SPEC 83001

Single 600 Volt USE-2 Aluminum Underground Service Entrance

...

Construction:

  1. Conductor:Conductors are stranded, compressed 1350-H16/H26 (3/4 Hard) aluminum
  2. Insulation:Cross Linked Polyethylene (XLPE) Type USE-2

For information about our Cable-Rejuvenation Services please visit us at:  Cable-Rejuvenation Services
You can email us at: Cable-Rejuvenation Services

Applications and Features:

Conductors are stranded, compressed 1350-H16/H26 (3/4 Hard) aluminum, insulated with cross-linked polyethylene UL listed as Type USE-2 . These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions.

Specifications:

  • ASTM B231 Standard Specification for Concentric-Lay-Stranded Aluminum 1350 Conductors
  • ASTM B901 Standard Specification for Compressed Round Stranded Aluminum Conductors Using Single Input Wire Construction. (The number of strands for both phase and neutral may differ)
  • UL 854 Service Entrance Cable
  • ICEA S-105-692 Standard For 600 Volt Single Layer Thermoset Insulated Utility Underground Distribution Cables
  • Table 1 – Weights and Measurements
    Stock NumberCode WordPhase Cond. SizePhase StrandDia. Over Phase ConductorPhase Insul. ThicknessDia. Over Phase InsulationApprox. ODApprox. Weight
    AWG/KcmilNo.inchmilinchinchlb/1000ft
    154435PRINCETON670.178600.2980.29843
    105437MERCER470.225600.3450.34562
    105445!CLEMSON270.283600.4030.40390
    105452!KENYON190.322800.4820.473121
    105460!HARVARD1/090.362800.5220.512146
    105478!YALE2/0110.405800.5650.555176
    105486!TUFTS3/0170.456800.6160.603213
    105494!BELOIT4/0180.512800.6720.658261
    161877!HOFSTRA250220.558950.7480.726314
    105502GONZAGA300370.611950.8010.784367
    105510!RUTGERS350300.661950.8510.831421
    105528!EMORY500340.789950.9790.95576
    245480EMORY500370.789950.9790.956578
    105536DUKE600610.8661101.0861.086703
    105551SEWANEE750550.9681101.1881.159852
    258954FORDHAM1000611.1171101.3371.3371116
    All dimensions are nominal and subject to normal manufacturing tolerances
    1. The actual number of strands may differ for single input wire per ASTM B901
    ! Conductor is ASTM B901
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Code WordPhase Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity in Duct or Buried
    75/90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmp
    PRINCETON61.21570.6740.840.05150/55
    MERCER41.42500.4240.5280.04865/75
    CLEMSON21.63980.2660.3310.04590/100
    KENYON11.95020.2110.2630.046100/115
    HARVARD1/026330.1670.2080.044120/135
    YALE2/02.27980.1330.1660.043135/150
    TUFTS3/02.410060.1050.1310.042155/175
    BELOIT4/02.612690.0840.1050.041180/205
    HOFSTRA2502.915000.070.0870.041205/230
    GONZAGA3003.118000.0590.0740.041230/260
    RUTGERS3503.321000.0510.0640.04250/280
    EMORY5003.830000.0360.0450.039310/350
    EMORY5003.830000.0360.0450.039310/350
    DUKE6005.436000.030.0380.039340/385
    SEWANEE7505.845000.0230.030.038385/435
    FORDHAM10006.760000.0170.0230.037445/500
    Ampacities are based on Table 310.15 (B)(16) of the NEC, 2017 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts, based on ambient temperature of 30°C (86°F)