SPEC 83353
Covered Line Wire With Crosslinked Polyethylene (XLPE)
Aluminum Conductor Covered with Black Crosslinked Polyethylene

Construction:
- Conductor:Conductors are solid or stranded compressed aluminum
- Insulation:Black Crosslinked Polyethylene (XLPE)
Applications and Features:
Aluminum alloy 1350-H19 or 6201 concentrically stranded. Covered with crosslinked polyethylene (XLP). Used primarily for, but not limited to, overhead secondary distribution lines. Installed on insulators, otherwise treated as a bare conductor. Crosslinked covered line wires have the below temperature ratings:
Normal Service temperature of 90ºC Emergency Overload of 130ºC Short Circuit temperature of 250ºC
Specifications:
Table 1 – Weights and Measurements
Stock Number | Code Word | Phase Cond. Size | Phase Strand | Phase Insul. Thickness | Approx. OD | Approx. Weight |
---|---|---|---|---|---|---|
AWG/Kcmil | No. | mil | inch | lb/1000ft | ||
TBA | Apple | 6 | Solid | 30 | 0.222 | 31 |
TBA | Plum | 6 | 7 | 30 | 0.238 | 56 |
TBA | Pear | 4 | Solid | 30 | 0.264 | 47 |
663570 | Apricot | 4 | 7 | 30 | 0.285 | 51 |
TBA | Cherry | 2 | Solid | 45 | 0.348 | 78 |
104240 | Peach | 2 | 7 | 45 | 0.373 | 84 |
TBA | Nectarine | 1 | 7 | 45 | 0.408 | 104 |
104257 | Quince | 1/0 | 7 | 60 | 0.477 | 136 |
TBA | Orange | 2/0 | 7 | 60 | 0.522 | 167 |
104273 | Fig | 3/0 | 7 | 60 | 0.57 | 205 |
104281 | Olive | 4/0 | 7 | 60 | 0.626 | 253 |
104299 | Pomegranate | 4/0 | 19 | 60 | 0.632 | 247 |
TBA | Mulberry | 266.8 | 19 | 60 | 0.694 | 305 |
104315 | Annona | 336.4 | 19 | 60 | 0.765 | 377 |
148130 | Chinquapin | 350 | 19 | 60 | 0.778 | 390 |
TBA | Molles | 397.5 | 19 | 80 | 0.861 | 462 |
104331 | Huckleberry | 477 | 37 | 80 | 0.931 | 538 |
104349 | Paw Paw | 556.5 | 37 | 80 | 0.992 | 619 |
202127 | Breadfruit | 636 | 61 | 95 | 1.081 | 715 |
148460 | Persimmon | 795 | 61 | 95 | 1.186 | 877 |
202135 | Grapefruit | 1033.5 | 61 | 95 | 1.326 | 1128 |
TBA | Hornbeam | 4 | 7 | 30 | 310 | 60 |
104547 | Linden | 2 | 7 | 45 | 406 | 99 |
104554 | Oilnut | 1/0 | 7 | 60 | 518 | 159 |
TBA | Waterash | 2/0 | 7 | 60 | 567 | 195 |
104570 | Shellbark | 3/0 | 7 | 60 | 622 | 240 |
TBA | Planetree | 4/0 | 7 | 60 | 683 | 297 |
All dimensions are nominal and subject to normal manufacturing tolerances
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
Code Word | Phase Cond. Size | Neutral Rated Breaking Strength | Allowable Ampacity In Air 75/90°C |
---|---|---|---|
AWG/Kcmil | lb | Amp | |
Apple | 6 | 445 | 105 |
Plum | 6 | 510 | 105 |
Pear | 4 | 710 | 135 |
Apricot | 4 | 790 | 140 |
Cherry | 2 | 1100 | 180 |
Peach | 2 | 1220 | 180 |
Nectarine | 1 | 1470 | 210 |
Quince | 1/0 | 1790 | 240 |
Orange | 2/0 | 2260 | 280 |
Fig | 3/0 | 2740 | 320 |
Olive | 4/0 | 3450 | 370 |
Pomegranate | 4/0 | 3620 | 370 |
Mulberry | 266.8 | 4470 | 430 |
Annona | 336.4 | 5540 | 495 |
Chinquapin | 350 | 5751 | 506 |
Molles | 397.5 | 6400 | 545 |
Huckleberry | 477 | 7820 | 610 |
Paw Paw | 556.5 | 8950 | 670 |
Breadfruit | 636 | 10500 | 720 |
Persimmon | 795 | 12900 | 825 |
Grapefruit | 1033.5 | 16500 | 970 |
Hornbeam | 4 | 1360 | 145 |
Linden | 2 | 2160 | 190 |
Oilnut | 1/0 | 3440 | 250 |
Waterash | 2/0 | 4160 | 290 |
Shellbark | 3/0 | 5240 | 335 |
Planetree | 4/0 | 6610 | 385 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
Revision: 1.000.007
Updated On: Dec. 31, 2024, 11:09 p.m. UTC