SPEC 83221

Triplex XLPE Service Drop. AAAC 6201 Alloy Neutral - Messenger

Aluminum Conductors With Crosslinked Polyethylene Insulation.

...

Construction:

  1. Conductor:Conductors are stranded, compressed 1350-H19 aluminum
  2. Insulation:Cross Linked Polyethylene (XLPE)
  3. Messenger:AAAC Neutral

Applications and Features:

Used to supply power, usually from a pole-mounted transformer, to the user's service head where connection to the service entrance cable is made. To be used at voltages of 600 volts phase-to-phase or less and at conductor temperatures 90°C for crosslinked polyethylene (XLP) insulated conductors.

Specifications:

  • ASTM B230 Aluminum, 1350-H19 Wire for Electrical Purposes
  • ASTM B231 Standard Specification for Concentric-Lay-Stranded Aluminum 1350 Conductors
  • ASTM B400 Standard Specification for Compact Round Concentric-Lay-Stranded, Aluminum 1350 Conductors
  • ASTM B901 Standard Specification for Compressed Round Stranded Aluminum Conductors Using Single Input Wire Construction. (The number of strands for both phase and neutral may differ)
  • ICEA S-76-474 Standard for Neutral-Supported Power Cable Assemblies with Weather-Resistant Extruded Insulation Rated 600V
  • Table 1 – Weights and Measurements
    Stock NumberCode WordPhase Cond. SizePhase StrandDia. Over Phase ConductorPhase Insul. ThicknessDia. Over Phase InsulationNeutral Cond. SizeNeutral StrandApprox. ODApprox. Weight
    AWG/KcmilNo.inchmilinchAWG/KcmilNo.inchlb/1000ft
    TBAMINEX6SOLID0.162450.252670.54489
    152645HIPPA670.178450.489670.579106
    TBAPRAWN4SOLID0.204450.294470.635134
    105080BARNACLE470.225450.59470.68158
    105098SHRIMP270.283450.717270.807240
    484828LOBSTER270.283600.751270.871255
    105114LEDA1/090.362600.91/071.02385
    105106GAMMARUS1/070.362600.911/071.03386
    105122DUNGENESE2/070.405601.0062/071.126477
    TBACYCLOPS2/0190.405600.5252/071.134415
    TBAFLUSTRA3/0190.456600.5763/071.244521
    105130LEPAS4/0180.512601.2154/071.335726
    All dimensions are nominal and subject to normal manufacturing tolerances
    1. The actual number of strands may differ for single input wire per ASTM B901
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Code WordPhase Cond. SizeNeutral Rated Breaking StrengthDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzGMRAllowable Ampacity In Air 75/90°C
    AWG/KcmillbΩ/1000ftΩ/1000ftΩ/1000ftftAmp
    MINEX611100.4110.5120.0510.06775/85
    HIPPA611100.6740.840.0510.06775/85
    PRAWN417600.2580.3210.0480.084100/115
    BARNACLE40.4240.5280.0480.084100/115
    SHRIMP228000.2660.3310.0450.105135/150
    LOBSTER20.2660.3310.0450.105135/150
    LEDA1/042700.1670.2080.0440.139180/205
    GAMMARUS1/042700.1670.2080.0440.139180/205
    DUNGENESE2/053900.1330.1660.0430.156210/235
    CYCLOPS2/053900.1330.1660.0430.156210/235
    FLUSTRA3/067900.1050.1310.0420.175240/270
    LEPAS4/085600.0840.1050.0410.197280/315
    Notes:
    1. DC resistances include a 1% length factor for plexing.
    2. Inductive reactance assumes the neutral is carrying current.
    3. Phase conductors assumed to be reverse lay stranded, compressed construction.
    4. Phase spacing assumes cables are touching.
    5. Resistances shown are for the phase conductor only.
    6. Sizes of AAAC neutrals are not the AAAC size, but are the size of an ACSR of equal diameter.
    7. Ampacity based on conductor temperature of 90°; ambient temperature of 40°C; emissivity 0.9; 2 ft./sec. wind in sun.

    Neutral Code Word

    Size-StrandsCode WordOD (inches)
    #6-7Akron0.198
    #4-7Alton0.250
    #2-7Ames0.316
    1/0-7Azusa0.398
    2/0-7Anaheim0.447
    3/0-7Amherst0.502
    4/0-7Alliance0.563