SPEC 83043

Triplex 600 Volt RHH/RHW-2 or USE-2 AlumaFlex® Underground Service Entrance

...

Construction:

  1. Conductor:Conductors are stranded, compressed Triple E per ASTM 800 and 801
  2. Insulation:Cross Linked Polyethylene (XLPE) Type RHH/RHW-2 or USE-2
  3. Neutral:Cross Linked Polyethylene (XLPE) with three Yellow Extruded Stripes (YES)

Applications and Features:

Conductors are stranded, compressed aluminum Triple E AA8000 (8176-H24), insulated with cross-linked polyethylene Type RHH/RHW-2 or USE-2. Neutrals are identified by three yellow extruded stripes. Cables with “YES” neutrals have sequential footage markers. Conductors are durably surface printed for identification. Two-phase conductors and one neutral conductor are cabled together to produce the triplex cable configuration. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions.

Specifications:

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 854 Service Entrance Cable
  • ICEA S-105-692 Standard For 600 Volt Single Layer Thermoset Insulated Utility Underground Distribution Cables
  • Table 1 – Weights and Measurements
    Code WordPhase Cond. SizePhase StrandDia. Over Phase ConductorPhase Insul. ThicknessDia. Over Phase InsulationNeutral Cond. SizeNeutral StrandNeutral Insul. ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.inchmilinchAWG/KcmilNo.milinchlb/1000ft
    HOLLINS3/0190.456800.6161/07801.331637
    All dimensions are nominal and subject to normal manufacturing tolerances
    ^ HI-SCORE: Medium Density Polyethylene Insulation
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Code WordPhase Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity in Duct or Buried
    75/90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmp
    HOLLINS3/06.730200.1050.1310.042155/175
    Notes:
    1. Inductive reactance assumes cables are cradled in conduit, and the neutral is carrying no current.
    2. Conductors assumed to be reverse lay stranded, compressed construction.
    3. Phase spacing assumes cables are touching.
    4. Resistances shown are for the phase conductors only.
    5. Ampacities based upon 2023 NEC Table 310.16 Ampacities of Insulated Conductors with Not More Than Three Current-Carrying Conductors in Raceway, Cable, or Earth (Directly Buried)

    Revision: 1.000.001

    Updated On: Dec. 31, 2024, 11:09 p.m. UTC