried 75/90°C |
|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | |
| PRINCETON | 6 | 1.2 | 157 | 0.674 | 0.84 | 0.051 | 50/55 |
| MERCER | 4 | 1.4 | 250 | 0.424 | 0.528 | 0.048 | 65/75 |
| CLEMSON | 2 | 1.6 | 398 | 0.266 | 0.331 | 0.045 | 90/100 |
| KENYON | 1 | 1.9 | 502 | 0.211 | 0.263 | 0.046 | 100/115 |
| HARVARD | 1/0 | 2 | 633 | 0.167 | 0.208 | 0.044 | 120/135 |
| YALE | 2/0 | 2.2 | 798 | 0.133 | 0.166 | 0.043 | 135/150 |
| TUFTS | 3/0 | 2.4 | 1006 | 0.105 | 0.131 | 0.042 | 155/175 |
| BELOIT | 4/0 | 2.6 | 1269 | 0.084 | 0.105 | 0.041 | 180/205 |
| HOFSTRA | 250 | 2.9 | 1500 | 0.07 | 0.087 | 0.041 | 205/230 |
| GONZAGA | 300 | 3.1 | 1800 | 0.059 | 0.074 | 0.041 | 230/260 |
| RUTGERS | 350 | 3.3 | 2100 | 0.051 | 0.064 | 0.04 | 250/280 |
| EMORY | 500 | 3.8 | 3000 | 0.036 | 0.045 | 0.039 | 310/350 |
| EMORY | 500 | 3.8 | 3000 | 0.036 | 0.045 | 0.039 | 310/350 |
| DUKE | 600 | 5.4 | 3600 | 0.03 | 0.038 | 0.039 | 340/385 |
| SEWANEE | 750 | 5.8 | 4500 | 0.023 | 0.03 | 0.038 | 385/435 |
| FORDHAM | 1000 | 6.7 | 6000 | 0.017 | 0.023 | 0.037 | 445/500 |
Ampacities are based on Table 310.15 (B)(16) of the NEC, 2017 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts, based on ambient temperature of 30°C (86°F)