SPEC 83224

Triplex Poly Service Drop. AAAC 6201 Alloy Reduced Neutral - Messenger

Aluminum Conductors With Polyethylene Insulation.

...

Construction:

  1. Conductor:Conductors are stranded, compressed 1350-H19 aluminum
  2. Insulation:Polyethylene (PE)
  3. Messenger:AAAC Neutral

Applications and Features:

Used to supply power, usually from a pole-mounted transformer, to the user's service head where connection to the service entrance cable is made. To be used at voltages of 600 volts phase-to-phase or less and at conductor temperatures 90°C for polyethylene (PE) insulated conductors.

Specifications:

  • ASTM B230 Aluminum, 1350-H19 Wire for Electrical Purposes
  • ASTM B231 Standard Specification for Concentric-Lay-Stranded Aluminum 1350 Conductors
  • ASTM B400 Standard Specification for Compact Round Concentric-Lay-Stranded, Aluminum 1350 Conductors
  • ASTM B901 Standard Specification for Compressed Round Stranded Aluminum Conductors Using Single Input Wire Construction. (The number of strands for both phase and neutral may differ)
  • ICEA S-76-474 Standard for Neutral-Supported Power Cable Assemblies with Weather-Resistant Extruded Insulation Rated 600V
  • Table 1 – Weights and Measurements
    Code WordPhase Cond. SizePhase StrandDia. Over Phase ConductorPhase Insul. ThicknessDia. Over Phase InsulationNeutral Cond. SizeNeutral StrandApprox. ODApprox. Weight
    AWG/KcmilNo.inchmilinchAWG/KcmilNo.inchlb/1000ft
    Artemia4Solid0.204300.264670.572190
    Crab470.225300.285670.618198
    Solaster270.282450.372470.806328
    Echinus1/0190.361600.481271.041535
    Sandcrab1/0190.361600.481271.041535
    Sipho2/0190.405600.525171.136652
    Crayfish2/0190.405600.525171.136652
    Fulgar3/0190.456600.5761/071.246797
    Arca4/0190.512600.6322/071.367978
    All dimensions are nominal and subject to normal manufacturing tolerances
    1. The actual number of strands may differ for single input wire per ASTM B901
    Table 2 – Electrical and Engineering Data
    Code WordPhase Cond. SizeNeutral Rated Breaking StrengthDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzGMRAllowable Ampacity In Air 90°C
    AWG/KcmillbΩ/1000ftΩ/1000ftΩ/1000ftftAmp
    Artemia411100.2580.3100.0480.007100 / 115
    Crab411100.4240.5110.0480.007100 / 115
    Solaster217600.2660.3200.0450.008135 / 150
    Echinus1/028000.1670.2010.0440.011180 / 205
    Sandcrab1/028000.1670.2010.0440.011180 / 205
    Sipho2/035300.1330.1590.0430.013210 / 235
    Crayfish2/035300.1330.1590.0430.013210 / 235
    Fulgar3/042700.1050.1260.0420.014240 / 270
    Arca4/053900.0840.1000.0410.016280 / 315
    Notes:
    1. DC resistances include a 1% length factor for plexing.
    2. Inductive reactance assumes the neutral is carrying current.
    3. Phase conductors assumed to be reverse lay stranded, compressed construction.
    4. Phase spacing assumes cables are touching.
    5. Resistances shown are for the phase conductor only.
    6. Sizes of AAAC neutrals are not the AAAC size, but are the size of an ACSR of equal diameter.
    7. Ampacity based on conductor temperature of 90°; ambient temperature of 40°C; emissivity 0.9; 2 ft./sec. wind in sun.

    Revision: 1.000.000

    Updated On: July 3, 2024, 9:53 p.m. UTC